background image

14

8. Electrical work

9.1. Before test run

s

After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M

W

W

W

W

W

.

s

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

W

W

W

W

W

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 M

W

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of

the compressor.

2. If the insulation resistance is below 1 M

W

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3. After connecting the wires to the compressor, the compressor will start to warm

up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

W

 after the compressor is warmed

up for two to three hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)

To operate the compressor with refrigerant accumulated in the compressor,
the compressor must be warmed up at least 12 hours to prevent breakdown.

4. If the insulation resistance rises above 1 M

W

, the compressor is not faulty.

 Caution:

• The compressor will not operate unless the power supply phase connection

is correct.

• Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can result in

severe damage to internal parts. Keep the power switch turned on during the op-
erational season.

9. Test run

9.2. Test run

9.2.1. Using wired remote controller

1

Turn on the power at least 12 hours before the test run.

2

Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

Press the [Mode selection] button and switch to the cooling (or heating) mode.

 Make sure that cold (or warm) wind is blown out.

5

Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

Check operation of the outdoor unit fan.

7

Release test run by pressing the [ON/OFF] button. 

 Stop

8

Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the operation
manual for the indoor unit.

[Fig. 9-1] (P.7)

A

ON/OFF button

B

Test run display

C

Indoor temperature liquid line temperature display

D

ON/OFF lamp

E

Power display

F

Error code display

Test run remaining time display

G

Set temperature button

H

Mode selection button

I

Fan speed button

M

TEST button

Function table 1

Select unit number 00

Function table 2

Select unit numbers 01 to 04 or all units (AL [wired remote controller]/07 [wireless remote controller])

*1 When the power supply returns, the air conditioner will start 3 minutes later.

Note:

When the function of an indoor unit were changed by function selection after the end of installation, always indicate the contents by entering a   or other mark in the
appropriate check filed of the tables.

Mode
Filter sign

External static pressure

Settings
100 Hr
2500 Hr
No filter sign indicator
15 Pa (0.06 in.WG)
35 Pa (0.14 in.WG)
50 Pa (0.20 in.WG)
The same as setting of mode no.08
5 Pa (0.02 in.WG) (set mode no. 08 to 1)

Mode no.

Setting no. Initial setting

Check

1

07

2
3
1

08

2
3
1

10

2

Settings
Not available
Available  *1
Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)

Mode no.

Setting no. Initial setting

Check

1

01

2
1

02

2
3
1

03

2
3

Mode
Power failure automatic recovery*1
(AUTO RESTART FUNCTION)
Indoor temperature detecting

LOSSNAY connectivity

Содержание Mr. SLim SEZ-KD18NA

Страница 1: ...this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER English Français MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte POUR L INSTALLATEUR ...

Страница 2: ...or more 3 10 mm 13 32 in or more 4 300 mm 11 13 16 in or more B C D A F G 3 4 E A 50 150 1 31 32 5 29 32 450 17 23 32 450 17 23 32 49 1 15 16 625 24 5 8 777 30 19 32 20 13 16 23 29 32 C B A D B E 200 7 7 8 1 2 90 3 9 16 57 2 1 4 Y X L W A Z A B A Unit mm in Model SEZ KD09 SEZ KD12 15 SEZ KD18 A 700 27 9 16 900 35 7 16 1100 43 5 16 B 752 29 5 8 952 37 1 2 1152 45 3 8 C 798 31 7 16 998 39 5 16 1198 ...

Страница 3: ...on field supplied I Pull J Flare nut A B C D F G E M L E F L AG H H K L J I J O O N N 20 20 20 20 Fig 6 3 Fig 6 6 Fig 6 4 Fig 6 5 a Flare nut b Copper tube a Burr b Copper tube pipe c Spare reamer d Pipe cutter Fig 6 7 Fig 6 8 a Flaring tool b Die c Copper tube d Flare nut e Yoke a Smooth b Inside is shiny without any scratches c Even length d Too much e Tilted f Scratch on flared plane g Cracked ...

Страница 4: ... G K J F I A 25 1 25 1 35 1 13 32 A Indoor unit B Pipe cover 60 mm 3 8 in accessory C Tie band accessory D Visible part E Insertion margin F Drain hose accessory G Drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supplied H Insulating material field supplied I Tie band accessory J Max 180 5 mm 7 3 32 7 32 in K No gap The joint section of the insulation material must meet at the top Unit mm in Fig 6 1...

Страница 5: ... connecting cable F Washer accessory G Tensile force H Use ordinary bushing I Remote controller cable A Terminal block for indoor outdoor unit connecting B Terminal block for remote controller C Indoor outdoor unit connecting cable D Remote controller cable Fig 8 2 3 Fig 8 2 4 A Terminal block box B Knockout hole C Remove A Screw holding cover 2pcs B Cover Fig 8 2 1 Fig 8 2 2 A B C S3 S2 S1 1 2 S1...

Страница 6: ... I I I H B J H B 1 B 2 Fig 8 5 8 A AB TB6 B A To the terminal block on the indoor unit B TB6 No polarity Fig 8 6 Fig 8 7 8 2 8 4 46 1 13 16 30 1 3 16 120 4 3 4 83 5 3 5 16 A B C 30 1 3 16 30 1 3 16 A Remote controller B Required clearances for the remote controller C Installation pitch Fig 8 4 Fig 8 3 A Indoor terminal block B Ground wire green yellow C Indoor outdoor unit connecting cable 3 core ...

Страница 7: ...MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF TEST RUN COOL HEAT A F C E D B M I H G C F SIMPLE PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF B C A E D A ON OFF button B Test run display C Indoor temperature liquid line temperature display D ON OFF lamp E Power display A CHECK button B Refrigerant address C...

Страница 8: ...l work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for...

Страница 9: ...vice space Units should be installed by licensed contractor accordingly to local code require ments For outdoor units to be connected refer to the Installation Manual that comes with the units 3 4 Indoor unit accessories The unit is provided with the following accessories No Name Quantity 1 Pipe cover for refrigerant piping joint 120 mm 3 4 in Small diameter 1 2 Pipe cover for refrigerant piping j...

Страница 10: ...oke Carry out flaring work using flaring tool as shown below Dimension Pipe diameter A mm in mm in When the tool for R410A is used B mm in Clutch type 6 35 1 4 0 to 0 5 0 to 1 32 9 1 3 8 9 52 3 8 0 to 0 5 0 to 1 32 13 2 17 32 12 7 1 2 0 to 0 5 0 to 1 32 16 6 21 32 15 88 5 8 0 to 0 5 0 to 1 32 19 7 25 32 Firmly hold copper tube in a die in the dimension shown in the table at above 6 2 5 Check Fig 6...

Страница 11: ... Support metal K Air bleeder L Raised M Odor trap Grouped piping D O D ø32 mm 1 1 4 in PVC TUBE E Make it as large as possible About 10 cm 3 15 16 in F Indoor unit G Make the piping size large for grouped piping H Downward slope 1 100 or more I O D ø38 mm 1 1 2 in PVC TUBE for grouped piping 9 mm 3 8 in or more insulation J Up to 550 mm 21 21 32 in N Drain hose accessory O Horizontal or slightly u...

Страница 12: ...OFF ON OFF Fig 6 12 P 4 Drainage by gravity A Indoor unit B Pipe cover 30 mm 3 16 in accessory C Tie band accessory D Band fixing part E Insertion margin F Drain hose accessory G Drain pipe O D ø32 PVC TUBE field supplied H Insulating material field supplied I Max 145 5 mm 7 Duct work When connecting ducts insert a canvas duct between the main body and the duct Use non combustible duct components ...

Страница 13: ... are simultaneously in operation select AL Refer to Function table 2 Fig 8 2 1 P 5 A Screw holding cover 2pcs B Cover Fig 8 2 2 P 5 A Terminal block box B Knockout hole C Remove Fig 8 2 3 P 5 A Use conduit to keep the weight of the cable and external force from being applied to the power supply terminal connector B Indoor outdoor unit connecting cable C Conduit D Terminal block box E Knockout hole...

Страница 14: ...turned on during the op erational season 9 Test run 9 2 Test run 9 2 1 Using wired remote controller 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make sure that cold or warm wind is ...

Страница 15: ...it G Refrigerant gas cylinder operating valve H Refrigerant gas cylinder for R410A with siphon I Refrigerant liquid J Electronic scale for refrigerant charging K Charge hose for R410A L Gauge manifold valve for R410A M Service port 1 Connect gas cylinder to the service port of stop valve 3 way 2 Execute air purge of the pipe or hose coming from refrigerant gas cylinder 3 Replenish specified amount...

Страница 16: ... Veuillez vous assurer d utiliser la pièce fournie ou les pièces spécifiées pour l installation Toute pièce défectueuse utilisée pourrait être la cause d un incendie d un choc électrique de l appareil tombant de sa position etc ce qui résulterait en une blessure ou une fuite d eau Aérez le local en cas de fuite de liquide frigorigène en cours de fonctionne ment Tout contact du liquide frigorigène ...

Страница 17: ... est situé du côté de l arrivée d air Le détecteur d incendie risque de se déclencher par erreur suite à l alimentation en air chaud pendant le fonctionnement du chauffage En cas de présence de produits chimiques sur les lieux comme dans des usines chimiques ou des hôpitaux une étude approfondie s avère nécessaire avant de procéder à l installation de l appareil Certains produits chimiques peuvent...

Страница 18: ...r sur les tuyau tube après ébarbage il est impossible de les fixer après mise en forme conique 6 2 4 Le fraisage Fig 6 6 P 3 a Fraise b Etau c Tube en cuivre d Ecrou évasé e Serrage Effectuez l évasement à l aide de l alésoir selon la méthode suivante Dimensions Diamètre de tuyau A mm in mm in Lors de l utilisation de l outil pour le R410A B mm in Type d embrayage 6 35 1 4 0 à 0 5 0 à 1 32 9 1 3 8...

Страница 19: ...n y a pas d espace ici Diriger les raccords vers le haut 1 Retirer et jeter le bouchon de caoutchouc qui a été inséré à l extrémité de la tuyau terie de l appareil 2 Evaser l extrémité du tuyau de réfrigérant 3 Sur le site extraire l isolation thermique des tuyaux de réfrigérant et replacer l iso lant comme à l origine Précautions concernant le raccordement des tuyaux de réfrigérant s s s s s Touj...

Страница 20: ...principal Il est donc impératif d instal ler l admission A A A A A le plus loin possible du corps principal Faire particulièrement attention lors de son installation pour une admis sion par le bas Utilisez suffisamment d isolation thermique afin d éviter toute condensa tion sur les conduits de sortie et leurs brides Raccordez le corps principal du climatiseur et le conduit afin que leurs potentiel...

Страница 21: ... de connexion de l appareil intérieur extérieur D Câble de la télécommande Effectuez le câblage selon le diagramme en bas et à gauche Veuillez vous procu rer le câble localement Assurez vous que les câbles utilisés sont de la polarité correcte Fig 8 3 P 6 A Bornier intérieur B Fil de mise à la terre vert jaune SEZ KD09 SEZ KD12 SEZ KD15 SEZ KD18 10 10 20 20 8 Installations électriques C Câble de c...

Страница 22: ...e du réfrigérant 3 sur 00 3 Appuyer sur D se met à clignoter sur l affichage du numéro d appareil 4 4 Utiliser le bouton C pour spécifier le numéro d appareil 4 à 01 04 ou AL 5 Appuyer sur la touche E MODE pour spécifier l adresse du réfrigérant numéro d appareil clignote momentanément sur l affichage du numéro de mode 1 6 Appuyez sur la touche F pour régler le numéro de mode 1 sur 08 7 Appuyer su...

Страница 23: ...rer que la résistance entre les terminaux d alimentation électrique et la terre soit au moins de 1 0 MW W W W W s Ne pas effectuer ce test sur les terminaux des câbles de contrôle circuit à basse tension Avertissement Ne pas utiliser le climatiseur si la résistance de l isolation est inférieure à 1 0 MW W W W W Résistance de l isolation Après l installation ou après la coupure prolongée de la sour...

Страница 24: ... 10 1 P 7 A Appareil intérieur B Raccord C Conduite de liquide D Conduit de gaz réfrigérant E Robinet d arrêt F Appareil extérieur G Vanne de fonctionnement du cylindre de réfrigérant H Cylindre de gaz réfrigérant pour R410A avec siphon I Réfrigérant liquide J Echelle électronique pour la charge de réfrigérant K Conduite flexible de chargement pour le R410A L Jauge collectrice pour le R410A M Pris...

Страница 25: ...ne number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KB79K740H02 ...

Отзывы: