7 CiA 402 DRIVE PROFILE
7.4 Control mode
Control switching between cyclic mode (csp/csv/cst) and profile mode (pp/pv/tq)
The control mode is switched between the cyclic mode (csp/csv/cst) and the profile mode (pp/pv/tq), and [Modes of operation
display (Obj. 6061h)] is changed only if condition for control switching is met. If the condition for control switching is not met,
the control mode will not be switched and [Modes of operation display (Obj. 6061h)] will also not be changed. The condition
for control switching is "Motor being stopped".
"Motor being stopped" means that S_ZSP (Bit 3 of [Status DO 2 (Obj. 2D12h)]) is on.
(servo motor speed being less than zero speed set in [Pr. PC07])
Setting "1" (Disabled (Control switching is performed regardless of the range of ZSP)) to [Pr. PC76.1] enables the control
mode to be switched without checking the condition "Motor being stopped" on the servo amplifier. Set "1" to [Pr. PC76.1] only
if switching the control mode without waiting for the motor to stop. Switching the control mode without waiting for the motor to
stop may cause a shock.
The following shows a timing chart of control switching between the cyclic mode (csp) and the profile mode (pp).
pp
csp
ON
OFF
[Modes of operation display (Obj. 6061h)]
[Modes of operation (Obj. 6060h)]
pp
csp
S_ZSP
Zero speed level
Within 4 ms
Servo motor speed
(Bit 3 of [Status DO 2 (Obj. 2D12h)])