60
SW2 setting
Display detail
Explanation for display
Unit
:
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs. 0.5secs. 2 secs.
Sub cool on error occurring. SC
0~130
Cooling = TH6-TH3
Heating = TH5-TH2
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs. 0.5secs. 2 secs.
Thermo-on time until error stops
0~999
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs. 0.5secs. 2 secs.
Indoor pipe temperature / Liquid
(TH2 (3))
Indoor 3
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Indoor pipe temperature / Cond./ Eva.
(TH5 (3))
Indoor 3
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
50
1
:
1
ON
2 3 4 5 6
Discharge super heat on error occurring
SHd
0~255
Cooling = TH4-TH6
Heating = TH4-Th5
Replacement operation
W
If replacement operation is conducted
even once, “1” is displayed.
If replacement operation time is less
than 2 hrs. “0” is displayed.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
:
Minute
:
–
1: Conducted.
0: Not yet.
15
1
15
4
OC294--2.qxp 03.6.9 7:37 PM Page 60