(3) Environment 

Operate the servo amplifier at or above pollution degree 2 set forth in EN 60664-1. For this 

purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, 

dust, dirt, etc. (IP54). 

 

(4) Power supply 

(a) This servo amplifier can be used under the conditions of the overvolttage category   set forth 

in EN 60664-1, a reinforced insulating transformer is not required in the power input section. 

Unit shall be supplied from a three phase earthed neutral system. 

 

(b) For the interface power supply, use a 24VDC power supply with reinforced insulation on I/O 

terminals. 

 

(5) Grounding 

(a) To prevent an electric shock, the protective earth (PE) terminal (marked  ) of the servo 

amplifier must be connected to the protective earth (PE) of the control box. 

 

(b) Do not connect two ground cables to the same protective earth (PE) terminal. Always connect 

cables to the terminals one-to-one. 

PE terminals

PE terminals

 

(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) 

terminals of the servo amplifier must be connected to the corresponding earth terminals. 

 

(6) Wiring 

(a) The wires to be connected to the terminal block of the servo amplifier must have crimping 

terminals provided with insulating tubes to prevent contact with adjacent terminals. 

Crimping terminal 

Insulating tube 

Wire

 

(b) Use the servo motor side power connector which complies with the EN Standard. 

The EN Standard-compliant power connector sets are available as options. 

 

(c) The servo amplifier must be installed in the metal cabinet (control box). 

 

(7) Auxiliary equipment and options 

(a) Use the molded-case circuit breaker and magnetic contactor models which are EN 

Standard-compliant products given in the MR-J2S-400VAC Compatible Servo Amplifier 

Supplementary Instruction Manual. 

 

(b) The sizes of the wires given in the MR-J2S-400VAC Compatible Servo Amplifier Supplementary 

Instruction Manual meet the following conditions. For use in any other conditions, follow 

Table 5 and Annex C of EN 60204-1. 

Ambient temperature: 40  (104 ) 

Sheath 

: PVC (polyvinyl chloride) 

Installation on wall surface or open cable tray 

 

 (c) Use the EMC filter for noise reduction. 

 

(8) Performing EMC tests 

When EMC tests are run on a machine/device into which the servo amplifier has been installed, it 

must conform to the electromagnetic compatibility (immunity/emission) standards after it has 

satisfied the operating environment/electrical equipment specifications. For the other EMC 

directive guidelines on the servo amplifier, refer to the EMC Installation Guidelines 

(IB(NA)67310). 

- MR-J2-Super Series are not intended to be used on a low-voltage public network which supplies 

domestic premises; 

- radio frequency interference is expected if used on such a network. 

The installer shall provide a guide for Installation and use, including recommended mitigation 

devices. 

 

3.  CONFORMANCE WITH UL/cUL STANDARD 

This servo amplifier complies with UL 508C and CSA C22.2 No.14 standard. 

Refer to section 1.3 (2) for the servo amplifier model names described in the tables and figures. 

 

(1) Servo amplifier and servo motor used 

Use the servo amplifiers and servo motors which standard product. 

 

  

 

Servo 

motor 

 

Servo 

amplifier 

HC-SFS  HA-LFS  

  

1000r/min 

1500r/min 

2000r/min 

MR-J2S-60A4/B4 524   

 

 

MR-J2S-100A4/B4 1024 

 

 

 

MR-J2S-200A4/B4 1524 2024  

 

 

MR-J2S-350A4/B4 3524 

 

 

 

MR-J2S-500A4/B4 5024 

 

 

 

MR-J2S-700A4/B4 7024  6014 701M4   
MR-J2S-11KA4/B4  

80141 2K14 11K1M4 

11K24 

MR-J2S-15KA4/B4   15K14 

15K1M4 

15K24 

MR-J2S-22KA4/B4  

20K14 25K14 22K1M4 

22K24 

 

(2) Installation 

The MR-J2S series have been approved as the products which have been installed in the 

electrical enclosure. The minimum enclosure size is based on 150  of each MR-J2S 

combination. And also, design the enclosure so that the ambient temperature in the enclosure is 

55  (131 ) or less, refer to the spec manual. The servo amplifier must be installed in the metal 

cabinet (control box). For environment, the units should be used in open type (UL 50) and 

overvoltage category III or lower. The servo amplifier need to be installed at or below of pollution 

degree 2. For connection, use copper wires. 

 

(3) Short-circuit current rating (SCCR) 

Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 kA rms Symmetrical 

Amperes, 500 Volts Maximum. 

 

(4) Flange 

Mount the servo motor on a flange which has the following size or produces an equivalent or 

higher heat dissipation effect. 

 

Servo motor 

Flange size 

[mm (in)] 

HC-SFS HA-LFS 

250 250 12 

(9.84 9.84 0.47) 

524 to 1524 

 

300 300 12 

(11.81 11.81 0.47) 

2024 3524  

650 650 35 

(25.59 25.59 1.38) 

5024 7024 

6014 to 12K14 

701M4 15K1M4 

11K24 to 22K24 

950 950 35 

(37.43 37.43 1.38) 

 

15K14 to 22K14 

22K1M4 

 

 

(5) About wiring protection 

For installation in United States, branch circuit protection must be provided, in accordance with 

the National Electrical Code and any applicable local codes. 

For installation in Canada, branch circuit protection must be provided, in accordance with the 

Canada Electrical Code and any applicable provincial codes.

 

 

 

(6) Capacitor discharge time 

The capacitor discharge time is as follows.To ensure safety, do not touch the charging section for 

15 minutes after power-off. 

 

Servo amplifier 

Discharge time (min) 

MR-J2S-60A4/B4 1 

MR-J2S-100A4/B4 2 
MR-J2S-200A4/B4 2 
MR-J2S-350A4/B4 5 
MR-J2S-500A4/B4 5 
MR-J2S-700A4/B4 8 

MR-J2S-11KA4/B4 4 
MR-J2S-15KA4/B4 6 
MR-J2S-22KA4/B4 8 

 

(7) Options, peripheral devices 

Use the UL/cUL Standard-compliant products. 

Use the molded-case circuit breaker (UL489 Listed MCCB) or a Class K5 fuse indicated in the 

table below. 

 

Molded-case  

circuit breaker 

(Note) 

Fuse 

Molded-case  

circuit breaker 

 (Note) 

Fuse 

Servo amplifier 

Current  Voltage 

AC 

Current 

[A] 

Voltage 

AC [V] 

Servo amplifier 

Current 

Voltage

AC 

Current

[A] 

Voltage

AC [V]

MR-J2S-60 4 

30A frame 

5A 

 10  MR-J2S-700 4  50A frame 

40A 

 55  

MR-J2S-100 4 30A frame 

10A 

 15  MR-J2S-11K 4  60A frame 

60A 

90 

MR-J2S-200 4 30A frame 

15A 

600Y/

347V 

20 600 MR-J2S-15K 4  100A frame

75A 

600Y/

347V

125 

600 

MR-J2S-350 4 30A frame 

20A 

 30  MR-J2S-22K 4  225A frame

125A 

 150  

MR-J2S-500 4 30A frame 

30A 

 40  

   

 

 

 

 

Note. When the power factor improving reactor is not used. 

 

(8) Selection example of wires 

To comply with the UL/cUL Standard, use UL-approved copper wires rated at 60/75  (140/167 ) 

for wiring. 

 

 

 

(Note 1) Wires [mm

2

]    

Servo amplifier 

L

1

L

2

L

3

 

L

11

L

21

  U V W P

1

P

 (Note 2) 

P C B1 B2 BU BV BW

MR-J2S-60A4/B4  

100A4/B4 

2(AWG14):a  

1.25(AWG16):a  

 

MR-J2S-200A4/B4  

 

2(AWG14):a 

 

1.25 

MR-J2S-350A4/B4 3.5(AWG12):b 

 

3.5(AWG12):b 

(AWG14):a (AWG16)

MR-J2S-500A4/B4  

700A4/B4 

5.5(AWG10):b 

1.25 

(AWG16)  5.5(AWG10):b  

 

 

MR-J2S-11KA4/B4 8(AWG8):c 

 

8(AWG8):c  3.5 

(AWG12):b

MR-J2S-15KA4/B4  

22KA4/B4 

14(AWG6):d  22(AWG4):e 5.5 

(AWG10):b

(AWG14)

2(AWG14) 

Note 1. Alphabets in the table indicate crimping tools. Refer to the following table for the crimping terminals and crimping tools. 

2. 7kW or less does not have P

1

 

Use the wires of the following sizes with the brake unit (FR-BU) and power regenerative 

converter (FR-RC). 

 

Model Wires 

[mm

2

FR-BU-H15K 
FR-BU-H30K 

3.5(AWG12) 

FR-BU-H55K 8(AWG8) 

 

Table: Recommended crimping terminals 

Servo amplifier side crimping terminal 

Symbol 

Crimping terminals 

Applicable tool 

Manufacturer name 

a 32959 

47387 

Tyco 

Electronics 

b FVD5.5-4  YNT-1210S 

c FVD8-5 

Body YF-1 E-4 

Head YNE-38 

Dies DH-111 DH-121 

d FVD14-6 

Body YF-1 E-4 

Head YNE-38 

Dies DH-112 DH-122 

e FVD22-6 

Body YF-1 E-4 

Head YNE-38 

Dies DH-113 DH-123 

Japan Solderless 

Terminals 

 

(9) Terminal block tightening torque 

Tightening torque [N m] ([lb in]) 

Servo amplifier 

TE1 TE2  PE 

MR-J2S-60A4/B4 to 200A4/B4 

 

 

 

MR-J2S-350A4/B4 500A4/B4 

1.0 (9) 

1.2 (10) 

MR-J2S-700A4 

1.2 (10) 

0.8 (7) 

 

MR-J2S-11KA4/B4 15KA4/B4 3.0 

(26) 

MR-J2S-22KA4/B4 6.0 

(52) 

1.2 (10) 

6.0 (52) 

 

(10)Overload Protection Characteristics 

An electronic thermal relay is built in the servo amplifier to protect the servo motor, servo 

amplifier and servo motor power line from overloads. The operation characteristics of the 

electronic thermal relay are shown below. It is recommended to use an unbalanced 

torque-generated machine, such as a vertical motion shaft, so that unbalanced torque is not more 

than 70  of the rated torque. 

Servo amplifier MR-J2S series have servo motor overload protection. (The motor full load current 

is 115  rated current.) 

 

1000

100

10

1

0.1

0

50

150

200

250

300

Load ratio [%] 

100

O

per

ati

on ti

m

[s

]

In operation

In servo lock

 

MR-J2S-60A4/B4 to 100A4/B4 

1000

100

10

1

0.1

0

50

150

200

250

300

100

O

per

at

io

n t

im

e

 [s

]

Load ratio [%] 

In operation

In servo lock

 

MR-J2S-200A4/B4 350A4/B4 

 

 

0

1

10

100

1000

10000

Op

erat

ion

 tim

e

 [

s]

Load ratio [%]

In operation

In servo lock

50

100

150

200

250

300

 

MR-J2S-500A4/B4 700A4/B4 

10000

1000

100

10

1

0

Load ratio [%]

O

perati

o

n ti

m

e

 [

s]

In operation

In servo lock

100

200

300

 

MR-J2S-11KA4/B4 to 22KA4/B4 

 

(11)Over-temperature protection for motor 

Motor Over temperature sensing is not provided by the drive. 

 

(12)Figure configuration 

Representative configuration example to conform to the UL/cUL standard is shown below.

 

The 

earth wiring is excluded from the figure configuration. 

Fuse

or

molded-case

circuit breaker

L

1,

L

2,

L

3

L

11,

L

21

CN1B CN1A

CN3

CN2

U, V, W

Command device

Encoder cable

Control panel side

Machine side

Servo motor

Encoder

Power
supply

 

 

4.  INSPECTION 

WARNING

Before starting maintenance and/or inspection, turn off the power and wait for 
15 minutes or more until the charge lamp turns off. Then, confirm that the 
voltage between P and N is safe with a voltage tester and others. Otherwise, 
an electric shock may occur. In addition, always confirm from the front of the 
servo amplifier whether the charge lamp is off or not. 
Any person who is involved in inspection should be fully competent to do the 
work. Otherwise, you may get an electric shock. For repair and parts 
replacement, contact your safes representative. 

 

 

CAUTION

Do not test the servo amplifier with a megger (measure insulation resistance), 
or it may become faulty. 
Do not disassemble and/or repair the equipment on customer side. 

 

 
(1) Inspection 

It is recommended to make the following checks periodically. 

 

(a) Check for loose terminal block screws. Retighten any loose screws. 

 

(b) Check the servo motor bearings, brake section, etc. for unusual noise. 

 

(c) Check the cables and the like for scratches and cracks. Perform periodic inspection according 

to operating conditions. 

 

(d) Check the servo motor shaft and coupling for misalignment. 

 

(2) Life 

The following parts must be changed periodically as listed below. If any part is found faulty, it 

must be changed immediately even when it has not yet reached the end of its life, which depends 

on the operating method and environmental conditions. 

For use in the atmosphere having much oil mist, dust, etc., clean and inspect every three months. 

For parts replacement, please contact your sales representative. 

 

 

Part name 

Standard life 

Smoothing capacitor 

10 years 

Relay 

Number of power-on and number of 

emergency stop times: 100,000 times 

Cooling fan 

10,000 to 30,000 hours (2 to 3 years) 

Servo amplifier 

Absolute position battery 

Refer to the MR-J2S-  Servo Amplifier 

Instruction Manual. 

Bearings 

20,000 to 30,000 hours 

Encoder 

20,000 to 30,000 hours 

Oil seal, V ring 

5,000 hours 

Servo motor 

Cooling fan 

20,000 hours 

 

(a) Smoothing capacitor 

Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor 

greatly depends on ambient temperature and operating conditions. The capacitor will reach 

the end of its life in 10 years of continuous operation in normal air-conditioned environment 

(Surrounding air temperature of 40  (104 ) or less.). 

 

(b) Relays 

Their contacts will wear due to switching currents and contact faults occur. Relays reach the 

end of their life when the cumulative number of power-on and emergency stop times is 

100,000, which depends on the power supply capacity 

 

(c) Servo amplifier cooling fan 

The cooling fan bearings reach the end of their life in 10,000 to 30,000 hours. Normally, 

therefore, the fan must be changed in a few years of continuous operation as a guideline. 

It must also be changed if unusual noise or vibration is found during inspection. 

 

 

(d) Servo motor bearings 

When the servo motor is run at rated speed under rated load, change the bearings in 20,000 to 

30,000 hours as a guideline. This differs on the operating conditions. The bearings must also 

be changed if unusual noise or vibration is found during inspection. 

 

(e) Servo motor oil seal, V ring 

Must be changed in 5,000 hours of operation at rated speed as a guideline. This differs on the 

operating conditions. These parts must also be changed if oil leakage, etc. is found during 

inspection. 

 

(f) Servo motor cooling fan 

The design life of the cooling fan is 20,000 hours. Change the cooling fan periodically. 

 

5.  ALARMS AND WARNINGS 

5.1  Alarms 

Indication 

Name Indication

Name Indication

Name 

10 

Under voltage 

30 

Regenerative error 

46 

Servo motor overheat 

12 

Memory error 1 

31 

Over speed 

50 

Overload 1 

13 

Clock error 

32 

Over current 

51 

Overload 2 

15 

Memory error 2 

33 

Over voltage 

52 

Error excessive 

16 

Encoder error 1 

34 

CRC error 

Serial communication 

17 

Board error 

Command pulse 

8A 

time-out error 

19 

Memory error 3 

35 

frequency error 

Serial communication 

1A 

Motor combination error

36 

Transfer error 

8E 

error 

20 Encoder 

error 

2 37 

Parameter 

error 88 

Watchdog 

24 

Main circuit error 

Main circuit device 

 

 

25 

Absolute position erase 

45 

Overheat  

 

 

5.2  Warnings 

Indication 

Name Indication

Name Indication

Name 

Battery cable  

E1 

Overload warning 

Controller emergency 

92 

disconnection warning 

Absolute position 

E7 

stop warning 

Home position setting 

E3 

counter warning 

Main circuit off 

96 

warning E4 

Parameter 

warning 

E9 

warning 

9F 

Battery warning 

E5 

ABS time-out warning 

EA 

ABS servo-on warning 

Excessive regenerative 

Servo emergency stop 

EE 

SSCNET error warning 

E0 

warning 

E6 

warning  

 

 

 

Warranty 

1. Warranty period and coverage 
We will repair any failure or defect hereinafter referred to as "failure" in our FA equipment hereinafter referred to as the 
"Product" arisen during warranty period at no charge due to causes for which we are responsible through the distributor from 
which you purchased the Product or our service provider. However, we will charge the actual cost of dispatching our engineer 
for an on-site repair work on request by customer in Japan or overseas countries. We are not responsible for any on-site 
readjustment and/or trial run that may be required after a defective unit are repaired or replaced. 

 

[Term] 
The term of warranty for Product is twelve (12) months after your purchase or delivery of the Product to a place designated by 
you or eighteen (18) months from the date of manufacture whichever comes first (“Warranty Period”). Warranty period for 
repaired Product cannot exceed beyond the original warranty period before any repair work. 

 

[Limitations] 
(1) You are requested to conduct an initial failure diagnosis by yourself, as a general rule. It can also be carried out by us or our 

service company upon your request and the actual cost will be charged. 
However, it will not be charged if we are responsible for the cause of the failure. 

 

(2) This limited warranty applies only when the condition, method, environment, etc. of use are in compliance with the terms 

and conditions and instructions that are set forth in the instruction manual and user manual for the Product and the caution 
label affixed to the Product. 

 

(3) Even during the term of warranty, the repair cost will be charged on you in the following cases; 

 

(i) 

: a failure caused by your improper storing or handling, carelessness or negligence, etc., and a failure caused by your 

hardware or software problem 

 

(ii)  : a failure caused by any alteration, etc. to the Product made on your side without our approval 

 

(iii)  : a failure which may be regarded as avoidable, if your equipment in which the Product is incorporated is equipped with 

a safety device required by applicable laws and has any function or structure considered to be indispensable 
according to a common sense in the industry 

 

(iv)  : a failure which may be regarded as avoidable if consumable parts designated in the instruction manual, etc. are duly 

maintained and replaced 

 

(v)  : any replacement of consumable parts (battery, fan, smoothing capacitor, etc.) 

 

(vi)  : a failure caused by external factors such as inevitable accidents, including without limitation fire and abnormal 

fluctuation of voltage, and acts of God, including without limitation earthquake, lightning and natural disasters 

 

(vii)  : a failure generated by an unforeseeable cause with a scientific technology that was not available at the time of the 

shipment of the Product from our company 

 

(viii)  : any other failures which we are not responsible for or which you acknowledge we are not responsible for 

 

2. Term of warranty after the stop of production 
(1) We may accept the repair at charge for another seven (7) years after the production of the product is discontinued. The 

announcement of the stop of production for each model can be seen in our Sales and Service, etc. 

 

(2) Please note that the Product (including its spare parts) cannot be ordered after its stop of production. 

 

3. Service in overseas countries 
Our regional FA Center in overseas countries will accept the repair work of the Product. However, the terms and conditions of 
the repair work may differ depending on each FA Center. Please ask your local FA center for details. 

 

4. Exclusion of responsibility for compensation against loss of opportunity, secondary loss, etc. 
Whether under or after the term of warranty, we assume no responsibility for any damages arisen from causes for which we 
are not responsible, any losses of opportunity and/or profit incurred by you due to a failure of the Product, any damages, 
secondary damages or compensation for accidents arisen under a specific circumstance that are foreseen or unforeseen by 
our company, any damages to products other than the Product, and also compensation for any replacement work, 
readjustment, start-up test run of local machines and the Product and any other operations conducted by you. 

 

5. Change of Product specifications 
Specifications listed in our catalogs, manuals or technical documents may be changed without notice. 

 

6. Application and use of the Product 
(1) For the use of our General-Purpose AC Servo, its applications should be those that may not result in a serious damage 

even if any failure or malfunction occurs in General-Purpose AC Servo, and a backup or fail-safe function should operate 
on an external system to General-Purpose AC Servo when any failure or malfunction occurs. 

 

(2) Our General-Purpose AC Servo is designed and manufactured as a general purpose product for use at general industries. 

Therefore, applications substantially influential on the public interest for such as atomic power plants and other power 
plants of electric power companies, and also which require a special quality assurance system, including applications for 
railway companies and government or public offices are not recommended, and we assume no responsibility for any 
failure caused by these applications when used. 
In addition, applications which may be substantially influential to human lives or properties for such as airlines, medical 
treatments, railway service, incineration and fuel systems, man-operated material handling equipment, entertainment 
machines, safety machines, etc. are not recommended, and we assume no responsibility for any failure caused by these 
applications when used. 
We will review the acceptability of the abovementioned applications, if you agree not to require a specific quality for a 
specific application. Please contact us for consultation. 

 

 

 