79
OCH708
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
Capacity setting display
Displayed as an outdoor capacity code.
Code
display
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoor unit setting information
Indoor pipe temperature / Liquid (TH2(1))
Indoor 1
- 39 to 88
Code
display
:
- 39 to 88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor room temperature (TH1)
8 to 39
Capacity
Code
SM100
20
SM125
25
SM140
28
• The tens digit (Total display for applied setting)
Setting details
Display details
H·P/Cooling only
0: H·P
1: Cooling only
Single phase/3 phase 0: Single phase 2: 3 phase
• The ones digit
Setting details
Display details
Defrosting switch
0: Normal
1: For high humidity
(Example) When heat pump, 3 phase and defrosting
(normal) are set up, “20” is displayed.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
(TH5(1))
Indoor 1
- 39 to 88
- 39 to 88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
:
- 39 to 88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
- 39 to 88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
:
:
:
8 to 39
Indoor pipe temperature / Liquid (TH2(2))
Indoor 2
- 39 to 88
Indoor pipe temperature / Cond. / Eva.
(TH5(2))
Indoor 2
- 39 to 88
1
ON
2 3 4 5 6
The number of connected indoor units
Unit
0 to 4
(The number of connected indoor units are dis-
played.)
The black square ( ) indicates a switch position.