36
2 APPENDIX
2.1 CC-Link IE TSN
• State coding
Bit 0 to Bit 3, Bit 5, and Bit 6 are switched depending on the PDS state (servo amplifier internal state). Details are as follows:
*1 Statusword is not sent when in the "Not ready to switch on" state.
Statusword (bin)
PDS state
x0xx xxx0 x0xx 0000
x0xx xxx0 x1xx 0000
Switch on disabled
x0xx xxx0 x01x 0001
Ready to switch on
x0xx xxx0 x01x 0011
Switched on
x0xx xxx0 x01x 0111
Operation enabled
x0xx xxx0 x00x 0111
Quick stop active
x0xx xxx0 x0xx 1111
Fault reaction active
x0xx xxx0 x0xx 1000
Fault