12
Having trouble?
Here is the solution. (Unit is operating normally.)
Noise is louder than specifications.
■
The indoor operation sound level is affected by the acoustics of the
particular room as shown in the following table and will be higher than
the noise specification, which was measured in an echo-free room.
High sound-
absorbing rooms Normal rooms
Low sound-
absorbing rooms
Location
examples
Broadcasting
studio, music
room, etc.
Reception room,
hotel lobby, etc.
Office, hotel
room
Noise levels
3 to 7 dB
6 to 10 dB
9 to 13 dB
Nothing appears in the wireless remote controller display, the display
is faint, or signals are not received by the indoor unit unless the remote
controller is close.
■
The batteries are low.
Replace the batteries and press the Reset button.
■
If nothing appears even after the batteries are replaced, make sure that
the batteries are installed in the correct directions (+, –).
The operation lamp near the receiver for the wireless remote controller
on the indoor unit is flashing.
■
The self diagnosis function has operated to protect the air conditioner.
■
Do not attempt to repair this equipment by yourself.
Turn off the power switch immediately and consult your dealer. Be sure
to provide the dealer with the model name.
6. Trouble Shooting
Item Model
PEA-M100GAA
PEA-M125GAA
PEA-M140GAA
Dimension
Height / Width / Depth
mm
400/1400/634
400/1400/634
400/1400/634
Net weight
kg
63
63
63
Airflow rate
50Pa
m
3
/min
34-42
48-60
Fan
(Low-High)
100Pa
m
3
/min
34-42
43-54
150Pa
m
3
/min
34-42
41-52
External static pressure
Pa
50/100/150
Sound pressure level
50Pa
dB(A)
39-42
42-45
(Low-High)
100Pa
dB(A)
42-45
43-47
150Pa
dB(A)
44-48
45-49
7. Specifications