background image

6

Fig. 5-1

5. Drainage piping work

A

B

C

5.1. Drainage piping work (Fig. 5-1)

• Use a PVC pipe (I.D. ø20mm, 13/16 inch) for drain piping and provide 1/100 or

more downward slope.

• Other PVC pipe sizes are available with the drain adaptor supplied.
• Make sure that there is no water leakage from the connections.
• If the drain pipe passes indoors it must be covered with insulating material (foamed

polyethylene: specific gravity: 0.03, thickness: 9 mm, 23/64 inch or more) available on the
market.

• Do not put the drain piping directly in a drainage ditch where sulphuric gas may be

generated.

• When piping has been completed, check that water flows from the end of the drain

pipe.

A

Drain connection socket

C

Indoor unit’s drain hose

B

Field drain pipe

 Caution:

The drain pipe should be installed according to this Installation Manual to en-
sure correct drainage. Thermal insulation of the drain pipes is necessary to
prevent condensation. If the drain pipes are not properly installed and insu-
lated, condensation may drip on the ceiling, floor or other possessions.

Preparing left and left rear piping (Fig. 5-2)

1

Remove the drain cap.

• Remove the drain cap by holding the bit that sticks out at the end of the pipe and

pulling.

A

Drain cap

2

Remove the drain hose.

• Remove the drain hose by holding on to the base of the hose 

a

 (shown by arrow)

and pulling towards yourself 

b

.

3

Insert the drain cap.

• Insert a screwdriver etc into the hole at the end of the pipe and be sure to push to

the base of the drain cap.

4

Insert the drain hose.

• Push the drain hose until it is at the base of the drain box connection outlet.
• Please make sure the drain hose hook is fastened properly over the extruding drain

box connection outlet.

B

Hooks

Remove the side panel of the indoor unit on the drain side. Pour water in the drain
pan and check that it comes out the drain pipe end. After confirmation, reinstall the
side panel.

A

a

b

A

A

B

1

3

2

4

Fig. 5-2

4. Installing the refrigerant piping

A

B

C

D

E

F

G

Fig. 4-4

4.3. Positioning refrigerant and drain piping

1

Position of refrigerant and drain piping (Fig. 4-2)

• The drain pipe can be cut midway to meet the on-site conditions.

A

(Total length of flexible hose)

D

Drain hose

B

Liquid pipe

E

Left-side piping

C

Gas pipe

F

Right-side piping

2

Determine the position of the knockout holes on the unit body. (Fig. 4-3)

s

Cut the knockout holes using a saw blade or an adequate knife.

Take care not to damage other parts of the unit.

• Remove the corner box and drill a knockout hole. If a hole is made without remov-

ing the box, the drain hose could be damaged.

A

Left-side piping

D

Remote controller cable through hole

B

Lower piping

E

Corner box

C

Right-side piping

Fig. 4-2

E

D

B

C

A

C

B

D

F

1-3/8

17-11/16

22-7/8

11-1/32

1-7/32

2-1/8

3-3/8

6-1/32

27-9/16

A

E

2-3/8

13/32

7/8

2-3/4

13/16

9-21/32

D

5/16

B

E

D

13/32

7-15/32

7/8

2-3/4

1-3/8

5/16

2-3/8

C

E

5/16

2-3/8

13/32

7/8

2-3/4

13/16

9-21/32

D

Fig. 4-3

1

2

4.4. Refrigerant piping (Fig. 4-4)

1. Remove the flare nut and cap of the indoor unit.
2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil

(available from your local supplier) to the flare sheet surface.

3. Quickly connect the on site cooling pipes to the unit.
4. Wrap the pipe cover 

3

 that is attached to the gas pipe and make sure that the

connection join is not visible.

5. Wrap the pipe cover of the unit’s liquid pipe and make sure that it covers the

insulation material of the on site liquid pipe.

6. Use the bands that are provided 

4

 to tighten both ends (15–20mm, 19/32 to

25/32 inch) of each pipe cover 

3

.

A

Cooling pipe and insulation (available from local supplier)

B

Unit’s gas pipe

E

Bands

4

C

Unit’s liquid pipe

F

On site gas pipe

D

Pipe cover 

3

G

On site liquid pipe

(inch)

(inch)

4.5. For twin combination

Refer to the outdoor unit unstallation manual.

Содержание Mr.Slim PKA-AA GA

Страница 1: ...he outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Español MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad exterior antes de instalar la unidad de aire acondicionado PARA EL INSTALADOR ...

Страница 2: ...e unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre q...

Страница 3: ...ole in the wall you must consult the building contractor A Supporting piece I Bottom left pipe slot knockout hole B Mount board J Bottom right pipe slot ø90 mm 3 9 16 inch C Main body K Bottom right pipe slot knockout hole D Slot 6 11 20 L Liquid pipe flare connection position 6P 7 16 25 32 inch M Gas pipe flare connection position E Unit center N Level setting standard F Bolt hole 14 ø14 mm V Ins...

Страница 4: ...pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left rear piping Fig 3 7 1...

Страница 5: ...iquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness of 12 mm 1 2 inch or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 9 mm 23 64 inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut...

Страница 6: ...d check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refrigerant piping A B C D E F G Fig 4 4 4 3 Positioning refrigerant and drain piping 1 Position of refrigerant and drain piping Fig 4 2 The drain pipe can be cut midway to meet the on site conditions A Total length of flexible hose D Drain hose B Liquid pipe E Left...

Страница 7: ... Indoor unit Outdoor unit 1 Indoor unit earth Remote controller Indoor unit 2 Indoor unit Outdoor unit S1 S2 3 Indoor unit Outdoor unit S2 S3 3 Remote controller Indoor unit 3 PKA 1A 15A 3 AWG16 polar 1 Min AWG16 2 AWG22 Non polar AC 208 230 V DC24 V DC12 V Circuit rating Wiring Wire No size ...

Страница 8: ...onnected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1 Installation area Area in which the remote controller is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exposed to cold or h...

Страница 9: ... 1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230 V setting number 1 208 V setting number 2 8 Press the MODE button E and mode and the setting number 1 and 2 will change to being on constantly and the contents of the setting can be confirmed 9 Press ...

Страница 10: ...10 ...

Страница 11: ... P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error 10 11 12 Fb Indoor unit control system error memory err...

Страница 12: ...o the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units only A control Indicates state of communication between the indoor and outdoor units Make sure that this LED is always blinking 7 Test run On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displaye...

Страница 13: ...button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Display A Press the ...

Страница 14: ...s manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U874H02 BG79U874H02 A ...

Отзывы: