(C) Capacity correction
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered com-
paring to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
3
3
When gas pipe is one size larger than standard size for PUHZ-RP4, 5 and 6.
1
Capacity can be obtained by referring to capacity curves of standard size.
1
1
Capacity curves for PUHZ-RP • VHA model <Standard size>
2
2
Capacity curve for PUHZ-RP3V model
<When gas pipe is one size smaller than standard size>
5
10
15
20
25
30
35
40
45
50
55
80
Capacity ratio [%]
Corrected pipe length
85
90
95
100
Heating RP3
Cooling RP3
Capacity ratio [%]
Corrected pipe length
Note: The permitted pipe length is up to 55m for RP3 model.
Cooling
RP3 model
Heating RP3, 4, 5
and 6 models
(Up to 55m for
RP3 model)
RP4 model
RP5 model
RP6 model
Cooling
Heating