7

3. Mounting and Connection 

  Do not touch or go near the product while the power is ON. Failure to observe this 

could lead to electric shocks or burns. 

 

 

  Make sure that foreign matter does not enter the product during mounting or wiring. 

There is a risk of load damage or fires resulting from contact faults or operation faults.

  Do not use a product that is damaged during transportation, mounting or wiring. 

Failure to observe this could lead to fires or malfunctions. 

  If the mounting screw size is changed or an insufficient number is used, or if the 

mounting onto the mounting rail (IEC35mm width) is incomplete, the product may fall off.

  If the control circuit wiring is long, turning OFF the control voltage may not open the 

circuit because of a stray capacitance. 

  Never manually operate the product in a live state. Failure to observe this could lead 

to electric shocks or burns. 

  If the product is stored in a box, always close the cover while the power is ON. 

Failure to observe this could lead to electric shocks. 

  Do not mount the product on the floor or ceiling. Mounting on the floor or ceiling will 

affect the contact’s conductive performance, operation performance, durability, etc. 

3.1  Mounting 

 Mount the product in a dry place that has little dust, corrosive gas or vibration. 

 The correct mounting position is a vertical surface. However, the product can be mounted vertically up to 

30

 in each direction.   

 Tighten the mounting screw with the mounting torque shown in the Table below. 

Correct 

mounting 

 

Tolerable limits to vertical surface 

Screw 

size 

Mounting screw tightening 

torque 

N

M4 

1.2 to 1.9 

 

 

 

 

 

 

 

 

 

 

 

Horizontal mounting 

(Excluding reversing type) 

If horizontal mounting is unavoidable, turn the product 90

 in 

the counterclockwise direction from the correct vertical 
mounting state, and mount. 
The characteristics will not change much from when the 
product is mounted horizontally but mechanical endurance may 
drop somewhat. 
This mounting method is not available with the reversing type. 
Also, the product cannot be mounted horizontally onto a 
mounting rail (IEC35mm width). 

 Mounting on IEC35mm rail 

The T10 to T32 series and SR-T series can be mounted 
on an IEC35mm wide rail. The rail height is 7.5 or 15mm. 
The rail dimensions are shown on the right.   
When mounting the rail onto a panel, keep the rail 
mounting screw pitch within the values shown on the 
right to maintain the mechanical strength. 
Always maintain the dimensions shown on page 8 as 
these influence temperature rises and product life. 

 

IEC35mm wide rail dimension 

 

Height 7.5mm wide rail: P = 250 or less 
Height 15mm wide rail: P = 500 or less 
For each, the dimensions show the case when the device is mounted on a 
7.5mm high mounting rail with the clearances shown in Table 1 on page 8. 

Interval between mount screws for IEC35mm wide rail

 

CAUTION 

WARNING 

 
Height 7.5mm 
"Z" details 

 
Height 15mm
"Z" details 

 
No burrs 

0.3 or less 

Rail mount screw 

Top 

Bottom

Содержание MS-T Series

Страница 1: ...og please be sure to read the instruction manual prior to use Safety Warning HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN www MitsubishiElectric co jp melfansweb Eco Changes is the Mitsubishi Electric Group s environmental statement and expresses the Group s stance on environmental management Through a wide range of businesses we are helping contribute to the realization...

Страница 2: ......

Страница 3: ... consequence such as a machine malfunction and power supply short circuit Take measures to prevent secondary damage such as personal injuries or fires resulting from this product s failure and malfunction Store the Instruction manual and Precautions for Use enclosed with the product in a place that is easily accessible Always disconnect the product from the power source before starting installatio...

Страница 4: ... welded because of wear there is a risk of fire Always use this product together with a suitable protection device such as a wiring breaker or fuse The coil s voltage fluctuation range is 85 to 110 however if a voltage exceeding 100 is applied for a long time deterioration of the coil insulation will increase and the mechanical durability will drop Always use the coil within an average rated volta...

Страница 5: ... Series 12 3 3 1 Additional auxiliary contact blocks 12 3 3 2 Mechanical interlock kits 13 3 3 3 Surge absorber 15 3 4 Wiring Diagram 16 3 4 1 S T 16 3 4 2 S 2 T 17 3 4 3 TH T KP 18 3 4 4 MSO T KP 18 3 4 5 MSO 2 T KP 19 4 Maintenance and Inspection of Thermal Overload Relay 20 5 Recommended Update Interval 25 6 Maintenance and Inspection Check List 25 7 Troubleshooting List 26 ...

Страница 6: ...nd thermal overload relay operation characteristics are affected by the ambient temperature Relative humidity 45 to 85 RH Note that there must be no dew condensation or freezing Altitude 2 000m or less Vibration 10 to 55Hz 19 6m s2 Max Impact 49m s2 Max Atmosphere Low levels of dust smoke corrosive gas water or sodium When used in a sealed state for a long time contact failure etc can occur Do not...

Страница 7: ...ing of insulator Lower load current Use heat resistant wires Do not use in places where the temperature in the panel exceeds 55 C High humidity Chemical plants Pump room Drop in insulation resistance Corrosion rusting Place in a waterproof type box etc Inspect regulary Corrosion proof treatment MSO YS supported by the S T type magnetic contactor as standard Corrosive gas sodium Petrol refining pla...

Страница 8: ...ity Do not leave the product for long periods in a place with a high humidity level Avoid corrosive gases Do not leave the product in an atmosphere containing sulfuric gas ammonium gas or chloric gas 2 Precautions for transportation Carefully pack and transport Do not drop the product during transportation When transporting the product after mounting and wiring it to a panel pack it carefully The ...

Страница 9: ... can be mounted vertically up to 30 in each direction Tighten the mounting screw with the mounting torque shown in the Table below Correct mounting Tolerable limits to vertical surface Screw size Mounting screw tightening torque N m M4 1 2 to 1 9 Horizontal mounting Excluding reversing type If horizontal mounting is unavoidable turn the product 90 in the counterclockwise direction from the correct...

Страница 10: ...h the B dimension of T10 to T32 allows closely attached mounting when continuing to apply current to the device or when mounting a product high in open close frequency and high utilization on the same rail the device life may be shortened in terms of temperature increase and impact so please keep the space between the devices over the minimum value shown in the above table as much as possible when...

Страница 11: ...To remove the wire completely loosen the screw lift the screw holder lower the crimp terminal toward the terminal and remove the wire Note 1 The terminal screw differs from the MS N series so make sure that differing types of screws are not used Note 2 If the screw holder cannot be lifted completely loosen the terminal screw and then lift it up Note 3 When tightening the screw slightly press down ...

Страница 12: ... conductor thickness stated above because of the length of the terminal screw In case of wiring with two boards used the total value of two boards must be below the value D dimension shown in the table Note 2 In each terminal two wires or two solderless terminals are allowed to be connected Note 3 The cross slot screw with pressure plate of T Series and N Series are same in size but different in p...

Страница 13: ...1 20N m Maximum tightening torque of screwdriver N m Phillips screwdriver made by VESSEL Right hand only Left hand only Both hands No 1 bit 2 5 2 3 2 8 No 2 bit 3 6 3 0 3 9 No 3 bit 4 2 3 9 5 7 1 Hold the screwdriver horizontally and rotate in the tightening direction 2 This is an example for a male having a right arm strength of 500N and left arm strength of 450N ...

Страница 14: ...Types Contact arrangement Method Applicable magnetic contactors and contactor relays Available nunmber of accessories 4a 4NO 3a1b 3NO1NC UT AX4 2a2b 2NO2NC Front crip on S T10 S T12 S T20 S T21 S T25 S T32 SR T5 1 2 Additional auxiliary block mounting procedures UT AX4 Installation Removing Terminal cover Installation and Removing 1 2 Click 1 2 3 Installation Removing ...

Страница 15: ...holes according to the dimensions as shown in clause 3 3 Install the interlock kit in both magnetic contactors as shown in clause 4 4 Fix the magnetic contactors onto mounting surface with screws 5 Provide a direct electrical interlock mutual to the magnetic contactors as shown in clause 4 for the reversing type Use the auxiliary contact on the inner side between the magnetic contactors for the el...

Страница 16: ...ts mounting procedures UT ML11 T10 T12 T20 UN ML21 T21 T25 T32 Torque 0 3 0 5 N m T10 T12 T20 Interlock kit Terminal cover Removing Thread fastening red black Wiring Installation and Removing T21 T25 T32 Coupling block ...

Страница 17: ...eeding the rated voltage 1 Types and applicable magnetic contactors Types Applicable magnetic contactors UT SA21 UT SA22 UT SA23 UT SA25 S T10 S T12 S T20 S T21 S T25 SR T5 2 Applicable voltage range Rated voltage Recommend applicable voltage range Minimum applicable voltage Remarks AC 48V AC24 AC50V DC24 60V AC DC12V UT SA25 AC12V DC12V UT SA21 UT SA23 UT SA25 CR type UT SA23 is exclusive for AC ...

Страница 18: ...16 3 4 Wiring Diagram representative example 3 4 1 S T S T10 1NO S T10 1NC S T12 T20 S T12 T20 2NO S T12 T20 2NC S T21 T25 S T32 ...

Страница 19: ...17 3 4 2 S 2 T S 2 T10 S 2 T12 T20 S 2 T21 T25 S 2 T32 ...

Страница 20: ...18 3 4 3 TH T KP TH T18 T25 TH T18KP T25KP 3 4 4 MSO T KP MSO T10 MSO T10KP MSO T12 T20 MSO T12KP T20KP MSO T21 T25 MSO T21KP T25KP ...

Страница 21: ...19 3 4 5 2 T KP MSO 2 T10 MSO 2 T10KP MSO 2 T12 T20 MSO 2 T12KP T20KP MSO 2 T21 T25 MSO 2 T21KP T25KP ...

Страница 22: ...es Do not disassemble Never touch the inside of the thermal overload relay The thermal overload relay has been configured precisely at Mitsubishi before shipping 2 Fusing of thermal overload relay The thermal overload relay is used to protect the motor from burning It cannot be used as protection against short circuits so if a short circuit occurs replace the thermal overload relay If a current la...

Страница 23: ...l screws Fig 1 3 Press in the thermal overload relay from the B direction and insert the thermal overload relay s notch A to the magnetic contactor s indent Fig 2 4 Turn the thermal overload relay in the direction of arrow C and turn the thermal overload relay notch D to the magnetic contactor s E face Fig 3 4 5 Tighten the main terminal screws 2 T1 4 T2 6 T3 while pressing the thermal overload re...

Страница 24: ...mal overload relay s notch A two places into the magnetic contactor s indents two places Fig 2 4 Turn the thermal overload relay in the direction of arrow B and confirm that the thermal overload relay notch section C one place is fit into the square hole at the indent on the magnetic contactor Fig 3 5 Tighten the main terminal screw while pressing the thermal overload relay toward the magnetic con...

Страница 25: ...current compensation method In the curves in Figures 1 and 2 find the compensation rate at the working ambient temperature Divide the motor s full load current by the identified compensation rate The obtained value is the settling value Example When the TH T25 s ambient temperature is 40 C 55 C inside control panel the compensate rate at the temperature with the minimum scale is 97 according to Fi...

Страница 26: ...a stopper is provided at the switching plate to prevent the setting from being changed easily TH T18 Changeover procedures 1 Remove the thermal overload relay s auxiliary terminal cover Fig 1 2 Cut off the stopper and then press down on the reset bar and slide the switching plate white in the direction of arrow X 3 Mount the terminal cover and confirm that the switching plate is at position A Fig ...

Страница 27: ...ance Visual Breakage Existence of mold breakage discoloration or deformation Per panel all Clamp screw Visual Loosening Are any of the clamp screws loose All Metal sections Visual Rusting corrosion Is there any rust or corrosion All Periodic inspection reference every six months Move ment of movable sections Manual or electric Movement fault Do movable sections move smoothly when operated manually...

Страница 28: ... necessary Replace the switch relay The contact is welded Replace the entire unit check the cause and take measures Dew has condensed on iron core surface Decrease the temperature difference Attraction due to residual magnetism The unit is worn Replace the entire unit The unit has deformed due to heat or mounting stress Replace the entire unit Contacts do not open Does not return There is no excit...

Страница 29: ...s large Check the cause and make modifications The contact s brazed section has fallen off The switching frequency is too high Lower the frequency or replace with a part having a large capacity There is corrosive gas Modify the case or installation position Abnormal wear of contact The wear is fast Simultaneous contact does not take place Set to approx 0 5mm or less Low voltage low current Set to ...

Страница 30: ...e Re select the relay or mount a saturable reactor The application is incorrect pole number change etc Re select for the correct application The ambient temperature has risen Compensate for the temperature or change the mounting position The thermal overload relay trip Occurs when starting The load is inconsistent Correct the load or re select the motor The relay capacity selection is incorrect Re...

Страница 31: ......

Страница 32: ... Magnetic Contactors and Magnetic Starters INSTRUCTION MANUAL To ensure proper use of the products listed in this catalog please be sure to read the instruction manual prior to use Safety Warning HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN www MitsubishiElectric co jp melfansweb ...

Отзывы: