4.  Installing the refrigerant piping

Fig. 4-5

A

B

D

C

4.4.  Refrigerant piping (Fig. 4-4)

Indoor unit

1.  Remove the flare nut and cap of the indoor unit.
2.  Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil 

(available from your local supplier) to the flare sheet surface.

3.  Quickly connect the on site cooling pipes to the unit. 
4.  Wrap the pipe cover that is attached to the gas pipe and make sure that the 

connection join is not visible.

5.  Wrap the pipe cover of the unit’s liquid pipe and make sure that it covers the 

insulation material of the on site liquid pipe.

6.  The portion where the insulation material is joined is sealed by taping.

Site-side refrigerant piping

Unit side refrigerant piping

4.4.1.  Storing in the piping space of the unit (Fig. 4-5)

1.  Wrap the supplied felt tape in the range of the refrigerant piping which will be 

housed within the piping space of the unit to prevent dripping.

2.  Overlap the felt tape at one-half of the tape width.
3.  Fasten the end portion of the wrapping with vinyl tape, etc.

Gas pipe

B

  Liquid pipe

C

  Indoor/outdoor connection cable

D

  Felt tape 

3

Fig. 4-4

B

A

Fig. 5-1

5.  Drainage piping work

A

B

C

E

D

C

F

C

G

H

I

J

K

5.1.  Drainage piping work (Fig. 5-1)

•  Drain pipes should have an inclination of 1/100 or more.

•  For extension of the drain pipe, use a soft hose (inner dia. 15 mm) available on 

the market or hard vinyl chloride pipe (VP-16/O.D. ø22 PVC TUBE).  Make sure 

that there is no water leakage from the connections.

•  Do not put the drain piping directly in a drainage ditch where sulphuric gas may 

be generated.

•  When piping has been completed, check that water flows from the end of the 

drain pipe.

 Caution:

The drain pipe should be installed according to this Installation Manual to 

ensure correct drainage. Thermal insulation of the drain pipes is necessary 

to prevent condensation. If the drain pipes are not properly installed and 

insulated, condensation may drip on the ceiling, floor or other possessions.

Inclined downwards

Must be lower than outlet point

Water leakage

Trapped drainage

Air

Wavy

The end of drain pipe is under water.

Drainage ditch

I

  5 cm or less between the end of drain pipe and the ground.

Drain hose

Soft PVC hose (Inside diameter 15 mm) 

 

or  

Hard PVC pipe (VP-16)

 

* Bond with PVC type adhesive 

Preparing left and left rear piping (Fig. 5-2)

Remove the drain cap.

•  Remove the drain cap by holding the bit that sticks out at the end of the pipe and 

pulling.

Drain cap

Remove the drain hose.

•  Remove the drain hose by holding on to the base of the hose 

a

 (shown by 

arrow) and pulling towards yourself 

b

.

Insert the drain cap.

•  Insert a screwdriver etc into the hole at the end of the pipe and be sure to push 

to the base of the drain cap.

Insert the drain hose.

•  Push the drain hose until it is at the base of the drain box connection outlet.
•  Please make sure the drain hose hook is fastened properly over the extruding 

drain box connection outlet.

Hooks

A

A

1

3

Fig. 5-2

a

b

A

B

2

4

en

RH79A071W01_01en.indd   7

2020/09/24   9:05:29

Содержание Mr. SLIM PKA-M-LAL Series

Страница 1: ...Air Conditioners PKA M LAL Series FOR INSTALLER English INSTALLATION MANUAL RH79A071W01_Cover indd 1 2020 09 24 9 08 55 ...

Страница 2: ...igerant comes into contact with a flame poisonous gases will be released All electric work must be performed by a qualified technician according to local regulations and the instructions given in this manual Do not use intermediate connection of the electric wires Use only specified cables for wiring The wiring connections must be made securely with no tension applied on the terminal connections A...

Страница 3: ...s or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high frequency medical equipment and radio communications equipment c...

Страница 4: ... the wall mounting fixture 3 2 1 Setting the wall mounting fixture and piping positions Using the wall mounting fixture determine the unit s installation position and the locations of the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole ø75 D Bottom right rear pipe hole ...

Страница 5: ... Reference marking for flare connection C Through hole D On site piping 3 4 Preparing the indoor unit Check beforehand because the preparatory work will differ depending on the exiting direction of the piping When bending the piping bend gradually while maintaining the base of the piping exiting portion Abrupt bending will cause misshaping of the piping Cut off outlet of the pipe depending on the ...

Страница 6: ...or unit is installed level A Mount board 1 B Indoor unit C Hook D Square hole Left and left rear piping Fig 3 11 3 While inserting the drain hose into the wall penetration hole penetration sleeve hang the top of the indoor unit to the mount board 1 Cut part of the shipping box and wrap into a cylindrical form as illustrated in the diagram Hook this to the rear surface rib as a spacer and raise the...

Страница 7: ...y ø6 35 thickness 0 8 mm ø9 52 thickness 0 8 mm ø12 7 thickness 0 8 mm ø15 88 thickness 1 0 mm Do not use pipes thinner than those specified above 4 2 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe shoul...

