27
10-5. TROUBLE CRITERION OF MAIN PARTS
MSZ-FD25VA MSZ-FD25VAS MSZ-FD35VA MSZ-FD35VAS MSZ-FD50VA MSZ-FD50VAS
Part name
Check method and criterion
Figure
Room temperature ther-
mistor (RT11)
Indoor coil thermistor
(RT12, RT13)
Measure the resistance with a tester.
Refer to 10-7. "Test point diagram and voltage", "Indoor electronic control
P.C. board", for the chart of thermistor.
Indoor fan motor (MF)
Check 10-6. .
Horizontal vane motor
(MV1)
Vertical vane motor
(MV2)
i-see Sensor motor
(MT)
Measure the resistance between the terminals with a tester.
(Part temperature 10 ~ 30°C)
Color of the lead wire
Normal
Horizontal vane motor (MV1)
BRN - other one
313 ~ 375
Ω
Vertical vane motor (MV2)
268 ~ 322
Ω
i-see Sensor motor (MT)
223 ~ 268
Ω
i-see Sensor (RR)
Cover the i-see Sensor with black vinyl tape. Then, turn ON the power
supply. (i-see Sensor is energized.) Measure the voltage between connector
terminals of i-see Sensor with a tester.
(Part temperature 10 ~ 40°C)
i-see Sensor connector terminals
Normal range
(GND) - (+)
1.874 ~ 3.387 VDC
(+) - (GND)
1.010 ~ 1.420 VDC
NOTE
: Pay attention to static electricity.
PLASMA electrode unit
Check 10-6.
RED
YLW
BRN
ORN
GRN
ROTOR
Cover the i-see
Sensor with
black vinyl tape.
i-see Sensor
i-see Sensor P.C. board
Black vinyl tape
connector
4
3
2(GND)
1