background image

Air-Conditioners
INDOOR UNIT

PEA-RP170,200 WHA

GB

INSTALLATION MANUAL

For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.

WT05749X01_cv.p65

09/9/15, 16:35

3

Содержание Mr.Slim PEA-RP200WHA

Страница 1: ...Air Conditioners INDOOR UNIT PEA RP170 200 WHA GB INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit ...

Страница 2: ... Refrigerant piping liquid C Refrigerant piping gas D Control box E Drain pipe F Air outlet 200 300 150 200 50 50 1350 730 450 470 more than 20 30 10 more than 20 more than 100 60 23 1324 23 37 1250 1100 1100 800 1034 B C D A A E Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned 701 494 235 1034 1324 A A B A 165 52 100 244 30 424 A B E C D F A Access doo...

Страница 3: ...en the insulation and the main body I Thermal insulation tubing small supplied 1 J Ties large supplied 4 K Ensure that there is no gap here Place join upwards L Thermal insulation tubing medium supplied 2 M Thermal insulation N Pull O Flared pipe end P Wrap with damp cloth Q Return to original position R Ensure that there is no gap here Fig 7 2 1 A B 1 C C C D 2 E A Downward slope 1 100 or more B ...

Страница 4: ... Air outlet I Keep duct work length 850 mm or more A Non polarized B TB15 C Remote Controller D TB4 Fig 9 2 2 B G E F H A I C C D D A B C 9 3 A Terminal bed box B Knockout hole C Remove A Screw holding cover 2pcs B Cover Fig 9 3 1 Fig 9 3 2 A B B C A A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C Remote controller A C TB4 TB15 B S1 S2 S3 S1 S2 S3 2...

Страница 5: ...F button B Test run display C Indoor temperature liquid line temperature display D ON OFF lamp E Power display A CHECK button B Refrigerant address C TEMP button D IC Indoor unit OC Outdoor unit E Check code F Error code display Test run remaining time display G Set temperature button H Mode selection button I Fan speed button M TEST button A Filter button Enter button B TEST button C Set Time but...

Страница 6: ...on the unit If a different refrigerant or air is mixed with the original refrigerant the refrig erant cycle may malfunction and the unit may be damaged If the air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent...

Страница 7: ...fied capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do not wash the air conditioner units Washing them may cause an electric shock Be careful that the installation base is not damaged by long use If the damage is left uncorrected the unit may fall and cause personal injury or property damage Install the drain piping ac...

Страница 8: ...indoor pipes with form polyethylene insulation with a minimum density of 0 03 and a thickness as specified in the table below 1 Select the thickness of insulating material by pipe size Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high temperature and hu...

Страница 9: ...Insertion margin F Drain hose accessory G Drain pipe O D ø32 PVC TUBE field supply H Insulating material field supply I Max 145 5 mm 7 Connecting refrigerant pipes and drain pipes 7 1 Refrigerant piping work This piping work must be done in accordance with the installation manuals for both outdoor unit For constraints on pipe length and allowable difference of elevation refer to the outdoor unit m...

Страница 10: ...ion and supplied installation manuals Special circuits should also be used If the power cir cuit lacks capacity or has an installation failure it may cause a risk of elec tric shock or fire 1 Be sure to install an earth leakage breaker to the power 2 Install the unit to prevent that any of the control circuit cables remote control ler transmission cables is brought in direct contact with the power...

Страница 11: ...for at least 2 seconds FUNCTION will start to flash 2 Use the C button to set the refrigerant address 3 to 00 3 Press D and will start to flash in the unit number 4 display 4 Use the C button to set the unit number 4 to 01 04 or AL 5 Press the E MODE button to designate the refrigerant address unit number will flash in the mode number 1 display momentarily 6 Press the F buttons to set the mode num...

Страница 12: ...election button and switch to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be regis...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC This product is designed and intended for use in the residential commer cial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K ...

Отзывы: