25
Start
Indoor unit
operates.
Outdoor unit
does not
operate.
Indoor unit does
not receive
the signal from
remote controller.
OPERATION INDICATOR
lamp on the indoor unit is
flashing ON and OFF.
Outdoor unit
operates only
in Test Run
operation.
Outdoor unit
does not
operate
even in
Test Run
operation.
Indoor unit
operates, when
EMERGENCY
OPERATION
switch is pressed.
Indoor unit
does not operate,
when
EMERGENCY
OPERATION
switch is pressed.
Check room
temperature
thermistor.
Refer to 9-7.
"Test point
diagram and
voltage".
Refer to
"How to check
inverter/
compressor".
Refer to 9-6.
"Check of
remote controller,
display receiver
P.C. board and
indoor control
P.C. board".
1. Check indoor / outdoor
connecting wire.
(Check if the power
is supplied to the
indoor unit.)
2. Refer to 9-6.
"Check of indoor
electronic control
P.C. board and indoor
fan motor".
Unit does
not operate
normal
operation in
COOL or
HEAT mode.
Refer to
"Check of
R.V. coil".
Left lamp
Flash ON and
OFF at
0.5-second
intervals
Cause:
Indoor/
Outdoor unit
0LVZLULQJ
or trouble
of serial signal
Left lamp
2-time flash
Cause:
Indoor unit
7URXEOHRI
room temp-
erature/
indoor coil
thermistor
Left lamp
3-time flash
Cause:
Indoor unit
7URXEOHRI
indoor fan
motor
Left lamp
5-time flash
Cause:
Outdoor unit
2XWGRRU
power
system
abnormality
Left lamp
6-time flash
Cause:
Outdoor unit
7URXEOHRI
thermistor
in outdoor
unit
Left lamp
7-time flash
Cause:
Outdoor unit
7URXEOHRI
outdoor
control
system
Check room
temperature
thermistor
and indoor
coil thermis-
tor.
Refer to 9-7.
"Test point
diagram and
voltage".
Refer to
"How to check
the inverter/
compressor".
Refer to
"Check of
outdoor
thermistors".
Replace the
inverter P.C.
board or
the outdoor
electronic
control P.C.
board.
Left lamp
14-time flash
or more
Cause:
Outdoor unit
2WKHU
abnormality
Check
"Flow chart of
the detailed
outdoor unit
failure mode
recall function."
Refer to 9-6.
"How to
check
miswiring
and serial
signal error
(when
outdoor unit
does not
work)".
Refer to 9-6.
"Check of
indoor fan
motor".
Left lamp
4-time flash
Cause:
Indoor unit
7URXEOHRI
indoor unit
control
system
Replace the
indoor
electronic
control
P.C. board.
Refer to outdoor unit service manual.
Indoor unit operates.
Outdoor unit does
not operate normally.
If blinking of OPERATION
INDICATOR lamp cannot be
checked, it can be checked with
failure mode recall function.
"Test Run operation" means the
operation within 30 minutes after
EMERGENCY OPERATION switch
is pressed.
9-3. INSTRUCTION OF TROUBLESHOOTING
2%+%
Содержание MUFZ-KJ-NAHZ Series
Страница 3: ...3 1 TECHNICAL CHANGES MFZ KJ09NA U1 MFZ KJ12NA U1 MFZ KJ15NA U1 MFZ KJ18NA U1 1 New model 2 ...
Страница 7: ...7 4 OUTLINES AND DIMENSIONS MFZ KJ09NA MFZ KJ12NA MFZ KJ15NA MFZ KJ18NA Unit inch 2 ...
Страница 8: ...8 MFZ KJ09NA MFZ KJ12NA MFZ KJ15NA MFZ KJ18NA 5 WIRING DIAGRAM 2 ...
Страница 41: ...41 2 ...