12

1. Insert the drain hose (accessory) into the drain port (insertion margin: 25 mm

[1 in]).
(The drain hose must not be bent more than 45° to prevent the hose from break-
ing or clogging.)
(Attach the hose with glue for the hard vinyl chloride pipe, and fix it with the band
(accessory).)

2. Attach the drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE, field supplied).

(Attach the pipe with glue for the hard vinyl chloride pipe, and fix it with the band
(accessory).)

3. Perform insulation work on the drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE)

and on the socket (including elbow).

4. Check the drainage. (Refer to [Fig. 6-13])
5. Attach the insulating material (accessory), and fix it with the band (accessory) to

insulate the drain port.

[Fig. 6-11] (P.4)

A

Indoor unit

B

Pipe cover (60 mm [3/8 in]) (accessory)

C

Tie band (accessory)

D

Visible part

E

Insertion margin

F

Drain hose (accessory)

G

Drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE, field supplied)

H

Insulating material (field supplied)

I

Tie band (accessory)

J

Max.180 ± 5 mm [7-3/32 ± 7/32 in]

K

No gap. The joint of the insulation material must meet at the top.

6. Refrigerant piping work

[Drainage by gravity]

1. Insert the drain hose (accessory) into the drain port.

(The drain hose must not be bent more than 45° to prevent the hose from breaking
or clogging.)
The connecting part between the indoor unit and the drain hose may be discon-
nected at the maintenance. Fix the part with the accessory band, not be adhered.

2. Attach the drain pipe (O.D. ø32 PVC TUBE, field supplied).

(Attach the pipe with glue for the hard vinyl chloride pipe, and fix it with the band
(accessory).)

3. Perform insulation work on the drain pipe (O.D. ø32 PVC TUBE) and on the socket

(including elbow).

6.6. Confirming drain discharge

s

s

s

s

s

Make sure that the drain-up mechanism operates normally for discharge
and that there is no water leakage from the connections.

• Be sure to confirm the above when in heating operation.
• Be sure to confirm the above before ceiling work is done in the case of a new

construction.

1. Remove the water supply port cover on the same side as the indoor unit piping.
2. Fill water into the feed water pump using a feed water tank. Be sure to put the end

of the pump or tank in a drain pan. (If the insertion is incomplete, water may flow
over the machine.)

3. Perform the test run in cooling mode, or turn on the switch SWE on the controller

circuit board. (The drain pump and the fan are forced to operate without any re-
mote controller operation.) Make sure using a transparent hose that drain is dis-
charged.

4. After confirmation, cancel the test run mode, and turn off the main power.

 

When

the switch SWE has been turned on, turn it off, and attach the water supply port
cover into its original position.

[Fig. 6-13] (P.4)

A

Insert pump's end 2 to 4 cm [13/16 to 1-19/32 in].

B

Remove the water supply port.

C

About 2000 liters

D

Water

E

Filling port

F

Screw

[Fig. 6-14] (P.4)

<Indoor board>

SWE

SWE

ON

OFF

ON

OFF

SWE

SWE

ON

OFF

ON

OFF

[Fig. 6-12] (P.4)

 * Drainage by gravity

A

Indoor unit

B

Pipe cover (30 mm [3/16 in]) (accessory)

C

Tie band (accessory)

D

Band fixing part

E

Insertion margin

F

Drain hose (accessory)

G

Drain pipe (O.D. ø32 PVC TUBE, field supplied)

H

Insulating material (field supplied)

I

Max. 145 ± 5 mm

7. Duct work

• When connecting ducts, insert a canvas duct between the main body and the duct.
• Use non-combustible duct components.

 Caution:

The sound from the intake will increase dramatically if intake 

A

A

A

A

A

 is fitted

directly beneath the main body. Intake 

A

A

A

A

A

 should therefore be installed as

far away from the main body as possible.
Particular care is required when using it with bottom inlet specifications.

Install sufficient thermal insulation to prevent condensation forming on
outlet duct flanges and outlet ducts.

To connect the air conditioner main body and the duct for potential equali-
zation.

The distance between the inlet grille and the fan should be at least over 850
mm [33-15/32 in] or more.
If it is less than 850 mm [33-15/32 in], install a safety guard so the fan can-
not be easily accessed.

[Fig. 7-1] (P.5)

A

Air inlet

B

Air outlet

C

Access door

D

Ceiling

E

Canvas duct

F

Air filter

G

Inlet grille

8.1. Power supply

Electrical specification

Input capacity Main Switch/Fuse (A)

Power supply

SEZ-KD09

SEZ-KD12

SEZ-KD15

SEZ-KD18

(1 phase ~/N, 208/230V, 60Hz)

10

10

20

20

 Warning:

• The compressor will not operate unless the power supply phase connection

is correct.

• Ground protection with a no-fuse breaker (ground leakage breaker) is usu-

ally installed for 

D

D

D

D

D

.

• The connection wiring between the outdoor and indoor units can be extended

up to a maximum of 50 m [164 ft], and the total extension including the crosso-
ver wiring between rooms is a maximum of 80 m [262 ft].

Provide switch with at least 3 mm [1/8 in] contact separation in each pole.
* Label each breaker according to purpose (heater, unit etc.).

[Fig. 8-1] (P.5)

A

Indoor unit

B

Outdoor unit

C

Wired remote controller

D

Main switch/fuse

E

Ground wire

8.2. Indoor wire connection

Work procedure
1. Remove two screws to detach the electric component cover.
2. Route each cable through the wiring intake into the electric component box. (Pro-

cure power cable and in-out connecting cable locally and use remote control cable
supplied with the unit.)

3. Securely connect the power cable and the in-out connecting cable and the remote

control cable to the terminal blocks.

4. Secure the cables with clamps inside the electric component box.
5. Reattach the electric component cover.
• Attach power supply cable and indoor/outdoor cable to control box by using buffer

bushing for tensile force. (PG connection or the like.)

 Warning:

• Attach the electrical part cover securely. If it is attached incorrectly, it could

result in a fire or electric shock due to dust, water, etc.

• Use the specified indoor/outdoor unit connecting wire to connect the indoor

and outdoor units. Attach the wire to the terminal block securely so that stress
is not applied to the terminal block connection.  Incomplete connection or
fixing of the wire could result in a fire.

8. Electrical work

Содержание Mr. SLim SEZ-KD18NA

Страница 1: ...this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER English Français MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte POUR L INSTALLATEUR ...

Страница 2: ...or more 3 10 mm 13 32 in or more 4 300 mm 11 13 16 in or more B C D A F G 3 4 E A 50 150 1 31 32 5 29 32 450 17 23 32 450 17 23 32 49 1 15 16 625 24 5 8 777 30 19 32 20 13 16 23 29 32 C B A D B E 200 7 7 8 1 2 90 3 9 16 57 2 1 4 Y X L W A Z A B A Unit mm in Model SEZ KD09 SEZ KD12 15 SEZ KD18 A 700 27 9 16 900 35 7 16 1100 43 5 16 B 752 29 5 8 952 37 1 2 1152 45 3 8 C 798 31 7 16 998 39 5 16 1198 ...

Страница 3: ...on field supplied I Pull J Flare nut A B C D F G E M L E F L AG H H K L J I J O O N N 20 20 20 20 Fig 6 3 Fig 6 6 Fig 6 4 Fig 6 5 a Flare nut b Copper tube a Burr b Copper tube pipe c Spare reamer d Pipe cutter Fig 6 7 Fig 6 8 a Flaring tool b Die c Copper tube d Flare nut e Yoke a Smooth b Inside is shiny without any scratches c Even length d Too much e Tilted f Scratch on flared plane g Cracked ...

Страница 4: ... G K J F I A 25 1 25 1 35 1 13 32 A Indoor unit B Pipe cover 60 mm 3 8 in accessory C Tie band accessory D Visible part E Insertion margin F Drain hose accessory G Drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supplied H Insulating material field supplied I Tie band accessory J Max 180 5 mm 7 3 32 7 32 in K No gap The joint section of the insulation material must meet at the top Unit mm in Fig 6 1...

Страница 5: ... connecting cable F Washer accessory G Tensile force H Use ordinary bushing I Remote controller cable A Terminal block for indoor outdoor unit connecting B Terminal block for remote controller C Indoor outdoor unit connecting cable D Remote controller cable Fig 8 2 3 Fig 8 2 4 A Terminal block box B Knockout hole C Remove A Screw holding cover 2pcs B Cover Fig 8 2 1 Fig 8 2 2 A B C S3 S2 S1 1 2 S1...

Страница 6: ... I I I H B J H B 1 B 2 Fig 8 5 8 A AB TB6 B A To the terminal block on the indoor unit B TB6 No polarity Fig 8 6 Fig 8 7 8 2 8 4 46 1 13 16 30 1 3 16 120 4 3 4 83 5 3 5 16 A B C 30 1 3 16 30 1 3 16 A Remote controller B Required clearances for the remote controller C Installation pitch Fig 8 4 Fig 8 3 A Indoor terminal block B Ground wire green yellow C Indoor outdoor unit connecting cable 3 core ...

Страница 7: ...MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF TEST RUN COOL HEAT A F C E D B M I H G C F SIMPLE PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF B C A E D A ON OFF button B Test run display C Indoor temperature liquid line temperature display D ON OFF lamp E Power display A CHECK button B Refrigerant address C...

Страница 8: ...l work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for...

Страница 9: ...vice space Units should be installed by licensed contractor accordingly to local code require ments For outdoor units to be connected refer to the Installation Manual that comes with the units 3 4 Indoor unit accessories The unit is provided with the following accessories No Name Quantity 1 Pipe cover for refrigerant piping joint 120 mm 3 4 in Small diameter 1 2 Pipe cover for refrigerant piping j...

Страница 10: ...oke Carry out flaring work using flaring tool as shown below Dimension Pipe diameter A mm in mm in When the tool for R410A is used B mm in Clutch type 6 35 1 4 0 to 0 5 0 to 1 32 9 1 3 8 9 52 3 8 0 to 0 5 0 to 1 32 13 2 17 32 12 7 1 2 0 to 0 5 0 to 1 32 16 6 21 32 15 88 5 8 0 to 0 5 0 to 1 32 19 7 25 32 Firmly hold copper tube in a die in the dimension shown in the table at above 6 2 5 Check Fig 6...

Страница 11: ... Support metal K Air bleeder L Raised M Odor trap Grouped piping D O D ø32 mm 1 1 4 in PVC TUBE E Make it as large as possible About 10 cm 3 15 16 in F Indoor unit G Make the piping size large for grouped piping H Downward slope 1 100 or more I O D ø38 mm 1 1 2 in PVC TUBE for grouped piping 9 mm 3 8 in or more insulation J Up to 550 mm 21 21 32 in N Drain hose accessory O Horizontal or slightly u...

Страница 12: ...OFF ON OFF Fig 6 12 P 4 Drainage by gravity A Indoor unit B Pipe cover 30 mm 3 16 in accessory C Tie band accessory D Band fixing part E Insertion margin F Drain hose accessory G Drain pipe O D ø32 PVC TUBE field supplied H Insulating material field supplied I Max 145 5 mm 7 Duct work When connecting ducts insert a canvas duct between the main body and the duct Use non combustible duct components ...

Страница 13: ... are simultaneously in operation select AL Refer to Function table 2 Fig 8 2 1 P 5 A Screw holding cover 2pcs B Cover Fig 8 2 2 P 5 A Terminal block box B Knockout hole C Remove Fig 8 2 3 P 5 A Use conduit to keep the weight of the cable and external force from being applied to the power supply terminal connector B Indoor outdoor unit connecting cable C Conduit D Terminal block box E Knockout hole...

Страница 14: ...turned on during the op erational season 9 Test run 9 2 Test run 9 2 1 Using wired remote controller 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make sure that cold or warm wind is ...

Страница 15: ...it G Refrigerant gas cylinder operating valve H Refrigerant gas cylinder for R410A with siphon I Refrigerant liquid J Electronic scale for refrigerant charging K Charge hose for R410A L Gauge manifold valve for R410A M Service port 1 Connect gas cylinder to the service port of stop valve 3 way 2 Execute air purge of the pipe or hose coming from refrigerant gas cylinder 3 Replenish specified amount...

Страница 16: ... Veuillez vous assurer d utiliser la pièce fournie ou les pièces spécifiées pour l installation Toute pièce défectueuse utilisée pourrait être la cause d un incendie d un choc électrique de l appareil tombant de sa position etc ce qui résulterait en une blessure ou une fuite d eau Aérez le local en cas de fuite de liquide frigorigène en cours de fonctionne ment Tout contact du liquide frigorigène ...

Страница 17: ... est situé du côté de l arrivée d air Le détecteur d incendie risque de se déclencher par erreur suite à l alimentation en air chaud pendant le fonctionnement du chauffage En cas de présence de produits chimiques sur les lieux comme dans des usines chimiques ou des hôpitaux une étude approfondie s avère nécessaire avant de procéder à l installation de l appareil Certains produits chimiques peuvent...

Страница 18: ...r sur les tuyau tube après ébarbage il est impossible de les fixer après mise en forme conique 6 2 4 Le fraisage Fig 6 6 P 3 a Fraise b Etau c Tube en cuivre d Ecrou évasé e Serrage Effectuez l évasement à l aide de l alésoir selon la méthode suivante Dimensions Diamètre de tuyau A mm in mm in Lors de l utilisation de l outil pour le R410A B mm in Type d embrayage 6 35 1 4 0 à 0 5 0 à 1 32 9 1 3 8...

Страница 19: ...n y a pas d espace ici Diriger les raccords vers le haut 1 Retirer et jeter le bouchon de caoutchouc qui a été inséré à l extrémité de la tuyau terie de l appareil 2 Evaser l extrémité du tuyau de réfrigérant 3 Sur le site extraire l isolation thermique des tuyaux de réfrigérant et replacer l iso lant comme à l origine Précautions concernant le raccordement des tuyaux de réfrigérant s s s s s Touj...

Страница 20: ...principal Il est donc impératif d instal ler l admission A A A A A le plus loin possible du corps principal Faire particulièrement attention lors de son installation pour une admis sion par le bas Utilisez suffisamment d isolation thermique afin d éviter toute condensa tion sur les conduits de sortie et leurs brides Raccordez le corps principal du climatiseur et le conduit afin que leurs potentiel...

Страница 21: ... de connexion de l appareil intérieur extérieur D Câble de la télécommande Effectuez le câblage selon le diagramme en bas et à gauche Veuillez vous procu rer le câble localement Assurez vous que les câbles utilisés sont de la polarité correcte Fig 8 3 P 6 A Bornier intérieur B Fil de mise à la terre vert jaune SEZ KD09 SEZ KD12 SEZ KD15 SEZ KD18 10 10 20 20 8 Installations électriques C Câble de c...

Страница 22: ...e du réfrigérant 3 sur 00 3 Appuyer sur D se met à clignoter sur l affichage du numéro d appareil 4 4 Utiliser le bouton C pour spécifier le numéro d appareil 4 à 01 04 ou AL 5 Appuyer sur la touche E MODE pour spécifier l adresse du réfrigérant numéro d appareil clignote momentanément sur l affichage du numéro de mode 1 6 Appuyez sur la touche F pour régler le numéro de mode 1 sur 08 7 Appuyer su...

Страница 23: ...rer que la résistance entre les terminaux d alimentation électrique et la terre soit au moins de 1 0 MW W W W W s Ne pas effectuer ce test sur les terminaux des câbles de contrôle circuit à basse tension Avertissement Ne pas utiliser le climatiseur si la résistance de l isolation est inférieure à 1 0 MW W W W W Résistance de l isolation Après l installation ou après la coupure prolongée de la sour...

Страница 24: ... 10 1 P 7 A Appareil intérieur B Raccord C Conduite de liquide D Conduit de gaz réfrigérant E Robinet d arrêt F Appareil extérieur G Vanne de fonctionnement du cylindre de réfrigérant H Cylindre de gaz réfrigérant pour R410A avec siphon I Réfrigérant liquide J Echelle électronique pour la charge de réfrigérant K Conduite flexible de chargement pour le R410A L Jauge collectrice pour le R410A M Pris...

Страница 25: ...ne number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KB79K740H02 ...

Отзывы: