<DRYoperation time chart>
Minimum 3 minutes
w
1
ON
Thermostat
Indoor fan
Booster heater
Compressor
ON
Low speed
LOW speed
ON
ON
OFF
OFF
OFF
OFF
OFF
Operation starts by
P O W E R b u t t o n
ON.
Operation stops by
P O W E R b u t t o n
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
w
1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
2-2 DRYoperation
(1) Compressor control
1
3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2
The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3
The compressor stops in check mode or during protective functions.
FILTER
CHECK MODE
TEST RUN
<How to operate>
1
Press POWER ON/OFF button.
2
Press the
button to display “
”
3
Press the
TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the
or
button is pressed one time.
Dry 19 to 30°C