Perform  the  airtight  test,  vacuum  air  purging, 

additional  refrigerant  charging  (if  necessary), 

and gas leak check.

4.7. Precautions when reusing existing R22 refrigerant pipes

• Refer to the flowchart below to determine if the existing pipes can be used and if it is necessary to use a filter dryer.

• If the diameter of the existing pipes is different from the specified diameter, refer to technological data materials to confirm if the pipes can be used.

Measure  the  existing  pipe  thickness  and 

check for damage.

The existing pipe thickness meets specifica

-

tions and the pipes are not damaged.

Check if the existing air conditioner can operate.

After operating the cooling system for about 30

minutes, do a pump down work.

Disconnect the existing air conditioner from the  

pipes.

Attach the new air conditioner

Test run

* Refer to 7.2.

The existing pipes cannot be reused.

Use new pipes.

* If  the  existing  air  conditioner  cannot  operate,  use  a 

refrigerant recovery device to collect the refrigerant.

* In case existing pipes were used for gas or oil heat 

pump systems, be sure to clean the pipes.

The existing pipe thickness does not meet

specifications or the pipes are damaged.

4. Installing the refrigerant piping

P100, 125, 140

Drain socket

PAC-SG61DS-E

Drain pan

PAC-SH97DP-E

5. Drainage piping work

Outdoor unit drainage pipe connection

When drain piping is necessary, use the drain socket or the drain pan (option).

4.8. For twin/triple combination (Fig. 4-8)

•  When  this  unit  is  used  as  a  FREE  COMPO  MULTI  unit,  install  the  refrigerant 

piping with the restrictions indicated in the drawing on the left. In addition, if the 

restrictions are going to be exceeded, or if there are going to be combinations of 

indoor and outdoor units, refer to installation instructions for the indoor unit for 

details about the installation.

Outdoor unit

Permissible total 

piping length 

A+B+C+D

B or C or D

Charge-less piping 

length

A+B+C+D

P100-140

50 m and less

20 m and less

30 m and less

Outdoor unit

| B-C | or | B-D |

or | C-D | 

No. of bends

P100-140

8 m and less

Within 15

Indoor unit

Outdoor unit

Multi distribution pipe (option)

Height difference (Indoor unit - 
Outdoor unit) Max. 30 m

Height difference (Indoor unit - 
Indoor unit) Max. 1 m

A: Main piping
B, C, D: Branch piping

<Limits of refrigerant piping installation>

P100-140 : A+B+C(+D) 

[

 50 m

* “D” is for triple.

Fig. 4-8

RG79Y933H01_EN.indd   8

2017/06/27   11:50:42

Содержание Mr.Slim PUHZ-P100VKA

Страница 1: ...o correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta le...

Страница 2: ...he unit electric shock or fire may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an expl...

Страница 3: ...tion The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Use C1220 copper phosphorus for copper and c...

Страница 4: ...Air protection guide 3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind direction if possible Fig 2 5 B Wind direction 2 4 2 When installing a single outdoor unit Refer to the last page Minimum dimensions are as follows except for Max meaning Maximum dimen sions indicated Refer to the figures for each case 1 Obstacles at rear only Fig 2 6 2 Obstacles at rear and ...

Страница 5: ...with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thick nesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contami...

Страница 6: ...o 4 4 Refrigerant pipe airtight testing method 4 A high performance vacuum pump is used at the stop valve service port to main tain a vacuum for an adequate time at least one hour after reaching 101 kPa 5 Torr in order to vacuum dry the inside of the pipes Always check the degree of vacuum at the gauge manifold If there is any moisture left in the pipe the degree of vacuum is sometimes not reached...

Страница 7: ...the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Precautions when using the charge valve Fig 4 7 Do not tighten the service port too much when installing it otherwise the valve core could be deformed and become loose causing a gas leak After positioning section B in the desired dire...

Страница 8: ...The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping P100 125 140 Drain socket PAC SG61DS E Drain pan PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option 4 8 For twin triple combination Fig 4 8 When this unit is used as a FREE COMPO MULT...

Страница 9: ...ch poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 2 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 sep...

Страница 10: ... SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of the outdoor unit The noise is coming from ...

Страница 11: ... minutes have passed If the refrigerant collecting operation has been completed normally LED1 off LED2 lit the unit will remain stopped until the power supply is turned off 4 Turn off the power supply circuit breaker Note that when the extension piping is very long with large refrigerant amount it may not be possible to perform a pump down operation When performing the pump down operation make sur...

Страница 12: ...te Business Park Ballymount Dublin 24 Ireland Italian Branch Centro Direzionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch H...

Страница 13: ...140EA R410A Standard Inverter Three Phase Product Information Sheet PSA RP100 140KA R410A Standard Inverter Product Information Sheet PUHZ P100 140V Y KA Parts List OCB670 PUHZ P100 140V Y KA Service Manual OCH670 PUHZ P100 140V YKA Installation Manual ...

Отзывы: