19
TROUBLESHOOTING
11
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
(1) Check the power supply voltage.
(2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during service.
(1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane has completely closed, turn off the breaker.
(2) Be sure to unplug the power cord before removing the air inlet grille, the front panel, the cabinet, the top panel and
the electronic control P.C. boards.
(3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
(4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
(1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
(2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and
the components for bursting and discoloration.
(3) When troubleshooting, refer to the flow chart and the check table on page 20 and 21.
MUCFH-A18WV -
MUCFH-A24WV -
E1
E1
OB337B--1.qxp 05.7.6 11:00 AM Page 19