9
5-3. STANDARD OPERATION DATA
Representative matching
PLA-A42BA4
Mode
COOLING
HEATING
Total
Capacity
BTU/h
42,000
45,000
Input
W
4,600
4,450
Electrical circuit
Indoor unit model
PLA-A42BA4
Phase
Single
Cycle
60Hz
Voltage
230V
Current
1.00A
0.94A
Outdoor unit model
PUZ-A42NHA5
Phase
Single
Cycle
60Hz
Voltage
230V
Current
Refrigerant circuit
Discharge pressure
MPa
Suction pressure
MPa
Discharge temperature
Condensing temperature
Suction temperature
Ref. Pipe length
m
20.4A
2.83
0.82
73.4
47.5
4.9
7.6
410
120
164
118
40
21.5A
2.93
0.69
80.3
47.5
0.3
7.6
425
100
177
118
33
Discharge pressure
PSIG
Suction pressure
PSIG
Discharge temperature
°F
Condensing temperature
°F
Suction temperature
°F
Ref. Pipe length
ft
25
25
side
Indoor
Intake air temperature DB
26.7
21.1
Intake air temperature WB
19.4
15.6
Discharge air temperature DB
12.9
41.9
side
Outdoor Intake air temperature DB
35
8.3
Intake air temperature WB
23.9
6.1
side
Indoor
Intake air temperature DB
°F
80
70
Intake air temperature WB
°F
67
60
Discharge air temperature DB
°F
55
107
side
Outdoor Intake air temperature DB
°F
95
47
Intake air temperature WB
°F
75
43
SHF
0.71
BF
–
–
0.15
5-3-1. Heat pump
OCH512