EN-6

2-4-3. EMBEDDING THE INDOOR UNIT IN A WALL

1) Make a hole in the wall.

2) Using reinforcement material, adjust the depth.

3) Remove 6 screws that fix the base to the unit. Remove the base from the unit.

4) Fix the indoor unit at 4 points with the included wood screws (9) and washers 

(10). Tighten the screws securely.

4

575

740

70

4

3

3

3

3

3 3

705

2-4. INDOOR UNIT INSTALLATION

2-4-1. INSTALLING THE INDOOR UNIT ON THE FLOOR

1) Place the indoor unit on the flat floor.

2) Fix the indoor unit at 4 points with the included wood screws (9) and washers 

(10). Tighten the screws securely.

2-4-2. MOUNTING THE INDOOR UNIT ON THE WALL

1) Hook the top of the indoor unit on the indoor unit mounting bracket (7).

2) Fix the indoor unit at 4 points with the included wood screws (9) and washers 

(10). Tighten the screws securely.

405

137

387

Indoor terminal block

Indoor/outdoor unit

 

connecting wire (A)

Outdoor terminal block

Earth wire 

(green/yellow)

•  Make earth wire a little longer than others. (More than 45 mm)

•  For future servicing, give extra length to the connecting wires.

•  Do not fold the excess wire, or cram it into small space. Take caution not to 

damage the wires.

•  Be sure to attach each screw to its correspondent terminal when securing 

the cord and/or the wire to the terminal block.

2-5. CONNECTING WIRES FOR INDOOR UNIT

1) Remove VA clamp.

2) Pass indoor/outdoor unit connecting wire (A) from the back of the indoor unit 

and process the end of the wire.

3) Loosen terminal screw, and connect first the earth wire, then indoor/outdoor 

unit connecting wire (A) to the terminal block. Be careful not to make mis-

wiring. Fix the wire to the terminal block securely so that no part of its core is 

appeared, and no external force is conveyed to the connecting section of the 

terminal block. 

4) Firmly  tighten  the  terminal  screws  to  prevent  them  from  loosening.  After 

tightening, pull the wires lightly to confirm that they do not move.

5) Secure indoor/outdoor unit connecting wire (A) and the earth wire with the VA 

clamp. Never fail to hook the left claw of the VA clamp. Attach the VA clamp 

securely.

Terminal block

Fixing screw

Indoor/outdoor unit 

connecting wire (A)

VA clamp

Lead wire

35 mm

15 mm

Reinforcement 

material

Unit

Base

When installing the unit, securely connect the refrigerant pipes before 

starting the compressor.

 

WARNING

RH79A056H01_4th.indd   6

2020/08/19   12:50:21

Содержание MFZ-KW25VG

Страница 1: ...FLOOR TYPE AIR CONDITIONERS REFRIGERANT R32 English INSTALLATION MANUAL For INSTALLER MFZ KW25VG MFZ KW35VG MFZ KW42VG MFZ KW50VG MFZ KW60VG RH79A056H01_4th indd 1 2020 08 19 12 50 18 ...

Страница 2: ...nstalling relocating or servicing the unit make sure that no substance other than the specified refrigerant R32 enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explo sion or injury The use of any refrigerant other than that specified for the system will cause mechanical failure system malfunction or unit breakdown In t...

Страница 3: ...asy to operate and easily visible Where children cannot touch it Select a position about 1 2 m above the floor and check that signals from the remote controller are surely received by the indoor unit from that position beep or beep beep receiving tone sounds After that attach remote controller holder to a pillar or wall and install wireless remote controller Note In rooms where inverter type fluor...

Страница 4: ...foam plastic 0 045 specific gravity 9 Be sure to use the insulation of specified thickness Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage KW25 35 42 KW50 60 Pipe length and height difference Max pipe length 20 30 m Max height difference 12 15 m Max number of bends 5 6 10 Refrigerant adjustment A 7 20 g m Insulation thicknes...

Страница 5: ...t and sides of unit are clear 2 When any 2 sides of left right and rear of unit are clear 3 The manufacturing year and month is indicated on the spec name plate clear 1 KW25 35 42 KW50 60 Appearance of the out door unit may differ from some models Air inlet Air outlet 2 10 mm 21 mm slot 800 840 mm 150 175 mm 500 mm 344 5 390 mm 285 330 mm 304 325 349 371 mm 40 mm Air inlet 350 mm or more Indoor un...

Страница 6: ...lowing figure is a view of the bottom of the indoor unit from above FOR REAR OR LEFT REAR PIPING The following figure is a front view of the indoor unit installation location FOR LEFT PIPING FOR RIGHT PIPING HOLE POSITIONS ø65 mm KW25 35 42 ø75 ø80 mm KW50 60 5 7 mm 2 3 INDOOR UNIT PREPARATION Remove the front panel of the indoor unit 1 Push down the tab on the both sides of the unit to open the f...

Страница 7: ...wire or cram it into small space Take caution not to damage the wires Be sure to attach each screw to its correspondent terminal when securing the cord and or the wire to the terminal block 2 5 CONNECTING WIRES FOR INDOOR UNIT 1 Remove VA clamp 2 Pass indoor outdoor unit connecting wire A from the back of the indoor unit and process the end of the wire 3 Loosen terminal screw and connect first the...

Страница 8: ...d point downward for easy drain flow Fig 1 If the drain hose provided with the indoor unit is too short connect it with drain hose J that should be provided at your site Fig 2 When connecting the drain hose to the hard vinyl chloride pipe be sure to insert it securely into the pipe Fig 3 Wrap the felt tape 11 tightly around the pipes and hose starting near where the pipes and hose are routed from ...

Страница 9: ...necting cable should be stored and placed where customers cannot touch it Rear horizontal vane 2 9 HOW TO ATTACH THE LABEL AND THE EXPLANATION The breaker must be always ON except when performing maintenance or inspection Hang the accompanying label 14 or 15 on the breaker and explain it to customers When turning the breaker OFF the power is not supplied to the refrigerant sensor mounted in the in...

Страница 10: ...damages the flare section Copper pipe Good Tilted Uneven Burred No good Fig 1 Fig 2 Burr Copper pipe Spare reamer Pipe cutter Clutch type Flaring tool Fig 4 Fig 3 Smooth all around Even length all around Inside is shining without any scratches Flare nut Die Fig 5 Fig 6 Copper pipe Wing nut type WARNING When installing the unit securely connect the refrigerant pipes be fore starting the compressor ...

Страница 11: ... the indoor outdoor unit connecting wire A for mis wiring After the test run emergency mode set temperature 24ºC will start 2 To stop operation press the E O SW several times until all LED lamps turn off Refer to operating instructions for details Checking the remote infrared signal reception Press the ON OFF button on the remote controller 12 and check that an electronic sound is heard from the i...

Страница 12: ...E TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment RH79A056H01_cover_1st indd 1 2020 08 19 12 51 21 ...

Отзывы: