11

8.3. Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor 

unit or the outdoor unit.

1

  Supply power (circuit breaker).

  *   When power is supplied, make sure that “CENTRALLY CONTROLLED” is not 

displayed  on  the  remote  controller.  If  “CENTRALLY  CONTROLLED”  is  dis-

played, the refrigerant collecting (pump down) cannot be completed normally.

  *   Start-up of the indoor-outdoor communication takes about 3 minutes after the 

power  (circuit  breaker)  is  turned  on.  Start  the  pump-down  operation  3  to  4 

minutes after the power (circuit breaker) is turned ON.

2

  After the liquid stop valve is closed, set the SWP switch on the control board of 

the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and 

outdoor units) start operating and refrigerant collecting operation begins. LED1 

and LED2 on the control board of the outdoor unit are lit.

  *   Only set the SWP switch (push-button type) to ON if the unit is stopped. How-

ever, even if the unit is stopped and the SWP switch is set to ON less than 3 

minutes after the compressor stops, the refrigerant collecting operation cannot 

be performed. Wait until compressor has been stopped for 3 minutes and then 

set the SWP switch to ON again.

3

  Because the unit automatically stops in about 2 to 3 minutes when the refrigerant 

collecting operation is completed (LED1 off, LED2 lit), be sure to quickly close the 

gas stop valve. If LED1 is lit and LED2 is off and the outdoor unit is stopped, refrig-

erant collection is not properly performed. Open the liquid stop valve completely, 

and then repeat step 

2

 after 3 minutes have passed.

  *   If the refrigerant collecting operation has been completed normally (LED1 off, 

LED2 lit), the unit will remain stopped until the power supply is turned off.

4

 Turn off the power supply (circuit breaker).

  *   Note that when the extension piping is very long with large refrigerant amount, 

it may not be possible to perform a pump-down operation. When performing 

the pump-down operation, make sure that the low pressure is lowered to near 

0 MPa (gauge).

 Warning:

When pumping down the refrigerant, stop the compressor before disconnect

-

ing the refrigerant pipes. The compressor may burst if air etc. get into it.

8. Special Functions

1 2 3 4 5 6

*  Set the refrigerant address using the DIP switch of the outdoor unit.

1

  Wiring from the Remote Control

This wire is connected to TB5 (terminal board for remote controller) of the indoor 

unit (non-polar).

2

 When a Different Refrigerant System Grouping is Used.

Up  to  16  refrigerant  systems  can  be  controlled  as  one  group  using  the  slim  MA 

remote controller.

Note:

In single refrigerant system (twin/triple), there is no need of wiring 

2

.

A

  Outdoor unit

B

  Indoor unit

C

  Master remote controller

D

  Subordinate remote controller

E

  Standard 1:1 (Refrigerant address = 00)

F

  Simultaneous twin (Refrigerant address = 01)

G

  Simultaneous triple (Refrigerant address = 02)

E

  SW 1 - 3 ~ 6

F

  SW 1 - 3 ~ 6

G

  SW 1 - 3 ~ 6

9. System control (Fig. 9-1)

Fig. 9-1

SW1

Function table

  <SW1>

Function

Operation according to switch setting

ON

OFF

SW1

function 

settings

1

Compulsory 

defrosting

Start

Normal

2

Error history 

clear

Clear

Normal

3
4
5
6

Refrigerant 

system ad-

dress setting

Settings for outdoor unit addresses 

0 to 15

TB1

A

G

F

A

A

E

B

B

B

B

B

B

D

C

TB1

TB1

TB4

TB5

TB4

TB5

TB4

TB4

TB5

TB4

TB4

1

1

2

 ON
 OFF

 ON
 OFF

 ON
 OFF

3    4    5    6

3    4    5    6

3    4    5    6

 ON
 OFF

2

RG79Y933H01_EN.indd   11

2017/06/27   11:50:45

Содержание Mr.Slim PUHZ-P100VKA

Страница 1: ...o correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta le...

Страница 2: ...he unit electric shock or fire may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an expl...

Страница 3: ...tion The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Use C1220 copper phosphorus for copper and c...

Страница 4: ...Air protection guide 3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind direction if possible Fig 2 5 B Wind direction 2 4 2 When installing a single outdoor unit Refer to the last page Minimum dimensions are as follows except for Max meaning Maximum dimen sions indicated Refer to the figures for each case 1 Obstacles at rear only Fig 2 6 2 Obstacles at rear and ...

Страница 5: ...with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thick nesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contami...

Страница 6: ...o 4 4 Refrigerant pipe airtight testing method 4 A high performance vacuum pump is used at the stop valve service port to main tain a vacuum for an adequate time at least one hour after reaching 101 kPa 5 Torr in order to vacuum dry the inside of the pipes Always check the degree of vacuum at the gauge manifold If there is any moisture left in the pipe the degree of vacuum is sometimes not reached...

Страница 7: ...the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Precautions when using the charge valve Fig 4 7 Do not tighten the service port too much when installing it otherwise the valve core could be deformed and become loose causing a gas leak After positioning section B in the desired dire...

Страница 8: ...The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping P100 125 140 Drain socket PAC SG61DS E Drain pan PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option 4 8 For twin triple combination Fig 4 8 When this unit is used as a FREE COMPO MULT...

Страница 9: ...ch poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 2 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 sep...

Страница 10: ... SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of the outdoor unit The noise is coming from ...

Страница 11: ... minutes have passed If the refrigerant collecting operation has been completed normally LED1 off LED2 lit the unit will remain stopped until the power supply is turned off 4 Turn off the power supply circuit breaker Note that when the extension piping is very long with large refrigerant amount it may not be possible to perform a pump down operation When performing the pump down operation make sur...

Страница 12: ...te Business Park Ballymount Dublin 24 Ireland Italian Branch Centro Direzionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch H...

Страница 13: ...140EA R410A Standard Inverter Three Phase Product Information Sheet PSA RP100 140KA R410A Standard Inverter Product Information Sheet PUHZ P100 140V Y KA Parts List OCB670 PUHZ P100 140V Y KA Service Manual OCH670 PUHZ P100 140V YKA Installation Manual ...

Отзывы: