20
E6
1
Contact failure, short circuit or,
mis-wiring (converse wiring) of
indoor/outdoor unit connecting
wire
2
Defective transmitting receiving
circuit of indoor controller board
3
Defective transmitting receiving
circuit of indoor controller board
4
Noise has entered into indoor/
outdoor unit connecting wire.
∗
Check LED display on the outdoor control cir-
cuit board. (Connect A-control service tool,
PAC-SK52ST.)
Refer to EA-EC item if LED displays EA-EC.
1
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin triple
indoor unit system.
2
-
4
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board.
∗
Other indoor controller board may have
defect in case of twin triple indoor unit
system.
E7
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
1
Defective transmitting receiving
circuit of indoor controller board
2
Noise has entered into power
supply.
3
Noise has entered into outdoor
control wire.
1
-
3
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
Indoor/outdoor unit communication
error (Signal receiving error)
1
Abnormal if indoor controller board
cannot receive any signal normally for
six minutes after turning the power on.
2
Abnormal if indoor controller board
cannot receive any signal normally for
three minutes.
3
Consider the unit as abnormal under the
following condition: When two or more
indoor units are connected to an
outdoor unit, indoor controller board
cannot receive a signal for three minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Error Code
Abnormal point and detection method
Cause
Countermeasure
Fb
Indoor controller board
Abnormal if data cannot be read normally
from the nonvolatile memory of the indoor
controller board.
1
Defective indoor controller
board
1
Replace indoor controller board.
E1
or
E2
Remote controller control board
1
Abnormal if data cannot be read normal-
ly from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
2
Abnormal if the clock function of remote
controller cannot be operated normally.
(Error code: E2)
1
Defective remote controller
1
Replace remote controller.
PA
(2500)
Water leakage
This detection is performed during the
operation (stop, heating, fan, or error stop
mode etc.) other than cooling and dry.
1
When a) and b) are found, water leakage
occurs.
a) Pipe <liquid> temperature - inlet tem-
perature < -10˚C[14˚F] for 30 minutes
b) When drain float switch is detected to
be soaked in the water for 15 minutes
or more.
* When drain float switch is detected to
be NOT soaked in the water, each
counting of a) and b) is cleared.
*When this error is detected, the error
will not be reset until the main power is
reset.
1
Mis-piping of extension pipes
(When connected with multiple
units)
2
Mis-wiring of indoor/outdoor
unit connecting wire (When
connected with multiple units)
3
Detection failure of the indoor
unit inlet/ pipe <liquid> ther-
mistor
4
Drain pump failure
5
Drainage failure
· Clogged drain pump
· Clogged drain pipe
6
Drain float switch failure
· Drain float switch is detected
to be soaked in the water (ON
status) due to the operation
failure of the moving parts.
· Contact failure of drain float
switch connector
(Loose connector)
1
Check the extension pipes for mis-piping.
2
Check the Indoor/outdoor unit connecting
wire for mis-wiring.
3
Check room temperature display on remote
controller and indoor pipe <liquid> tempera-
ture. (Refer to the countermeasure on P2.)
4
Check if drain-up machine works.
5
Check drain function.
6
Check drain float switch. (Refer to the coun-
termeasure on P4 and P5.)