background image

3

2.1. Outline dimensions (Indoor unit) (Fig. 2-1)

Select a proper position allowing the following clearances for installation and mainte-
nance.

(inch)

Models

W

D

H

A

E

F

G

H

A12, A18

990

235

340

Min. 30

Max. 130 Min. 180

Min. 50

Min. 150

39

9-1/4

13-3/8

Min. 1-13/16

Max. 5

Max. 7-3/32 Min. 1-31/32 Min. 5-29/32

B

Ceiling

C

Wall

D

Furnishing, etc

 Warning:

Mount the indoor unit on a ceiling strong enough to withstand the weight of the
unit.

2.2. Outline dimensions (Outdoor unit)

Refer to the outdoor unit installation manual.

2. Installation location

3. Installing the indoor unit

3.1. Check the indoor unit accessories (Fig. 3-1)

The indoor unit should be supplied with the following accessories.

PART NUMBER

ACCESSORY

QUANTITY

 LOCATION OF SETTING

1

Mount board

1

Fix at the back of the unit

2

Tapping screw 4 

×

 35

12

3

Pipe cover

1

4

Band

5

5

Felt tape

3

Set inside the unit

6

Wireless remote controller

1

7

Remocon holder

1

8

Alkali batteries (size AAA)

2

9

Mount piece (Package)

1

0

Wired remote controller

1

for PKA-A·GA

q

Drain adaptor

1

Fig. 2-1

1

2

3

4

5

6

7

8

9

Fig. 3-1

Fig. 3-3

3.2. Installing the wall mounting fixture (Fig. 3-2)

3.2.1. Setting the wall mounting fixture and piping positions

s

Using the wall mounting fixture, determine the unit’s installation position
and the locations of the piping holes to be drilled.

 Warning:

Before drilling a hole in the wall, you must consult the building contractor.

A

Supporting piece

I

Bottom left pipe slot knockout hole

B

Mount board

J

Bottom right pipe slot (ø90 mm, 3-9/16 inch)

C

Main body

K

Bottom right pipe slot knockout hole

D

Slot (6-11 

×

 20,

L

Liquid pipe flare connection position

6P-7/16

×

 25/32 inch)

M

Gas pipe flare connection position

E

Unit center

N

Level setting standard

F

Bolt hole (14-ø14 mm,

V

Insert scale.

14P-9/16 inch)

Y

Hole centre

G

Tapping hole (49-ø5 mm,

Z

Align the scale with the line.

49P-3/16 inch)

H

Bottom left pipe slot

(ø90 mm, 3-9/16 inch)

A

C

D

E

B

E

D

C

B

A

F

H

D

W

G

H

A

Sleeve

B

Hole

C

(Indoors)

D

Wall

E

(Outdoors)

3.2.2. Drilling the piping hole (Fig. 3-3)

s

Use a core drill to make a hole of 90-100 mm, 3-9/16 to 4 inch diameter in the
wall in the piping direction, at the position shown in the diagram to the left.

s

The hole should incline so that the outside opening is lower than the inside
opening.

s

Insert a sleeve (with a 90 mm, 3-9/16 inch diameter and purchased locally)
through the hole.

Note:
The purpose of the hole’s inclination is to promote drain flow.

(mm)

B

Y

Z

X

3-15/16

W

16-17/32

19-1/2

15-15/16

14-3/16

11-13/16

9-21/32

7-15/32

5-5/16

2-15/16

1-1/4 25/32

0

1-3/8

31/32

3-3/4

8-1/16

10-1/4

12-19/32

13-19/32

19-1/2

5-29/32

9-1/16  8-9/32

5-1/2

6-11/16 7-15/32

16-23/32

1-9/16

0

0
1-3/8

2-5/32
3-5/32

5-1/8

7-15/32

9-1/16

10-23/32
12-7/32

13-3/8

12-11/16

A

E

B

C

D

F

G

H

I

J

K

L

M

N

(inch)

Fig. 3-2

0

}

for PKA-A·GAL

6

6

6

6

6

 - 

8

8

8

8

8

 are stored in a cut-out section of the packing material (styrofoam).

q

Содержание Mr.Slim PKA-AA GA

Страница 1: ...he outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Español MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad exterior antes de instalar la unidad de aire acondicionado PARA EL INSTALADOR ...

Страница 2: ...e unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre q...

Страница 3: ...ole in the wall you must consult the building contractor A Supporting piece I Bottom left pipe slot knockout hole B Mount board J Bottom right pipe slot ø90 mm 3 9 16 inch C Main body K Bottom right pipe slot knockout hole D Slot 6 11 20 L Liquid pipe flare connection position 6P 7 16 25 32 inch M Gas pipe flare connection position E Unit center N Level setting standard F Bolt hole 14 ø14 mm V Ins...

Страница 4: ...pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left rear piping Fig 3 7 1...

Страница 5: ...iquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness of 12 mm 1 2 inch or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 9 mm 23 64 inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut...

Страница 6: ...d check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refrigerant piping A B C D E F G Fig 4 4 4 3 Positioning refrigerant and drain piping 1 Position of refrigerant and drain piping Fig 4 2 The drain pipe can be cut midway to meet the on site conditions A Total length of flexible hose D Drain hose B Liquid pipe E Left...

Страница 7: ... Indoor unit Outdoor unit 1 Indoor unit earth Remote controller Indoor unit 2 Indoor unit Outdoor unit S1 S2 3 Indoor unit Outdoor unit S2 S3 3 Remote controller Indoor unit 3 PKA 1A 15A 3 AWG16 polar 1 Min AWG16 2 AWG22 Non polar AC 208 230 V DC24 V DC12 V Circuit rating Wiring Wire No size ...

Страница 8: ...onnected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1 Installation area Area in which the remote controller is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exposed to cold or h...

Страница 9: ... 1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230 V setting number 1 208 V setting number 2 8 Press the MODE button E and mode and the setting number 1 and 2 will change to being on constantly and the contents of the setting can be confirmed 9 Press ...

Страница 10: ...10 ...

Страница 11: ... P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error 10 11 12 Fb Indoor unit control system error memory err...

Страница 12: ...o the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units only A control Indicates state of communication between the indoor and outdoor units Make sure that this LED is always blinking 7 Test run On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displaye...

Страница 13: ...button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Display A Press the ...

Страница 14: ...s manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U874H02 BG79U874H02 A ...

Отзывы: