![Mitsubishi Electric MS-30SV-A1 Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/mitsubishi-electric/ms-30sv-a1/ms-30sv-a1_service-manual_1810351035.webp)
35
Check of LEV (Expansion valve)
G
Replace the
LEV coil.
With remote controller set toward the indoor unit, press
OPERATE/ STOP(ON/ OFF) button and confirm one
beep tone.
LEV operates in full-opening
direction.
Is LEV coil properly fixed to
the body?
Cooling does not operate.
Ok
Do you hear LEV "click,
click·······"?
Do you touch LEV and feel
it vibrate?
Is LEV coil resistance as per
characteristics below?
No
Yes
Yes
Yes
No
LEV (CN 724)
WHT–RED
RED–ORN
YLW–BRN
BRN–BLU
Resistance
30.3
"
~ 37.0
"
Characteristics of LEV coil
No
Properly fix LEV coil to
the body.
Replace the
DEICER P.C. board.
NOTE : After check LEV, do the undermentioned operation.
1. Turn OFF the breaker of the unit and turn ON again.
2. Press the RESET button on the remote controller.
1
During pressing OPERATION SELECT button
on remote controller, press RESET button.
2
First, release RESET button.
(Confirm all displays of remote controller.)
3
Then release OPERATION SELECT button.
1
During pressing OPERATION SELECT
button on remote controller, press
RESET button.
2
First, release RESET button.
(Confirm all displays of remote controller.)
3
Then release OPERATION SELECT button.
AMPM
CLOCK
˚C
AMPM
OB255--2qxp 7/20/00 10:12 AM Page 35