background image

APPX

Appendix 4  I/O Module

173

A

FX5-C32EYT/D

FX5-C32EYT/D-TS

FX5-C32ET/D

FX5-C32ET/DS-TS

FX5-C32EYT/DSS

FX5-C32EYT/DSS-TS

FX5-C32ET/DSS

FX5-C32ET/DSS-TS

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM1

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM1

Notch

Smaller 
numbers

Larger 
numbers

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17

COM0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM1

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17

COM1

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Input

X0
X1
X2
X3
X4
X5
X6
X7

COM

X0
X1
X2
X3
X4
X5
X6
X7

COM

Notch

Input

X0
X1
X2
X3
X4
X5
X6
X7

S/S

X10
X11
X12
X13
X14
X15
X16
X17

S/S

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

COM0

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17

COM0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V1

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V1

Notch

Smaller 
numbers

Larger 
numbers

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17
+V0

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V1

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17
+V1

Input

X0
X1
X2
X3
X4
X5
X6
X7

COM0

X0
X1
X2
X3
X4
X5
X6
X7

COM0

Notch

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Input

X0
X1
X2
X3
X4
X5
X6
X7

S/S

X10
X11
X12
X13
X14
X15
X16
X17

S/S

Output

Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7

+V0

Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17
+V0

Содержание MELSEC iQ-F FX5UC-32MT/D

Страница 1: ...MELSEC iQ F FX5UC User s Manual Hardware ...

Страница 2: ......

Страница 3: ...uld be designed to ensure safe machinery operation in such a case Note that when an error occurs in a relay transistor or triac of an output circuit the output might stay on or off For output signals that may lead to serious accidents external circuits and mechanisms should be designed to ensure safe machinery operation in such a case Construct an interlock circuit in the program so that the whole...

Страница 4: ...y to open Warning Explosion Hazard Substitution of any component may impair suitability for Class Division 2 Warning Explosion Hazard Do not disconnect equipment while the circuit is live or unless the area is known to be free of ignitable concentrations Do not open the cover of the CPU module and remove the battery unless the area is known to be nonhazardous CAUTION When an inductive load such as...

Страница 5: ...ation and wiring work to prevent foreign objects such as cutting and wiring debris However when the installation work is completed make sure to remove the sheet to provide adequate ventilation Failure to do so may cause fire equipment failures or malfunctions Install the product on a flat surface If the mounting surface is rough undue force will be applied to the PC board thereby causing nonconfor...

Страница 6: ...ly wire to the terminal block European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the ends of stranded wi...

Страница 7: ...Failure to do so may result in wire damage breakage or PLC failure Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to malfunction of the PLC caused by abnormal data written to the PLC due to the effects of noise Do not bundle the power line control line and communication cables together with or lay them close to the main circuit high ...

Страница 8: ...er bring near fire or touch liquid leakage or other contents directly When replacing the battery make sure to use our specified product FX3U 32BL When a battery error occurs BAT LED is lit in red follow the description in this manual Incorrect handling of the battery may cause heat excessive generation bursting ignition liquid leakage or deformation and lead to injury fire or failures and malfunct...

Страница 9: ...a parameter and the BAT LED is OFF and check the battery life If the PLC is transported with the BAT LED ON or the battery exhausted the battery backed data may be unstable during transportation The PLC is a precision instrument During transportation avoid impacts larger than those specified in the general specifications Page 30 Generic Specifications by using dedicated packaging boxes and shock a...

Страница 10: ...limites de positionnement Notez que lorsque le module CPU détecte une erreur telle qu une erreur de minuteur de surveillance pendant l auto diagnostic toutes les sorties sont désactivées En outre lorsqu une erreur qui ne peut pas être détectée par le module CPU se produit dans un bloc de contrôle E S la commande de sortie peut être désactivée Les circuits et mécanismes externes devraient être conç...

Страница 11: ...au Pour maintenir la sécurité en cas d accès via Internet prendre des mesures adéquates telles que l installation d un pare feu Precautions d utilisation des produits en environnement de UL cUL Class Division 2 Les produits 1 marques Cl DIV 2 sur la plaque signaletique peuvent etre utilises en Class Division 2 local dangereux de groupe A B C et D ou uniquement en local non dangereux Ce logo indiqu...

Страница 12: ...s modules d extension Si une panne de courant de longue durée ou une chute de tension anormale se produit le contrôleur programmable s arrête et la sortie est désactivée Lorsque l alimentation est rétablie elle redémarre automatiquement lorsque le commutateur RUN STOP RESET est sur le côté RUN AVERTISSEMENT Assurez vous de couper toutes les phases de l alimentation externe avant d essayer l instal...

Страница 13: ...C ce qui entraînera des non conformités Installez le produit solidement à l aide d un rail DIN Connectez l adaptateur d extension de manière sécurisée à leurs connecteurs désignés Les connexions lâches peuvent provoquer des dysfonctionnements Travailler soigneusement lorsque vous utilisez un tournevis comme pour l installation du produit Faute de quoi il y a risque d endommagement du produit ou de...

Страница 14: ...ent aux précautions suivantes Faute de quoi il y a risque d électrocution de panne d équipement de court circuit de rupture de fil de dysfonctionnements ou de dommages au produit La taille de l extrémité du câble lors de la mise au rebut doit suivre les dimensions décrites dans le manuel Le couple de serrage doit suivre les spécifications du manuel Tordre les extrémités des fils échoués et s assur...

Страница 15: ...haute tension la ligne de charge ou la ligne d alimentation À titre indicatif posez la ligne d alimentation la ligne de commande et les câbles de communication au moins à 100 mm du circuit principal de la ligne à haute tension de la ligne de charge ou de la ligne d alimentation Effectuer la mise à la terre du blindage du fil blindé ou du câble blindé en un point sur le contrôleur programmable Tout...

Страница 16: ...se en service de la carte mémoire SD ne pas insérer retirer la carte mémoire plus de 500 fois Cette opération de plus de 500 fois peut causer un dysfonctionnement Coupez l alimentation du contrôleur programmable avant de connecter ou déconnecter les câbles d extension Faute de quoi il y a risque de panne ou de dysfonctionnement des équipements Coupez l alimentation du contrôleur programmable avant...

Страница 17: ... un instrument de précision Pendant le transport évitez de donner des chocs supérieurs à ceux spécifiés dans les spécifications générales Page 30 Generic Specifications en utilisant des boîtes d emballage dédiées et des palettes amortisseuse Faute de quoi il y a risque de panne du contrôleur programmable Après le transport vérifiez le bon fonctionnement du contrôleur programmable et contrôlez l ab...

Страница 18: ...cur if the product fails install appropriate backup or failsafe functions in the system Note If in doubt at any stage during the installation of the product always consult a professional electrical engineer who is qualified and trained in the local and national standards If in doubt about the operation or use please consult the nearest Mitsubishi Electric representative Since the examples indicate...

Страница 19: ...17 MEMO ...

Страница 20: ...7 Communication Specifications 37 Built in Ethernet communication 37 Built in RS 485 communication 38 2 8 External Dimensions 38 CPU module 38 2 9 Terminal Layout 39 CHAPTER 3 PRODUCT LIST 42 3 1 Overall Configuration 42 3 2 CPU Module 43 3 3 Extension Module 44 I O module 44 Intelligent function module 47 Extension power supply module 49 Connector conversion module 49 Bus conversion module 50 3 4...

Страница 21: ...es in enclosure 75 Layout in enclosure 76 5 2 Examination for Installing Method in Enclosure 77 5 3 Procedures for Installing on and Detaching from DIN Rail 78 Preparation for installation 78 Installation of CPU module 78 Installation of extension modules extension cable type 79 Installation of terminal modules 79 Removal of CPU module 79 5 4 Procedures for Installing Directly with M4 Screws 80 Ho...

Страница 22: ...ring for Various Uses 123 Positioning function 123 Communication function 123 High speed counter 123 Interruption 126 Digital switch 127 Input matrix 129 Seven segment with latch 130 CHAPTER 7 OPERATION ADJUSTMENT 132 7 1 Preparation for Operation 132 Preliminary inspection 132 Procedure until operation 132 Connection with a personal computer 133 7 2 Operation and Test 134 Self diagnostic function...

Страница 23: ...x 2 Standards 150 Certification of UL cUL standards 150 Compliance with EC directive CE Marking 150 Appendix 3 Precautions for Operating Ambient Temperature 154 Appendix 4 I O Module 155 Product configuration 155 Product list 155 Specifications 158 External dimensions and component names 166 Terminal layout 172 Appendix 5 Connector Conversion Module 175 External dimensions and component names 175 ...

Страница 24: ...g of Batteries and Devices with Built in Batteries in EU Member States 193 Disposal precautions 193 Exportation precautions 193 Appendix 10Added and Changed Functions 194 INDEX 195 REVISIONS 196 WARRANTY 197 TRADEMARKS 198 ...

Страница 25: ...23 CONTENTS ...

Страница 26: ...rt communication function MELSEC iQ F FX5 User s Manual SLMP JY997D56001 Explains methods for the device that is communicating with the CPU module by SLMP to read and write the data of the CPU module MELSEC iQ F FX5 User s Manual CC Link IE JY997D64201 Describes CC Link IE field network module MELSEC iQ F FX5 User s Manual CC Link SH 081793ENG Describes CC Link system master intelligent device mod...

Страница 27: ...es Input module Generic term for Input modules extension cable type and Input modules extension connector type Input module extension cable type Generic term for FX5 8EX ES and FX5 16EX ES Input module extension connector type Generic term for FX5 C16EX D FX5 C16EX DS FX5 C32EX D FX5 C32EX DS and FX5 C32EX DS TS Output module Generic term for Output modules extension cable type and Output modules ...

Страница 28: ...BSD NZ1MEM 8GBSD NZ1MEM 16GBSD L1MEM 2GBSD and L1MEM 4GBSD SD memory cards Abbreviation of Secure Digital Memory Card Device that stores data using flash memory Peripheral device Generic term for engineering tools and GOTs GOT Generic term for Mitsubishi Electric Graphic Operation Terminal GOT1000 and GOT2000 series Software packages Engineering tool The product name of the software package for th...

Страница 29: ... Indicates the program running status Lit Operating normally Flashing Paused Off Stopped or stop error BAT LED Indicates the battery status Flashing Battery error Off Operating normally Page 141 Checking with LEDs CARD LED Indicates whether an SD memory card can be used or not Lit Can be used or cannot be removed Flashing In preparation Off Not inserted or can be removed SD RD LED Lit when the CPU...

Страница 30: ...5 SD memory card disable switch Switch for disabling access to the SD memory card when the card is to be removed 16 SD memory card slot Slot for inserting an SD memory card 17 RUN STOP RESET switch Switch for operating the CPU module Page 135 Methods of running stopping and resetting RUN Runs the program STOP Stops the program RESET Resets the CPU module hold the switch on the RESET side for appro...

Страница 31: ... that the tip of a tool does not damage the switch or case No Name Description 1 Battery cover Cover for protecting the battery connecting connector 2 Power connector for CPU module Connector for connecting power cables 3 RS 485 terminal resistor selector switch Switch for switching terminal resistance for built in RS 485 communication 3 2 1 ...

Страница 32: ...The withstand surge voltage for the equipment with the rated voltage up to 300 V is 2500 V 11 This index indicates the degree to which conductive material is generated in the environment in which the equipment is used Pollution level 2 is when only non conductive pollution occurs Temporary conductivity caused by condensation must be expected occasionally Dielectric withstand voltage test and insul...

