11
GB
D
F
E
I
NL
P
GR
RU
TR
CZ
SV
HG
PO
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension
may break, or overheat and burn.
9.3. Connecting electrical connections
Please identify the model name of the operation manual attached on the terminal
bed box cover with that shown on the rating name plate.
1. Remove the screw (2pcs) holding the cover to dismount the cover.
[Fig. 9.3.1] (P.4)
A
Screw holding cover (2pcs)
B
Cover
2. Open knockout holes
(Recommend to use a screwdriver or the like for this work.)
[Fig. 9.3.2] (P.4)
A
Terminal bed box
B
Knockout hole
C
Remove
3. Fix power source wiring to terminal bed box by using buffer bushing for tensile
force. (PG connection or the like.) Connect transmission wiring to transmission
terminal bed through the knockout hole of terminal bed box using ordinary
bushing.
4. Connect the power source, Earth, transmission and remote controller wiring.
The dismounting of the terminal bed box is not needed.
[Fig. 9.3.3] (P.5)
E
Use PG bushing to keep the weight of the cable and external force from being
applied to the power supply terminal connector. Use a cable tie to secure the
cable.
Wind the wire around the cable strap once to keep it from being pulled out.
F
Power source wiring
G
Tensile force
H
Use ordinary bushing
I
Power source terminal bed
J
Terminal bed for indoor transmission
K
Terminal bed for remote controller
L
To 1-phase power source
M
Transmission line
N
Terminal bed for outdoor transmission line
O
Transmission line to the remote controller
[Transmission cable connection]
[Fig. 9.3.4] (P.5)
A
Terminal bed
B
Round terminal
C
Transmission cable (polar)
5. After wiring is complete, make sure again that there is no slack on the connec-
tions, and attach the cover onto the terminal bed box in the reverse order of
removal.
Notes:
•
Do not pinch the cables or wires when attaching the terminal bed box
cover. Doing so may cause a risk of disconnection.
•
When accommodating the terminal bed box, make sure that the connec-
tors on the box side are not removed. If removed, it cannot operate nor-
mally.
9.4. Function settings (Function selection
via the remote controller)
9.4.1
Function setting on the unit (Selecting the unit
functions)
1) Changing the external static pressure setting [Fig. 9.4.1] (P.5)
•
Be sure to change the external static pressure setting depending on the duct
and the grill used.
1
Go to the function setting mode.
Switch OFF the remote controller.
Press the
A
and
B
buttons simultaneously and hold them for at least
2 seconds. FUNCTION will start to flash.
2
Use the
C
button to set the refrigerant address (
3
) to 00.
3
Press
D
and [--] will start to flash in the unit number (
4
) display.
4
Use the
C
button to set the unit number (
4
) to 01-04 or AL.
5
Press the
E
MODE button to designate the refrigerant address/unit number.
[--] will flash in the mode number (
1
) display momentarily.
6
Press the
F
buttons to set the mode number (
1
) to 08.
7
Press the
G
button and the current set setting number (
2
) will flash.
Use the
F
button to switch the setting number in response to the external
static pressure to be used.
8
Press the MODE button
E
and mode and the setting number (
1
) and (
2
) will
change to being on constantly and the contents of the setting can be con-
firmed.
9
Press the FILTER
A
and TEST RUN
B
buttons simultaneously for at least two
seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.
2) Other functions
1
Select unit number 00 for the settings. (Settings for all indoor units)
Refer to Function table 1.
2
Select unit number 01 to 04 or AL for the settings. (Settings for each indoor
unit)
To set the indoor unit in the individual system, select unit number 01.
To set each indoor unit of two, three or four indoor units, which are connected
when these units are simultaneously in operation, select unit number 01 to 04.
To set all indoor units of two, three or four indoor units which are connected
when these units are simultaneously in operation, select AL.
Refer to Function table 2.
External static
pressure
60 Pa
75 Pa
100 Pa
150 Pa (before shipment)
Setting no. of mode
no. 08
1
2
3
1
Setting no. of mode
no. 10
2
2
2
1
Function table 2
Select unit numbers 01 to 04 or all units (AL [wired remote controller]/07 [wireless remote controller])
*1 When the power supply returns, the air conditioner will start 3 minutes later.
Note:
When the function of an indoor unit were changed by function selection after the end of installation, always indicate the contents by entering a or other mark in the
appropriate check filed of the tables.
Mode
Filter sign
Settings
100 Hr
2500 Hr
No filter sign indicator
Mode no.
Setting no. Initial setting
Check
1
07
2
3
Function table 1
Select unit number 00
Settings
Not available
Available
Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
Mode no.
Setting no. Initial setting
Check
1
01
2
1
02
2
3
1
03
2
3
Mode
Power failure automatic recovery*1
(AUTO RESTART FUNCTION)
Indoor temperature detecting
LOSSNAY connectivity
WT05749X01_GB.p65
09/11/6, 12:27
11