66
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
Capacity setting display
Displayed as an outdoor capacity code
Code
display
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoor unit setting information
Indoor pipe temperature / Liquid (TH2(1))
Indoor 1
– 38~190
Code
display
˚F
– 38~190 (– 39~88
:
)
(When the temperature is 0ºF or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor room temperature (TH1)
46~102
Capacity
A42N
Code
25
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P / Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 : Single phase 2 : 3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example) When heat pump, 3 phase and
defrosting (normal) are set up, “20” is
displayed.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
(TH5(1))
Indoor 1
– 38~190
– 38~190 (– 39~88
:
)
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
˚F
– 38~190 (– 39~88
:
)
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
– 38~190 (– 39~88
:
)
(When the temperature is 0˚F or less, “–” and
temperature are displayed by turns.)
˚F
˚F
˚F
46~102 (8~39
:
)
Indoor pipe temperature / Liquid (TH2(2))
Indoor 2
– 38~190
Indoor pipe temperature / Cond. / Eva.
(TH5(2))
Indoor 2
– 38~190
1
ON
2 3 4 5 6
The number of connected indoor units
Unit
0~3
(The number of connected indoor units are displayed.)
The black square (
■
) indicates a switch position.
OCH512