Страница 8: ...C TUBE Make sure that there is no water leakage from the connections Do not put the drain piping directly in a drainage ditch where sulphuric gas may be generated When piping has been completed check that water flows from the end of the drain pipe Caution The drain pipe should be installed according to this Installation Manual to ensure correct drainage Thermal insulation of the drain pipes is nec...

Страница 9: ...g strand wires because beards may cause the wiring to short out 3 Install the parts that were removed back to their original condition 4 Fasten each of the wires with the clamp under the electrical parts box A Electrical box cover B Fixing screw C Clamp D Ground wire connection portion E MA remote control terminal block 1 2 do not have polarity F Terminal block for indoor and outdoor units connect...

Страница 10: ...ting Indoor unit L N 3 Indoor unit Outdoor unit S1 S2 3 230 V AC Indoor unit Outdoor unit S2 S3 3 4 24 V DC 28 V DC Wired remote controller option Indoor unit 3 12 V DC 1 For 35 140 outdoor unit application Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 m...

Страница 11: ...r supply terminal kit is used change the indoor unit electrical box wiring refering to the figure in the right and the DIP switch settings of the outdoor unit control board Refer to the installation manual for the Power supply terminal kit Affix label B that is included with the manuals near each wiring diagram for the indoor and outdoor units Note Some units cannot be used in a simultaneous twin ...

Страница 12: ...splay 12 hour format 24 hour format B AUTO mode Single set point Dual set point C Pair No 0 3 D Backlight On Off E 4 1 Switching to the initial setting mode 1 Press the button 1 to stop the air conditioner 2 Press the button 2 The Function setting screen will be displayed and the function No A will blink Fig 6 6 Press the button 4 to change the function No 3 Check that function No 1 is displayed a...

Страница 13: ...rsor Cursor Ref address Mode 1 Mode 2 Mode 3 Mode 4 Grp F1 F2 F3 F4 Function setting Cursor Cursor Request Ref address Mode 1 Mode 2 Mode 3 Mode 4 Grp Fig 6 11 Fig 6 12 F1 F2 F3 F4 Function setting Ref address Sending data Grp Fig 6 13 Fig 6 14 Fig 6 16 Fig 6 15 Fig 6 17 6 3 2 By wireless remote controller 1 Going to the function select mode Press the button between of 5 seconds Start this operati...

Страница 14: ...ported indoor unit is equipped with outdoor air intake 3 Power voltage 240 V 04 1 220 V 230 V 2 Select unit numbers 1 to 4 or All Mode Settings Mode no Setting no Initial setting setting Filter sign 100 Hr 07 1 2500 Hr 2 No filter sign indicator 3 Fan speed Silent 08 1 Standard 2 High ceiling 3 Fan speed during the cooling thermostat is OFF Setting fan speed 27 1 Stop 2 Extra low 3 1 When the powe...

Страница 15: ... is turned on Please Wait is displayed for 3 minutes during system startup Normal After power is turned on Please Wait is displayed for 3 minutes then error code is dis played After startup is displayed green once and red once blink alternately F1 Incorrect connection of outdoor terminal block L N and S1 S2 S3 After startup is displayed green once and red twice blink alternately F3 F5 F9 Outdoor u...

Страница 16: ...ller power supply Indicates whether power is supplied to the wired remote controller The LED is lit only for the indoor unit that is con nected to the outdoor unit that has an address of 0 LED 3 indoor outdoor unit communication Indicates whether the indoor and outdoor units are communicating Make sure that this LED is always blinking Test run Fig 7 5 1 Press the button 1 to stop the air condition...

Страница 17: ...ignal received Beeper sounds Refer to the following tables for details on the check codes Wireless remote controller Output pattern A 7 3 Self check Refer to the installation manual that comes with each remote controller for details Output pattern A Errors detected by indoor unit Wireless remote controller Wired remote controller Symptom Remark Beeper sounds OPERATION INDICATOR lamp blinks Number ...

Страница 18: ...ceived the specified refrigerant address is incorrect On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displayed in the LCD If the unit cannot be operated properly after test run refer to the following table to find the cause Symptom Cause Wired remote controller LED 1 2 PCB in outdoor uni...

Страница 19: ...l Ref address Cool Ref address Cool Sub cool OU TH4 temp OU TH6 temp OU TH7 temp IU air temp IU HEX temp IU filter time 1 2 3 Select Service from the Main menu and press the SELECT button Select Check with the F1 or F2 button and press the SELECT button Select Smooth maintenance with the F1 or F2 button and press the SELECT button Select each item Select the item to be changed with the F1 or F2 bu...

Страница 20: ...99 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travellers Lane Hatfield Herts AL10 8XB England U K Polish Branch Krakowska 50 PL 32 083 Balice Poland MITSUBISHI ELECTRIC TURKEY ELEKTRİK ÜRÜNLERI A Ş Şerifali Mah Kale Sok No 41 34775 Ümra...

Отзывы: