68
4 SYSTEM CONFIGURATION
4.5 Rules of System Configuration and Examples of Reconfiguration
■
Number of remote I/O points
(
Page 59 Calculation of the number of remote I/O points)
■
Total number of I/O points and remote I/O points
(
Page 58 Limitation on the Number of Input/Output Points)
Check of limitation on current consumption
Check if power required for extension devices can be supplied from the CPU module and extension power supply module.
■
Check of power supply from the CPU module
(
Page 61 Power supply check from the CPU module (current consumption calculation))
• Power supply capacity of the CPU module
• Current consumption of extension devices
Network
No. of remote I/O points
AnyWireASLINK
64 points
Type
Model
Power supply capacity
5 V DC power supply
24 V DC power supply
CPU module
FX5UC-32MT/D
720 mA
500 mA
Type
Model
Current consumption
5 V DC power supply
24 V DC power supply
Expansion adapter
FX5-232ADP
30 mA
30 mA
Expansion adapter
FX5-485ADP
20 mA
30 mA
Input module
FX5-C16EX/D
100 mA
Output module
FX5-C16EYT/D
100 mA
100 mA
Output module
FX5-C16EYT/D
100 mA
100 mA
Output module
FX5-C16EYT/D
100 mA
100 mA
Connector conversion module
FX5-CNV-IFC
Simple motion module
FX5-40SSC-S
Bus conversion module
FX5-CNV-BUS
150 mA
Pulse output module
FX3U-1PG
150 mA
Analog input module
FX3U-4AD
110 mA
Temperature controller module
FX3U-4LC
160 mA
AnyWireASLINK master module
FX3U-128ASL-M
130 mA
CC-Link intelligent device module
FX3U-64CCL
≤
384 points
Remote I/O points
64 points
OK
Maximum number of
Remote I/O points
≤
152 points
512 points
Number of input/output points
+
Remote I/O points
64 points
Total number of input/output points
= 216 points
OK
Max. number of
input/output points
Calculation
result