38
12-4. TROUBLESHOOTING CRITERION OF MAIN PARTS
MUFZ-KW25VGHZ MUFZ-KW35VGHZ MUFZ-KW50VGHZ MUFZ-KW60VGHZ
Part name
Check method and criterion
Figure
Defrost thermistor (RT61)
Fin temperature
thermistor (RT64)
Ambient temperature
thermistor (RT65)
Outdoor heat exchanger
temperature thermistor
(RT68)
Measure the resistance with a tester.
Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Discharge temperature
thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the
thermistor with your hands to warm it up.
Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester.
(Temperature: -10 to 40°C)
Normal (Ω)
MUFZ-KW25VGHZ
MUFZ-KW35VGHZ
MUFZ-KW50VGHZ
MUFZ-KW60VGHZ
U-V
U-W
V-W
0.82 - 1.11
0.87 - 1.18
W
U
V
WHT
RED BLK
Outdoor fan motor
Measure the resistance between lead wires using a tester.
(Temperature: -10 ~ 40°C)
Color of lead wire
Normal (Ω)
MUFZ-KW25VGHZ
MUFZ-KW35VGHZ
MUFZ-KW50VGHZ
MUFZ-KW60VGHZ
RED – BLK
BLK – WHT
WHT – RED
32 - 43
25 - 34
W
U
V
WHT
RED BLK
R.V. coil (21S4)
Measure the resistance using a tester. (Temperature: -10 to 40°C)
Normal (kΩ)
MUFZ-KW25VGHZ
MUFZ-KW35VGHZ
MUFZ-KW50VGHZ
MUFZ-KW60VGHZ
1.41 - 2.00
1.17 - 1.66
Expansion valve coil
(LEV)
Measure the resistance using a tester. (Temperature: -10 to 40°C)
Color of lead wire
Normal (Ω)
RED – ORN
37 - 54
RED – WHT
RED – BLU
RED – YLW
RED
(+12V)
YLW
BLU
WHT
ORN
LEV
Defrost heater
Measure the resistance using a tester. (Temperature: -10 to 40°C)
Normal (Ω)
MUFZ-KW25VGHZ
MUFZ-KW35VGHZ
MUFZ-KW50VGHZ
MUFZ-KW60VGHZ
802 - 990
376 - 461
OBH895