background image

7

GB

D

F

E

I

NL

P

GR

RU

TR

CZ

SV

HG

PO

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections.

- The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.

Use liquid refrigerant to fill the system.

- If gas refrigerant is used to seal the system, the composition of the refriger-

ant in the cylinder will change and performance may drop.

Do not use a refrigerant other than R410A.

- If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may

cause the refrigerator oil to deteriorate.

Use a vacuum pump with a reverse flow check valve.

- The vacuum pump oil may flow back into the refrigerant cycle and cause the

refrigerator oil to deteriorate.

Do not use the following tools that are used with conventional refriger-
ants.
(Gauge manifold, charge hose, gas leak detector, reverse flow check valve,
refrigerant charge base, vacuum gauge, refrigerant recovery equipment)

- If the conventional refrigerant and refrigerator oil are mixed in the R410A,

the refrigerant may deteriorated.

- If water is mixed in the R410A, the refrigerator oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-

tional refrigerants will not react to it.

Do not use a charging cylinder.

- Using a charging cylinder may cause the refrigerant to deteriorate.

Be especially careful when managing the tools.

- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deterio-

rate.

1.3. Before getting installed

 Caution:

Do not install the unit where combustible gas may leak.

- If the gas leaks and accumulates around the unit, an explosion may result.

Do not use the air conditioner where food, pets, plants, precision instru-
ments, or artwork are kept.

- The quality of the food, etc. may deteriorate.

Do not use the air conditioner in special environments.

- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of

the air conditioner or damage its parts.

When installing the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.

- The inverter equipment, private power generator, high-frequency medical

equipment, or radio communication equipment may cause the air conditioner
to operate erroneously, or fail to operate. On the other hand, the air condi-
tioner may affect such equipment by creating noise that disturbs medical
treatment or image broadcasting.

Do not install the unit on a structure that may cause leakage.

- When the room humidity exceeds 80% or when the drain pipe is clogged,

condensation may drip from the indoor unit. Perform collective drainage work
together with the outdoor unit, as required.

The indoor models should be installed the ceiling over than 2.5 m from
floor.

1.4. Before getting installed (moved) - elec-

trical work

 Caution:

Ground the unit.

- Do not connect the ground wire to gas or water pipes, lightning rods, or

telephone ground lines. Improper grounding may result in electric shock.

Install the power cable so that tension is not applied to the cable.

- Tension may cause the cable to break and generate heat and cause a fire.

Install an leak circuit breaker, as required.

- If an leak circuit breaker is not installed, electric shock may result.

Use power line cables of sufficient current carrying capacity and rating.

- Cables that are too small may leak, generate heat, and cause a fire.

Use only a circuit breaker and fuse of the specified capacity.

- A fuse or circuit breaker of a larger capacity or a steel or copper wire may

result in a general unit failure or fire.

Do not wash the air conditioner units.

- Washing them may cause an electric shock.

Be careful that the installation base is not damaged by long use.

- If the damage is left uncorrected, the unit may fall and cause personal injury

or property damage.

Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.

- Improper drain piping may cause water leakage and damage to furniture

and other possessions.

Be very careful about product transportation.

- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a

means of transportation. It is dangerous.

- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on

the unit base. Also support the outdoor unit at four points so that it cannot
slip sideways.

Safely dispose of the packing materials.

- Packing materials, such as nails and other metal or wooden parts, may cause

stabs or other injuries.

- Tear apart and throw away plastic packaging bags so that children will not

play with them. If children play with a plastic bag which was not torn apart,
they face the risk of suffocation.

1.5. Before starting the test run

 Caution:

Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can

result in severe damage to internal parts. Keep the power switch turned on
during the operational season.

Do not touch the switches with wet fingers.

- Touching a switch with wet fingers can cause electric shock.

Do not touch the refrigerant pipes during and immediately after opera-
tion.

- During and immediately after operation, the refrigerant pipes are may be hot

and may be cold, depending on the condition of the refrigerant flowing through
the refrigerant piping, compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the refrigerant pipes.

Do not operate the air conditioner with the panels and guards removed.

- Rotating, hot, or high-voltage parts can cause injuries.

Do not turn off the power immediately after stopping operation.

- Always wait at least five minutes before turning off the power. Otherwise,

water leakage and trouble may occur.

2. Indoor unit accessories

The unit is provided with the following accessories:

3. Selecting an installation site

Select a site with sturdy fixed surface sufficiently durable against the weight of
unit.

Before installing unit, the routing to carry in unit to the installation site should
be determined.

Select a site where the unit is not affected by entering air.

Select a site where the flow of supply and return air is not blocked.

Select a site where refrigerant piping can easily be led to the outside.

Select a site which allows the supply air to be distributed fully in room.

Do not install unit at a site with oil splashing or steam in much quantity.

Do not install unit at a site where combustible gas may generate, flow in, stag-
nate or leak.

Do not install unit at a site where equipment generating high frequency waves
(a high frequency wave welder for example) is provided.

No.

Accessories

Quantity

1

Insulation pipe 25 mm small diameter

1

2

Insulation pipe 125 mm small diameter

1

3

Insulation pipe 120 mm large diameter

1

4

Tie band (small)

2

5

Tie band (large)

5

6

Drain hose

1

7

Washer

8

8

Wired remote controller

1

WT05749X01_GB.p65

09/11/6, 12:27

7

Содержание Mr.Slim PEA-RP200WHA

Страница 1: ...Air Conditioners INDOOR UNIT PEA RP170 200 WHA GB INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit ...

Страница 2: ... Refrigerant piping liquid C Refrigerant piping gas D Control box E Drain pipe F Air outlet 200 300 150 200 50 50 1350 730 450 470 more than 20 30 10 more than 20 more than 100 60 23 1324 23 37 1250 1100 1100 800 1034 B C D A A E Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned 701 494 235 1034 1324 A A B A 165 52 100 244 30 424 A B E C D F A Access doo...

Страница 3: ...en the insulation and the main body I Thermal insulation tubing small supplied 1 J Ties large supplied 4 K Ensure that there is no gap here Place join upwards L Thermal insulation tubing medium supplied 2 M Thermal insulation N Pull O Flared pipe end P Wrap with damp cloth Q Return to original position R Ensure that there is no gap here Fig 7 2 1 A B 1 C C C D 2 E A Downward slope 1 100 or more B ...

Страница 4: ... Air outlet I Keep duct work length 850 mm or more A Non polarized B TB15 C Remote Controller D TB4 Fig 9 2 2 B G E F H A I C C D D A B C 9 3 A Terminal bed box B Knockout hole C Remove A Screw holding cover 2pcs B Cover Fig 9 3 1 Fig 9 3 2 A B B C A A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C Remote controller A C TB4 TB15 B S1 S2 S3 S1 S2 S3 2...

Страница 5: ...F button B Test run display C Indoor temperature liquid line temperature display D ON OFF lamp E Power display A CHECK button B Refrigerant address C TEMP button D IC Indoor unit OC Outdoor unit E Check code F Error code display Test run remaining time display G Set temperature button H Mode selection button I Fan speed button M TEST button A Filter button Enter button B TEST button C Set Time but...

Страница 6: ...on the unit If a different refrigerant or air is mixed with the original refrigerant the refrig erant cycle may malfunction and the unit may be damaged If the air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent...

Страница 7: ...fied capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do not wash the air conditioner units Washing them may cause an electric shock Be careful that the installation base is not damaged by long use If the damage is left uncorrected the unit may fall and cause personal injury or property damage Install the drain piping ac...

Страница 8: ...indoor pipes with form polyethylene insulation with a minimum density of 0 03 and a thickness as specified in the table below 1 Select the thickness of insulating material by pipe size Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high temperature and hu...

Страница 9: ...Insertion margin F Drain hose accessory G Drain pipe O D ø32 PVC TUBE field supply H Insulating material field supply I Max 145 5 mm 7 Connecting refrigerant pipes and drain pipes 7 1 Refrigerant piping work This piping work must be done in accordance with the installation manuals for both outdoor unit For constraints on pipe length and allowable difference of elevation refer to the outdoor unit m...

Страница 10: ...ion and supplied installation manuals Special circuits should also be used If the power cir cuit lacks capacity or has an installation failure it may cause a risk of elec tric shock or fire 1 Be sure to install an earth leakage breaker to the power 2 Install the unit to prevent that any of the control circuit cables remote control ler transmission cables is brought in direct contact with the power...

Страница 11: ...for at least 2 seconds FUNCTION will start to flash 2 Use the C button to set the refrigerant address 3 to 00 3 Press D and will start to flash in the unit number 4 display 4 Use the C button to set the unit number 4 to 01 04 or AL 5 Press the E MODE button to designate the refrigerant address unit number will flash in the mode number 1 display momentarily 6 Press the F buttons to set the mode num...

Страница 12: ...election button and switch to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be regis...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC This product is designed and intended for use in the residential commer cial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K ...

Отзывы: