(5) For the applicable wire size and terminal screw tightening torque, refer to Table 2.
(6) Always ground the metal enclosure.
Table 2 Wire size and tightening torque
Model
Terminal dimension and size/type of screw
Main circuit
Operating
circuit
Applicable electric wire
size [
φ
mm, mm
2
]
Connection
conductor
thickness
(D) [mm]
Applicable solderless
terminal size
(JST Cat No.)
Tightening torque of
terminal screw
[N·m]
Standard type
Contactor Relays
Magnetic Contactors
Thermal Overload
Relays
Dimension of
terminal
portion
A x B x C
[mm] (Note 1)
Screw
size
Screw
type
cross slot
screw with
pressure
plate
Main
circuit
Operating
circuit
Main
circuit
(Note 1)
Main circuit
Operating
circuit
Main
circuit
Operating
circuit
SR-T5, T9
–
–
–
M3.5×7.6
–
–
–
–
S-T10, T12, T20
7.5×3.7×4.5 M3.5×7.6
M3.5×7.6
φ
1.6
0.75 to 2.5
1.6
1.25-3.5 to 2-3.5
5.5-S3
0.9 to 1.5
S-T21, T25, T32
10.5×5.2×5.5 M4×10.5
cross slot
screw with
pressure
plate
M3.5×7.6
φ
1.6 - 2.6
1.25 to 6
φ
1.6
0.75 to 2.5
3
1.25-4 to 5.5-4
1.25-3.5 to
2-3.5
1.2 to 1.9
0.9 to 1.5
TH-T18
(Load side)
7.5×4×4 M3.5×7.6
M3.5×7.6
φ
1.6
0.75 to 2.5
2
1.25-3.5 to 2-3.5
5.5-S3
0.9 to 1.5
TH-T25
(Power side / Load side)
10.2×6.8×5/
10.2×5.7×5
M4×10.5/
M4×10.5
cross slot
screw with
pressure
plate
M3.5×7.6
φ
1.6 - 2.6
1.25 to 6
φ
1.6
0.75 to 2.5
2.5
1.25-4 to 5.5-4
1.25-3.5 to
2-3.5
1.2 to 1.9
0.9 to 1.5
Note 1. The dimension of the main circuit terminal is a dimension for board
conductor wiring. (See the right diagram) The board conductor
thickness (D dimension) must be below the allowable connection
conductor thickness stated above because of the length of the
terminal screw. In case of wiring with two boards used, the total
value of two boards must be below the value (D dimension) shown in
the table.
Note 2. In each terminal, two wires or two solderless terminals are allowed to
be connected.
Note 3. The cross slot screw with pressure plate of T Series and N Series are same in size but different in
pressure plate dimension, so please avoid the mixed use of such screws. This may break the
insulation barrier or make the wire likely to fall out.
Note 4. When using IEC60529-based finger safe specification, be sure to use an insulation tube-attached
solderless terminal.
Note 5. Tightening the3 terminal screw excessively without wiring may break the screw and consequently
disable the tightening, so please avoid such excessive tightening.
Note 6. Operational circuits are coil terminals of magnetic contactors and control circuit terminals of
Thermal Overload Relays.
Note 7. Please use swaging tool which is recommended by JST.
Note 8. For the auxiliary a fixed contact elements of the S-T21 and T25 types, these elements could drop
off if its terminal screw is tightened with a screwdriver tilted towards the unit body. Do not tilt the
screwdriver towards the unit body when tightening the screw.
本体
ドライバ
補助a固定接触子
Note 9. Connection to magnetic contactor's load side auxiliary circuit terminal when using magnetic contactor
(MSO-(2
) T10 to T20)
Bend the crimp terminal or wire as shown below and connect.
When connecting two crimp terminals or two wires, use a 0.75 to 1.25mm
2
wire for the "A" wire.
圧着端子の場合
A
サーマルリレー
11
0°
Thermal overload relay
For crimp terminal
Unit body
Screwdriver
Auxiliary a fixed contact element
Содержание MS-T Series
Страница 2: ......
Страница 19: ...17 3 4 2 S 2 T S 2 T10 S 2 T12 T20 S 2 T21 T25 S 2 T32 ...
Страница 21: ...19 3 4 5 2 T KP MSO 2 T10 MSO 2 T10KP MSO 2 T12 T20 MSO 2 T12KP T20KP MSO 2 T21 T25 MSO 2 T21KP T25KP ...
Страница 31: ......