24
NOTE : Opening increases and decreases to be in the target discharge temperature during operation.
Opening
completely
Positioning
Power ON
Opening at starting
Standard opening
Remote
controller
ON
➔
Operation
Thermostat
OFF
Standard opening
Thermostat
ON
Opening in stop
Opening at starting
Operation
Opening in stop
Remote
controller
OFF
Opening
completely
Remote
controller
ON
➔
Positioning
Opening at starting
Standard opening
Operation
Time
LEV opening
(2) LEV time chart
8-10. Function of soft start relay
Soft start relay will chop some starting current.
Starting current is reduced as shown in the following figures.
(Sec.)
(A)
WITH SOFT START RELAY
WITHOUT SOFT START RELAY
9
SERVICE FUNCTIONS
9-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
9-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.
The time will be shortened as follows. (Refer to page 37.)
Set time : 1-minute
➔
1-second
Set time : 3-minute
➔
3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
MS-30SV -
A1
OB255--1qxp 7/20/00 10:09 AM Page 24