5. Removing the compressor. (A,B)
(1) Remove the cabinet. (Refer to 1)
(2) Remove the relay panel. (Refer to 2)
(3) Remove the terminal cover.
(4) Pull out lead from the compressor.
(5) Remove the suction pipe welded section and discharge
pipe welded section using a burner. Pull out when the
welding melts.
(6) Remove the sound proof felt.
(7) Remove the compressor set nuts.
(8) Remove the compressor.
6. Removing the compressor. (C,D)
(1) Remove the cabinet. (Refer to 1)
(2) Remove the relay panel. (Refer to 2)
(3) Remove the screws fixing rear panel. (Refer to photo 2)
(4) Remove the rear panel.
(5) Remove the terminal cover.
(6) Pull out lead from the compressor.
(7) Remove the suction pipe welded section and discharge
pipe welded section using a burner. Pull out when the
welding melts.
(8) Remove the sound proof felt.
(9) Remove the compressor set nuts.
(10) Remove the compressor.
Photo 7
Sound proof felt Suction pipe
Discharge pipe
Terminal cover