3
Outdoor unit model
SUZ-KA09NA SUZ-KA12NA
SUZ-KA15NA
SUZ-KA15NA
Power supply
V , phase , Hz
208/230 , 1 , 60
Max. fuse size (time delay)
A
15
Min. circuit ampacity
A
12
12
12
14
Fan motor
F.L.A
0.50
0.93
Compressor
Model
KNB073FQDHC KNB092FQAHC
SNB130FQBH
R.L.A 6.6
6.6
7.4
10.0
L.R.A 8.2
8.2
9.3
12.5
Refrigeration oil oz. (Model)
10.8 (NEO22)
15.2 (NEO22)
Refrigerant control
Linear expansion valve
Sound level
1
Cooling dB(A)
46
49
49
54
Heating dB(A)
50
51
51
56
Defrost method
Reverse cycle
Dimensions
W
in.
31-1/2
33-1/16
D
in.
11-1/4
13
H
in.
21-5/8
33-7/16
Weight Ib.
66
77
80
119
External
fi
nish
Munsell 3Y 7.8/1.1
Control voltage (by built-in transformer)
VDC
12 - 24
Refrigerant piping
Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in.
1/4
(0.0315)
Gas
in.
3/8 (0.0315)
1/2 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor &
outdoor units
Height difference
ft.
40
50
Piping length
ft.
65
100
Refrigerant charge (R410A)
1 lb. 16 oz.
2 lb. 9 oz.
3 lb. 16 oz.
NOTE
: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80
˚
FDB, 67
˚
FWB, Outdoor: 95
˚
FDB, (75
˚
FWB)
(Heating) — Indoor: 70
˚
FDB, 60
˚
FWB, Outdoor: 47
˚
FDB, 43
˚
FWB
3
SPECIFICATION
OPERATING RANGE
(1) POWER SUPPLY
Rated voltage
Guaranteed voltage (V)
Outdoor unit
208/230 V
1 phase
60 Hz
Min. 187
208
230
Max. 253