76
Function
Settings
Mode No.
Setting No.
: Initial setting (Factory setting)
- : Not available
4-Way cassette
Ceiling suspended
PCA-KA
Filter sign
100h
1
2500h
07
(107)
2
"Clean the filter" indicator is not displayed
3
Air flow
Quiet
1
(Fan speed)
Standard
08
(108)
2
High ceiling
3
No.of air outlets
4 directions
1
-
3 directions
09
(109)
2
-
2 directions
3
-
Optional high efficiency
Not supported
10
(110)
1
filter
Supported
2
Vane setting
No vanes (Vane No.3 setting : PLA only)
1
Vane No.1 setting
11
(111)
2
Vane No.2 setting
3
Optional humidifier
Not supported
13
(113)
1
-
(PLA only)
Supported
2
-
Vane differential setting
No.1 setting (TH5: 75-82°F (24-28
))
1
in heating mode
No.2 setting (Standard, TH5: 82-90°F (28-32
))
14
(114)
2
(cold wind prevention)
No.3 setting (TH5: 90-100°F (32-38
))
3
Swing
23
(123)
1
2
Set temperature in heating
24
(124)
1
mode (4 deg up) *1
2
Fan speed when the
Extra low
1
heating thermostat is OFF
Stop
25
(125)
2
Keeping fan speed set by remote controller
3
Fan speed when the
Keeping fan speed set by remote controller
27
(127)
1
cooling thermostat is OFF
Stop
2
Detection of abnormality of
Detect
28
(128)
1
the pipe temperature (P8)
Neglect
2
PLA-BA
Not available Swing
Available
Wave air flow
Available
Not available
}
PLA-BA
Wired remote controller
(RF thermistor)
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of IR wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4
setting the
indoor unit number.
• When setting functions for a simultaneous twin indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to
4
setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL
(07 in case of IR wireless remote controller) referring to
4
setting the indoor unit number.
Mode No.11
Setting No. Settings
PLA-BA
PCA-KA
1
No Vanes
Vane No.3 setting
( Downward position than the standard )
Less smudging
No vane function
2
Vane No.1 setting
Standard
Standard
3
Vane No.2 setting
( Upward position than the standard )
Less draft *
( Upward position than the standard )
Less draft *
* Be careful of the smudge on ceiling.
OCH512