background image

EN-10

4.  TEST RUN

When relocating or disposing of the air conditioner, pump down the system follow

-

ing the procedure below so that no refrigerant is released into the atmosphere.

1) Connect the gauge manifold valve to the service port of the stop valve on the 

gas pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.

3) Close the stop valve on the gas pipe side of the outdoor unit almost completely 

so that it can be easily closed fully when the pressure gauge shows 0 MPa 

[Gauge] (0 kgf/cm

2

).

4) Start the emergency COOL operation.

  To start the emergency operation in COOL mode, disconnect the power supply 

plug and/or turn off the breaker. After 15 seconds, connect the power supply plug 

and/or turn on the breaker, and then press the E.O. SW once. (The emergency 

COOL operation can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the 

pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.

  Press the E.O. SW several times until all LED lamps turn off. Refer to operating 

instructions for details.

When pumping down the refrigerant, stop the compressor before discon-

necting the refrigerant pipes. The compressor may burst if air etc. get 

into it.

 

WARNING

5.  PUMPING DOWN

4-4. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, how to 

remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.)

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

Caution:

•  After test run or remote signal reception check, turn off the unit with the E.O. SW or the remote controller before turning off the power supply. Not doing so will 

cause the unit to start operation automatically when power supply is resumed.

To the user

•  After installing the unit, make sure to explain the user about auto restart function. 

•  If auto restart function is unnecessary, it can be deactivated. Consult the service representative to deactivate the function. Refer to the service manual for details.

4-3. AUTO RESTART FUNCTION

This product is equipped with an auto restart function. When the power supply is stopped during operation, such as during blackouts, the function automatically 

starts operation in the previous setting once the power supply is resumed. (Refer to the operating instructions for details.) 

4-2. TEST RUN

Make sure the following is done.

• Panel is installed correctly.

• Indoor and outdoor units are installed correctly, and power is supplied.
1) Press the E.O. SW once for COOL, and twice for HEAT operation. Test run will be performed for 30 minutes. If the left lamp of the opera

-

tion indicator blinks every 0.5 seconds, inspect the indoor/outdoor unit connecting wire (A) for mis-wiring. After the test run, emergency 

mode (set temperature 24ºC) will start.

2) To stop operation, press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details. 

Checking the remote (infrared) signal reception

Press the ON/OFF button on the remote controller (12) and check that an electronic sound is heard from the indoor unit. Press the ON/

OFF button again to turn the air conditioner off.

•  Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air 

conditioner.

Emergency operation 

switch (E.O. SW)

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. 

(The stop valves are fully closed and covered in caps in initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve 

on the gas pipe side of the outdoor unit.

Stop valve for 

GAS

Stop valve cap

(Torque 19.6 to 

29.4 N•m, 200 

 

to 300 kgf•cm)

Vacuum pump (or the vacuum 

pump with the function to 

prevent the back flow)

Gauge manifold valve 

(for R32, R410A)

Compound pressure gauge 

(for R32, R410A)

0.101 MPa 

 

(

760 mmHg)

Handle 

Low

Handle High

Adapter for 

preventing the 

back flow

Charge hose 

(for R32, R410A)

*Close

*Open

Hexagonal wrench

Precautions when using the control valve

When  attaching  the  control  valve 

to the service port, valve core may 

deform or loosen if excess pressure 

is applied. This may cause gas leak.

Service port

Body

Close

<R32>

Open

Control 

valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then  tighten  part A.  Do  not  tighten 

part A or turn the body when valve 

core is in open position.

Service port cap

(Torque 13.7 to 

17.7 N•m, 140 to 

180 kgf

cm)

*4 to 5 turns

3) Run the vacuum pump. (Vacuumize until 500 microns is achieved.)

4) Check the vacuum with gauge manifold valve, then close gauge mani

-

fold valve, and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure pointer gauge manifold 

valve remains in the same position. Confirm that pressure gauge shows 

–0.101 MPa [Gauge] (–760 mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.

7) After refrigerant pipes are connected and evacuated, fully open all stop 

valves on both sides of gas pipe and liquid pipe. Operating without fully 

opening lowers the performance and this causes trouble.

8) Refer to 1-3., and charge the prescribed amount of refrigerant if needed. 

Be sure to charge slowly with liquid refrigerant. Otherwise, composition 

of the refrigerant in the system may be changed and affect performance 

of the air conditioner.

9) Tighten cap of service port to obtain the initial status.

10) Leak test

Stop valve 

for LIQUID

Pressure gauge

(for R32, R410A)

Charge 

hose

Make sure to 

replace the cap after 

the operation.

 WARNING

To avoid risk of fire, make sure that there are no flammable hazards 

or ignition risks before opening the stop valves.

RH79A056H01_4th.indd   10

2020/08/19   12:50:23

Содержание MFZ-KW25VG

Страница 1: ...FLOOR TYPE AIR CONDITIONERS REFRIGERANT R32 English INSTALLATION MANUAL For INSTALLER MFZ KW25VG MFZ KW35VG MFZ KW42VG MFZ KW50VG MFZ KW60VG RH79A056H01_4th indd 1 2020 08 19 12 50 18 ...

Страница 2: ...nstalling relocating or servicing the unit make sure that no substance other than the specified refrigerant R32 enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explo sion or injury The use of any refrigerant other than that specified for the system will cause mechanical failure system malfunction or unit breakdown In t...

Страница 3: ...asy to operate and easily visible Where children cannot touch it Select a position about 1 2 m above the floor and check that signals from the remote controller are surely received by the indoor unit from that position beep or beep beep receiving tone sounds After that attach remote controller holder to a pillar or wall and install wireless remote controller Note In rooms where inverter type fluor...

Страница 4: ...foam plastic 0 045 specific gravity 9 Be sure to use the insulation of specified thickness Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage KW25 35 42 KW50 60 Pipe length and height difference Max pipe length 20 30 m Max height difference 12 15 m Max number of bends 5 6 10 Refrigerant adjustment A 7 20 g m Insulation thicknes...

Страница 5: ...t and sides of unit are clear 2 When any 2 sides of left right and rear of unit are clear 3 The manufacturing year and month is indicated on the spec name plate clear 1 KW25 35 42 KW50 60 Appearance of the out door unit may differ from some models Air inlet Air outlet 2 10 mm 21 mm slot 800 840 mm 150 175 mm 500 mm 344 5 390 mm 285 330 mm 304 325 349 371 mm 40 mm Air inlet 350 mm or more Indoor un...

Страница 6: ...lowing figure is a view of the bottom of the indoor unit from above FOR REAR OR LEFT REAR PIPING The following figure is a front view of the indoor unit installation location FOR LEFT PIPING FOR RIGHT PIPING HOLE POSITIONS ø65 mm KW25 35 42 ø75 ø80 mm KW50 60 5 7 mm 2 3 INDOOR UNIT PREPARATION Remove the front panel of the indoor unit 1 Push down the tab on the both sides of the unit to open the f...

Страница 7: ...wire or cram it into small space Take caution not to damage the wires Be sure to attach each screw to its correspondent terminal when securing the cord and or the wire to the terminal block 2 5 CONNECTING WIRES FOR INDOOR UNIT 1 Remove VA clamp 2 Pass indoor outdoor unit connecting wire A from the back of the indoor unit and process the end of the wire 3 Loosen terminal screw and connect first the...

Страница 8: ...d point downward for easy drain flow Fig 1 If the drain hose provided with the indoor unit is too short connect it with drain hose J that should be provided at your site Fig 2 When connecting the drain hose to the hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Wrap the felt tape 11 tightly around the pipes and hose starting near where the pipes and hose are routed from ...

Страница 9: ...necting cable should be stored and placed where customers cannot touch it Rear horizontal vane 2 9 HOW TO ATTACH THE LABEL AND THE EXPLANATION The breaker must be always ON except when performing maintenance or inspection Hang the accompanying label 14 or 15 on the breaker and explain it to customers When turning the breaker OFF the power is not supplied to the refrigerant sensor mounted in the in...

Страница 10: ...damages the flare section Copper pipe Good Tilted Uneven Burred No good Fig 1 Fig 2 Burr Copper pipe Spare reamer Pipe cutter Clutch type Flaring tool Fig 4 Fig 3 Smooth all around Even length all around Inside is shining without any scratches Flare nut Die Fig 5 Fig 6 Copper pipe Wing nut type WARNING When installing the unit securely connect the refrigerant pipes be fore starting the compressor ...

Страница 11: ... the indoor outdoor unit connecting wire A for mis wiring After the test run emergency mode set temperature 24ºC will start 2 To stop operation press the E O SW several times until all LED lamps turn off Refer to operating instructions for details Checking the remote infrared signal reception Press the ON OFF button on the remote controller 12 and check that an electronic sound is heard from the i...

Страница 12: ...E TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment RH79A056H01_cover_1st indd 1 2020 08 19 12 51 21 ...

Отзывы: