107
OCH708
6. Removing the thermistor <Ambient> (TH7)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Disconnect the connector TH7/6 (red) on the controller
circuit board in the electrical parts box.
(4) Loosen the 2 wire clamps on top of the electrical parts box.
(See Photo 12)
(5) Pull out the thermistor <Ambient> (TH7) from the sensor holder.
Note: When replacing thermistor <Ambient> (TH7),
replace it together with thermistor <2- phase pipe>
(TH6), since they are combined together. Refer to
procedure No.5 to remove thermistor <2-phase
pipe>.
7. Removing the thermistor <Liquid> (TH3), thermistor
<Discharge> (TH4) and thermistor <Comp. surface> (TH33)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 2 front cover panel fixing screws (5 × 12) and
remove the front cover panel. (See Photo 1)
(4) Remove 4 back cover panel fixing screws (5 × 12) and
remove the back cover panel.
(5) Remove 4 right side panel fixing screws (5 × 12) in the rear
of the unit and remove the right side panel (See Photo 18)
(6) Disconnect the connectors, TH3 (white), TH4 (white) and
TH33 (black) on the controller circuit board in the electrical
parts box.
(7) Loosen the fastener for the lead wire under the electrical
parts box. (See Photo 14)
(8) Pull out the thermistor <Liquid> (TH3) from thermistor clip.
(9) Pull out the thermistor <Discharge> (TH4) from the
thermistor holder. (See Photo 16)
[Removing the thermistor <Comp. surface> (TH33)]
(10) Remove the sound proof cover (upper) for compressor.
(See Photo 16)
(11) Pull out the thermistor <Comp. surface> (TH33) from the
holder of the compressor shell. (See Photo 17)
Photo 16 (100V/YKA)
Photo 17 (140V/YKA)
Fastener
Photo 14
Photo 13
Thermistor <Ambient> (TH7)
Sensor holder
Photo 15
Thermister
<liquid>
(TH3)
Thermistor
<Comp.surface> (TH33)
Compressor
Thermistor
<Discharge> (TH4)
Nut
Thermistor
<Comp.surface> (TH33)
Compressor
Thermistor
<Discharge> (TH4)
Nut
OPERATING PROCEDURE