Left lamp
of the
OPERATION
INDICATOR
lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit
failure mode
recall function
11-time fl ash
2.5 seconds
OFF
Bus-bar voltage (DC)
8-time fl ash
2.5 seconds OFF
Bus-bar voltage of inverter cannot be
detected normally.
• Refer to 11-5. "How
to check inverter/
compressor".
—
○
Each phase current of
compressor
9-time fl ash
2.5 seconds OFF
Each phase current of compressor
cannot be detected normally.
14-time fl ash
or more
2.5 seconds
OFF
Stop valve (Closed valve)
14-time fl ash
2.5 seconds OFF
Closed valve is detected by
compressor current.
• Check the stop valve.
○
○
4-way valve/
Pipe temperature
16-time fl ash
2.5 seconds OFF
The 4-way valve does not work
properly.
The indoor coil thermistor detects an
abnormal temperature.
• Check the 4-way
valve.
• Replace the inverter
P.C. board.
Outdoor refrigerant system
abnormality
17-time fl ash
2.5 seconds OFF
A closed valve and air trapped in the
refrigerant circuit are detected based
on the temperature sensed by the
indoor and outdoor thermistors and the
current of the compressor.
• Check for a gas leak
in a connecting piping
etc.
• Check the stop valve.
• Refer to 11-5.
“Check of outdoor
refrigerant circuit”.
○
○
NOTE:
Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (11-3.).
OBH668E
Содержание MUFZ-KJ25VEHZ
Страница 8: ...8 WIRING DIAGRAM 6 MUFZ KJ25VEHZ E1 ER1 ET1 MUFZ KJ35VEHZ E1 ER1 ET1 OBH668E ...
Страница 9: ...9 MUFZ KJ25VEHZ E2 ER2 ET2 MUFZ KJ35VEHZ E2 ER2 ET2 OBH668E ...
Страница 10: ...10 MUFZ KJ50VEHZ E1 ER1 ET1 OBH668E ...
Страница 11: ...11 MUFZ KJ50VEHZ E2 ER2 ET2 OBH668E ...
Страница 49: ...49 2 Relay P C board MUFZ KJ50VEHZ To inverter P C board CN681 CN680 CN60 L68B L68A 10 VDC OBH668E ...