5
For special environment
Special environment
Problem points
General measures
Name Type
Sudden temperature
changes
Rusting or
malfunctioning due
to dew
condensation
(freezing)
Install a space
heater to lower the
relative humidity.
Move the product
to a place with little
temperature
change.
Low temperature
Freezer storage
Low temperature
room
Freezing
Malfunctioning or
rust due to dew
condensation.
Install a space
heater, etc., to
increase the
temperature.
Dry the area.
Consult
Mitsubishi when
the temperature
is –10
C or less.
High temperature
Steel mill
Molding forming
plant
Malfunctioning
Heat resistance of
connected wires
Overheating of
insulator
Lower load
current.
Use heat resistant
wires.
Do not use in
places where the
temperature in the
panel exceeds
55
C.
High humidity
Chemical plants
Pump room
Drop in insulation
resistance
Corrosion, rusting
Place in a
waterproof type
box, etc.
Inspect regulary.
Corrosion-
proof
treatment
MSO-
YS
(supported by the
S-T type
magnetic
contactor as
standard.)
Corrosive gas, sodium
Petrol refining plant
Chemical plant
Coastline
City water pump
room (Chlorine
disinfectant)
Corrosion, rusting
Place
anti-corrosive
product in
corrosion-proof
type box, etc.
Corrosion-
proof
treatment
MSO-
YS
(supported by the
S-T type
magnetic
contactor as
standard.)
Use it in
corrosion-proof
box.
Dus
t, mois
ture
Cement plant
Textile plant
Failure in contact
continuity
Failure in
mechanism
operation
Deterioration of
insulation
Place in a dust-
proof box, etc.