15
2) Simple Check Table for Main Parts
Part name
Test criteria
Tube temperature
detection thermistor
Disconnect the connector and measure the resistance values with a tester (Part temperature
10°C to 30°C).
Normal
Abnormal
8.0K
Ω
to 20.8K
Ω
Open or shorted
Room temperature
sensor
Disconnect the connector and measure the resistance values with a tester (Part temperature
10°C to 30°C).
Normal .............8.0 to 20.8K
Ω
(between pins 3-4)
Abnormal .........Open or shorted
Compressor
Disconnect the connector and measure the resistance values across terminals with a tester
(Coil temperature 10°C to 30°C).
Normal
Abnormal
C-R side
24
Ω
to 27
Ω
Open or shorted
C-S side
40
Ω
to 45
Ω
Blower fan motor
Measure the resistance values across terminals with a tester (Part temperature: 10°C to
30°C).
Normal
Abormal
Yellow-Blue
217
Ω
to 236
Ω
Open or shorted
Black-Blue
219
Ω
to 237
Ω
* Be careful of injury or shock
Solenoid valve coil
Measure the resistance values across terminals with a tester (Part temperature: 10°C to
30°C).
Normal
Abnormal
2.0K
Ω
to 2.2K
Ω
Open or shorted
Stepping motor
Measure the resistance values across terminals with a tester (Part temperature: approx
25°C).
Normal
Abnormal
Terminals 1-2
342
Ω
to 418
Ω
Open or shorted
Terminals 1-3
Terminals 1-4
Terminals 1-5
Содержание MJ-E14EG-S1-IT
Страница 2: ...2 1 Precautions 2 Note This page is extracted from the instruction manual ...
Страница 3: ...3 3 Note This page is extracted from the instruction manual ...
Страница 4: ...4 2 Names and Functions of Parts Note This page is extracted from the instruction manual ...
Страница 8: ...8 7 Technical Points Note This page is extracted from the instruction manual ...
Страница 18: ...18 Note This page is extracted from the instruction manual 10 Troubleshooting ...
Страница 19: ...19 Note This page is extracted from the instruction manual ...
Страница 20: ...20 11 Maintenance Note This page is extracted from the instruction manual ...
Страница 33: ...33 ...