26
L AREA R
POWER CLEAN PLASMA
No. Abnormal
point
Operation indicator lamp
Symptom
Condition
Correspondence
1
Attachment
of the hori-
zontal vane
All lamps
fl
ash at the same time.
0.5-second ON
0.5-second OFF
Indoor unit and
outdoor unit do
not operate.
The electricity is not conducted to the inter-
lock switch (Fan) of the horizontal vane.
Refer to 10-6. "Check of in-
stallation of the horizontal vane".
•
L AREA R
POWER CLEAN PLASMA
No.
Abnormal
point
Operation indicator lamp
Symptom
Condition
Correspondence
1
PLASMA
control
PLASMA lamp
fl
ashes.
2-time
fl
ash
2.5-second OFF
Indoor unit and
outdoor unit do
not operate.
PLASMA operation can not be turned OFF
even if the PLASMA operation is turned OFF
with remote controller.
Refer to 10-6. ”Check of
PLASMA operation”.
•
L AREA R
POWER CLEAN PLASMA
No.
Abnormal
point
Operation indicator lamp
Symptom
Condition
Correspondence
1
MXZ type
Operation
mode
setting
POWER lamp is lighted.
AREA lamps
fl
ash.
2.5-second OFF
Outdoor unit
operates but
indoor unit does
not operate.
The operation mode of the each indoor unit
is differently set to COOL (includes DRY) and
HEAT at the same time, the operation mode
of the indoor unit that has operated at
fi
rst has
the priority.
Unify the operation mode.
Refer to outdoor unit service
manual.
•