36
(1) Request Code List
Rotation setting
Initial
setting
Initial
setting
2nd stage cut-in setting
Setting contents
Setting No.
(Request code)
No.7
(316)
No.8
(317)
No.9
(318)
Rotation and Back-up OFF (Normal group control operation)
Monitoring the request code of current setting.
Setting No.
(Request code)
No.1
(310)
No.2
(311)
No.3
(312)
No.4
(313)
No.5
(314)
No.6
(315)
Cut-in function ON (Set point = Set temp. +8
(14.4°F))
Cut-in function ON (Set point = Set temp. +6
(10.8°F))
Cut-in function ON (Set point = Set temp. +4
(7.2°F))
Cut-in function OFF
Monitoring the request code of current setting.
Setting contents
Rotation ON (Alternating interval = 28days) and back-up function
Rotation ON (Alternating interval = 14days) and back-up function
Rotation ON (Alternating interval = 1day) and back-up function
Back-up function only
No.5
(324)
Rotation ON (Alternating interval = 7days) and back-up function
Rotation ON (Alternating interval = 5days) and back-up function
Rotation ON (Alternating interval = 3days) and back-up function
No.1
(320)
No.2
(321)
No.3
(322)
No.4
(323)
11-1-2.How to perform the operation of rotation function(Back-up funcion, 2nd stage cut-in function)
Set by wired remote controller.(Maintenance monitor)
It is necessary to set the same content to both main unit and sub unit.
Every time indoor controller board is replaced for servicing, it is necessary to set each function.
NOTE