24
Error Code
Abnormal point and detection method
Cause
Countermeasure
P1
Room temperature thermistor (TH1)
1
The unit is in 3-minute resume preven-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
reset normally after 3 minutes. (The
unit returns to normal operation, if it
has been reset normally.)
2
Constantly detected during cooling, dry-
ing, and heating operation.
Short:
-90
:
(194
˚
F) or more
Open:
-40
:
(-40
˚
F) or less
1
Defective thermistor
characteristics
2
Contact failure of connector
(CN20) on the indoor controller
board (Insert failure)
3
Breaking of wire or contact
failure of thermistor wiring
4
Defective indoor controller
board
1
–
3
Check resistance value of thermistor.
0
:
(32
˚
F)
• • • • • • • • • • •
15.0k
"
10
:
(50
˚
F)
• • • • • • • • • • • • •
9.6k
"
20
:
(68
˚
F)
• • • • • • • • • • • • •
6.3k
"
30
:
(86
˚
F)
• • • • • • • • • • • • •
4.3k
"
40
:
(104
˚
F)
• • • • • • • • • • • •
3.0k
"
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor
breaking of wire or contact failure can be detected.
2
Check contact failure of connector (CN20)
on the indoor controller board. Refer to 10-7.
Turn the power on again and check restart
after inserting connector again.
4
Check room temperature display on remote
controller.
Replace indoor controller board if there is abnor-
mal difference with actual room temperature.
Turn the power off, and on again to operate
after check.
P2
Pipe temperature thermistor/Liquid
(TH2)
1
The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 min-
utes. (The unit returns to normal opera-
tion, if it has been reset normally.)
2
Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short:
90
:
(194
˚
F) or more
Open:
-40
:
(-40
˚
F) or less
1
Defective thermistor
characteristics
2
Contact failure of connector
(CN21) on the indoor controller
board (Insert failure)
3
Breaking of wire or contact
failure of thermistor wiring
4
Defective refrigerant circuit is
causing thermistor temperature
of 90
:
(194
˚
F) or more or
-40
:
(-40
˚
F) or less.
5
Defective indoor controller board
1
–
3
Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2
Check contact failure of connector (CN21)
on the indoor controller board. Refer to 10-7.
Turn the power on and check restart after
inserting connector again.
4
Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defect.
5
Check pipe <liquid> temperature with remote
controller in test run mode. If there is extreme
difference with actual pipe <liquid> temperature,
replace indoor controller board.
Turn the power off, and on again to operate
after check.
P4
Drain sensor (DS)
1
Suspensive abnormality, if short/open
of thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
2
Short/open is detected for 30 seconds con-
tinuously during suspensive abnormality.
(The unit returns to normal operation, if
it has been reset normally.)
3
Detect the following condition.
• During cooling and drying operation
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open tem-
perature.
• During drain pump operation
1
Defective thermistor
characteristics
2
Contact failure of connector
(CN31) on the indoor controller
board (Insert failure)
3
Breaking of wire or contact
failure of drain sensor wiring
4
Defective indoor controller board
1
–
3
Check resistance value of thermistor.
0
:
(32
˚
F)
• • • • • • • • • • • •
6.0k
"
10
:
(50
˚
F)
• • • • • • • • • • • •
3.9k
"
20
:
(68
˚
F)
• • • • • • • • • • • •
2.6k
"
30
:
(86
˚
F)
• • • • • • • • • • • •
1.8k
"
40
:
(104
˚
F)
• • • • • • • • • •
1.3k
"
2
Check contact failure of connector (CN31)
on the indoor controller board. Refer to 10-7.
Turn the power on again and check restart
after inserting connector again.
4
Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-
1
and
2
is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
P5
Malfunction of drain pump (DP)
1
Suspensive abnormality, if thermistor
of drain sensor heats itself and
temperature rises slightly. Turn off
compressor and indoor fan.
2
Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3
Constantly detected during drain pump
operation.
1
Malfunction of drain pump
2
Defective drain
Clogged drain pump
Clogged drain pipe
3
Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire.
• Clogged filter is causing
wave of drain.
4
Defective indoor controller board
1
Check if drain pump works.
2
Check drain function.
3
Check the setting of lead wire of drain sensor
and check clogs of the filter.
4
Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-
1
and
2
is short-circuited
and abnormality reappears.
Refer to 10-7.
Turn the power off, and on again to operate
after check.
10-3. SELF-DIAGNOSIS ACTION TABLE
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.