Страница 33: ...configuration connectable to the CPU module The value does not include the external 24 V DC power supply of extension devices The following shows the power failure detection time of the FX5UC CPU module Item Specifications Power supply voltage 24 V DC Voltage fluctuation range 20 15 Allowable instantaneous power failure time Operation can be continued upon occurrence of instantaneous power failure...

Страница 34: ... 200 kHz When capturing pulses of a response frequency of 50 to 200 kHz refer to Page 102 When a high speed pulse is captured FX5UC 64MT FX5UC 96MT X0 to X7 FX5UC 32MT X6 to X17 10 kHz FX5UC 64MT FX5UC 96MT X10 to X17 FX5UC 64MT FX5UC 96MT X20 and subsequent 0 1 0 05 kHz Pulse waveform Waveform T1 pulse width T2 rise fall time FX5UC 32MT X0 to X5 2 5 s or more 1 25 s or less FX5UC 64MT FX5UC 96MT ...

Страница 35: ...o coupler insulation Indication of input operation LED is lit when input is on DISP switch IN Input circuit configuration FX5UC MT D FX5UC MT DS Sink input wiring Source input wiring Item Specifications X COM 24 V DC Fuse 1 Input impedance 1 Photocoupler X COM0 Photocoupler 24 V DC 1 Input impedance 2 For FX5UC 32MT DS S TS the COM0 terminal is the S S terminal 1 2 Fuse X COM0 Photocoupler 24 V DC...

Страница 36: ...V DC Max load Y0 to Y3 0 3 A point The total load current per common terminal should be the following value 8 output points common terminal 0 8 A or less 1 For details of the common refer to Page 39 Terminal Layout Y4 and subsequent 0 1 A point Open circuit leakage current 0 1 mA or less 30 V DC Voltage drop when ON Y0 to Y3 1 0 V or less Y4 and subsequent 1 5 V or less Response time Y0 to Y3 2 5 ...

Страница 37: ...al global Constant scan 0 2 to 2000 ms can be set in 0 1 ms increments Fixed cycle interrupt 1 to 60000 ms can be set in 1 ms increments Timer performance specifications 100 ms 10 ms 1 ms No of program executions 32 No of FB files 16 Up to 15 for user Operation specifications Execution type Standby type initial execution type scan execution type fixed cycle execution type event execution type Inte...

Страница 38: ...r LC 10 1024 points can be changed with parameter 1 Data register D 10 8000 points can be changed with parameter 1 Link register W 16 32768 points can be changed with parameter 1 Link special register SW 16 32768 points can be changed with parameter 1 No of system device points Special relay SM 10 10000 points fixed Special register SD 10 12000 points fixed Module access device Intelligent functio...

Страница 39: ... occur Example 0 0 0 0 127 0 0 0 etc 6 A straight cable can be used If a personal computer or GOT and CPU module are directly connected a cross cable can be used Item Specifications Data transmission speed 100 10 Mbps Communication mode Full duplex FDX Half duplex HDX 1 Interface RJ45 connector Transmission method Base band Maximum segment length The distance between hub and node 100 m Cascade con...

Страница 40: ...ex HDX Maximum total extension distance 50 m Protocol type MELSOFT connection Non protocol communication MELSEC Communication protocol 3C 4C frame MODBUS RTU communication Predefined protocol support Inverter communication N N Network Parallel link Insulation method Not insulated Terminal resistors Built in OPEN 110 330 Terminal block used European type terminal block Model W Mass weight FX5UC 32M...

Страница 41: ...rnet connector Model W Mass weight FX5UC 32MT DS TS FX5UC 32MT DSS TS 48 1 mm Approx 0 25 kg Exterior color Main body Munsell 0 6B7 6 0 2 Accessories Manual supplied with product FX2NC 100MPCB power cable 1 m 90 W 93 7 74 Unit mm RDA RXD RDB RXD SDA TXD 5 poles SDB TXD SG GND Pin 1 2 3 4 5 6 7 8 Signal name TXD TXD RXD Not used Not used RXD Not used Not used 8 1 ...

Страница 42: ...34 Y35 Y36 Y37 V1 Notch Notch Input X0 X1 X2 X3 X4 X5 X6 X7 COM0 X10 X11 X12 X13 X14 X15 X16 X17 COM0 Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 V0 Input X20 X21 X22 X23 X24 X25 X26 X27 COM X30 X31 X32 X33 X34 X35 X36 X37 COM Output Y20 Y21 Y22 Y23 Y24 Y25 Y26 Y27 COM1 Y30 Y31 Y32 Y33 Y34 Y35 Y36 Y37 COM1 Input X0 X1 X2 X3 X4 X5 X6 X7 COM X10 X11 X12 X13 X14 X15 X16 X17 COM ...

Страница 43: ...TS Input X0 X1 X2 X3 X4 X5 X6 X7 S S X10 X11 X12 X13 X14 X15 X16 X17 S S Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 COM0 Input X0 X1 X2 X3 X4 X5 X6 X7 S S X10 X11 X12 X13 X14 X15 X16 X17 S S Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 V0 1 Red 2 Black 3 Ground Green ...

Страница 44: ...5 16EYT ES FX5 16EYT ESS Network FX5 CCLIEF FX5 CCL MS FX5 ASL M Analog FX5 4AD FX5 4DA FX5 8AD FX5 4LC FX5 Intelligent function module Simple motion FX5 40SSC S FX5 80SSC S FX5 20PG P Positioning Expansion adapter FX5 232ADP FX5 485ADP Communication FX5 4AD ADP FX5 4DA ADP FX5 4AD PT ADP FX5 4AD TC ADP Analog CPU module FX5UC 32MT D FX5UC 32MT DSS FX5UC 64MT D FX5UC 64MT DSS FX5UC 96MT D FX5UC 96...

Страница 45: ...sink Connector 720 mA 500 mA FX5UC 32MT DSS 24 V DC sink source Transistor source FX5UC 32MT DS TS Transistor sink Spring clamp terminal block FX5UC 32MT DSS TS Transistor source FX5UC 64MT D 64 points 32 points 32 points 24 V DC sink Transistor sink Connector FX5UC 64MT DSS 24 V DC sink source Transistor source FX5UC 96MT D 96 points 48 points 48 points 24 V DC sink Transistor sink Connector FX5U...

Страница 46: ...ESS Transistor source output Input output module T D 24 V DC sink input Transistor sink output T DSS TS 24 V DC sink source input Transistor source output T DS TS 24 V DC sink source input Transistor sink output R ES 24 V DC sink source input relay output T ES 24 V DC sink source input transistor sink output T ESS 24 V DC sink source input transistor source output Powered input output module R DS ...

Страница 47: ...nts 32 points 24 V DC sink Connector 120 mA 130 mA FX5 C32EX DS 24 V DC sink source FX5 C32EX DS TS Spring clamp terminal block Model Number of input output points Input type Output type Input output connection type Current consumption Total No of points No of input points No of output points 5 V DC power supply 24 V DC power supply FX5 8EX ES 8 points 8 points 24 V DC sink source Screw terminal b...

Страница 48: ...ints No of output points 5 V DC power supply 24 V DC power supply External 24 V DC power supply 24 V DC power supply for input circuits FX5 C32ET D 32 points 16 points 16 points 24 V DC sink Transistor sink Connector 120 mA 100 mA 65 mA FX5 C32ET DSS 24 V DC sink source Transistor source FX5 C32ET DS TS Transistor sink Spring clamp terminal block FX5 C32ET DSS TS Transistor source Model No of inpu...

Страница 49: ...r supply FX5 16ET ES H 1 16 points 8 points 8 points 24 V DC Sink source Transistor sink Screw terminal block 100 mA 125 mA 82 mA 2 FX5 16ET ESS H 1 Transistor source Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply External 24 V DC power supply FX5 4AD 1 4 ch voltage input current input 8 points 100 mA 40 mA FX5 4DA 1 4 ch voltage outp...

Страница 50: ...5 V DC power supply 24 V DC power supply External 24 V DC power supply FX5 CCLIEF 1 Intelligent device station for CC Link IE Field network 8 points 10 mA 230 mA FX5 CCL MS 1 Master station intelligent device station for CC Link Ver 2 00 and Ver 1 10 compatible 8 points 2 100 mA FX5 ASL M 1 4 Master for AnyWireASLINK 8 points 200 mA 100 mA 3 Model Function No of occupied input output points Curren...

Страница 51: ...ifications of the extension power supply module refer to MELSEC iQ F FX5 C1PS 5V Hardware Manual 1 If the ambient temperature exceeds 40 use the extension power supply module at the following current values within the derating range Connector conversion module Connector conversion modules are used to connect FX5 extension module extension cable type in FX5UC systems Model Function No of occupied i...

Страница 52: ...extension cable and module of extension cable type except for extension power supply module Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply FX5 CNV BUSC Bus conversion from CPU module or extension modules extension connector type 8 points 150 mA FX5 CNV BUS Bus conversion from extension modules extension cable type or FX5 intelligent f...

Страница 53: ...rnal 24 V DC power supply FX 16E TB Directly connected to the I O connector of a PLC 112 mA FX 32E TB 112 mA 16 points FX 16EX A1 TB 100 V AC input type 48 mA FX 16EYR TB Relay output type 80 mA FX 16EYT TB Transistor output type sink output 112 mA FX 16EYS TB Triac output type 112 mA FX 16E TB UL Directly connected to the I O connector of a PLC 112 mA FX 32E TB UL 112 mA 16 points FX 16EYR ES TB ...

Страница 54: ... power supply module Y0 to Y17 Y20 to Y57 FX5 C32EYT D FX5 232ADP Configuration of a whole system CPU module Expansion adapter X20 to X57 FX5 C32EX D Remote I O Remote I O FX5 C32ET D Y60 to Y77 X60 to X77 Input output module Connector conversion module Intelligent module Intelligent module Intelligent module Expansion adapter Output module Input module FX5 extension module FX5 40SSC S Module No 1...

Страница 55: ...tput points of extension devices max 256 points and number of remote I O points max 384 points can be controlled For details on the number of input output points refer to Page 58 Limitation on the Number of Input Output Points CPU module Up to 2 modules Up to 1 module Up to 1 module Expansion adapter Communi cation Up to 4 modules Expansion adapter Analog Connector conversion module Bus conversion...

Страница 56: ...the extended extension cable connection destination is a module of extension cable type except for extension power supply module When connecting a bus conversion module in the same system connect the powered input output module directly after the extended extension cable This cannot be used with the FX3 extension module Model Limitation FX5 CCLIEF Only one module may be connected per system FX5 CC...

Страница 57: ...to 4 adapters can be connected Type Limitation Extension module Up to 16 modules can be connected to a system excluding extension power supply module and connector conversion module Extension power supply module Up to 2 modules can be connected to a system Connector conversion module Only 1 module can be connected to a system Extended extension cable Only 1 cable can be connected to a system Bus c...

Страница 58: ...function modules bus conversion module FX3 intelligent function modules Up to 8 modules can be connected Total No of FX3 intelligent function modules Up to 6 modules can be connected Type Limitations Total No of input module output module intelligent function modules and bus conversion modules Up to 10 modules can be connected Total No of intelligent function module and bus conversion modules Up t...

Страница 59: ... modules connected on the right side of the bus conversion module must be as follows Precautions FX5 extension modules cannot be connected on the right side of the bus conversion module Type Limitation Total No of I O modules intelligent function modules and bus conversion modules Up to 10 modules can be connected Total No of FX5 intelligent function modules bus conversion modules and FX3 intellig...

Страница 60: ...ncluding input output occupied points Up to 256 points CPU module I O module Expansion adapter Connector conversion module CC Link master 1 AnyWireASLINK master 2 CC Link AnyWireASLINK system CC Link IE field network Basic system 2 Number of remote I O points Up to 384 points Remote I O station Remote I O station Remote I O station Remote I O station Number of input output points on whole system U...

Страница 61: ...odule are occupied For information on CC Link IE field network Basic refer to CC Link IE Field Network Basic Reference Manual When using CC Link master FX3U 16CCL M and AnyWireASLINK master FX3U 128ASL M together connect FX3U 128ASL M on the left side In the FX5UC CPU module FX3U 16CCL M parameters are set up by PLC program and will occupy up to 256 remote I O points Therefore the remote I O point...

Страница 62: ...the rotary switch on the FX3U 128ASL M main body For details refer to the following manuals MELSEC iQ F FX5 User s Manual ASLINK FX3U 128ASL M User s Manual 384 points Actually used CC Link IE field network Basic remote I O points stations The total number of number of occupied stations 64 points a 64 points Maximum number of CC Link IE field network Basic remote I O points a CC Link IE field netw...

Страница 63: ...of extension devices Page 44 Extension Module 3 Calculate the total current consumption of each power supply Type Model Power supply capacity 5 V DC power supply 24 V DC power supply CPU module FX5UC 32MT D 720 mA 500 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion adapter FX5 232ADP 30 mA 30 mA Output module FX5 C32EYT D 120 mA 200 mA Input module FX5 C32EX D ...

Страница 64: ...mption exceeds the power supply capacity of the CPU module Reconfigure the system adding extension power supply modules mA mA CPU module Total number of extension devices Current consumption 5 V DC power supply capacity mA 0 mA Calculation result 630 mA 720 mA 90 mA Ex mA mA CPU module Total number of extension devices Current consumption mA 0 mA Calculation result 230 mA 500 mA 270 mA 24 V DC pow...

Страница 65: ...7 Intelligent function module 3 Calculate the total current consumption of each power supply Type Model Power supply capacity 5 V DC power supply 24 V DC power supply Powered input output module FX5 32ER DS 965 mA 310 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Input module FX5 16EX ES 100 mA 85 mA Output module FX5 16EYR ES 100 mA 125 mA Simple motion module FX5 40S...

Страница 66: ...late following the procedure below 1 Check the power supply capacity of the extension power supply module used Page 49 Extension power supply module Type Model Power supply capacity 5 V DC power supply 24 V DC power supply Extension power supply module FX5 C1PS 5V 1200 mA 625 mA mA mA Powered input output module Current consumption mA 0 mA Calculation result Ex 460 mA 965 mA 505 mA Capacity of 5 V...

Страница 67: ... supply modules Type Model Current consumption 5 V DC power supply 24 V DC power supply Output module FX5 C32EYT D 120 mA 200 mA Connector conversion module FX5 CNV IFC Simple motion module FX5 40SSC S Input module FX5 16EX ES 100 mA Bus conversion module FX5 CNV BUS 150 mA Analog input FX3U 4AD 110 mA Power supply type Total current consumption 5 V DC power supply 480 mA 24 V DC power supply 200 ...

Страница 68: ... Connection to the bus conversion module connection with FX3 extension devices Type No of modules used Limitations Judgment Expansion adapter Communication 2 Up to 2 OK Type No of modules used Limitations Judgment Extension module 11 Connector conversion module is excluded Up to 16 Extension power supply modules connector conversion module are excluded OK Connector conversion module 1 Only 1 OK Bu...

Страница 69: ...le OK Model Limitations Judgment FX3U 128ASL M Only one module may be connected to the system Use together with the FX5 ASL M is not possible OK FX3U 64CCL Only one module may be connected to the system When using the FX5 CCL MS as the intelligent device station it cannot be used together with the FX5 CCL MS OK Type Model No of input output points No of occupied input output points CPU module FX5U...

Страница 70: ...4 V DC power supply CPU module FX5UC 32MT D 720 mA 500 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion adapter FX5 232ADP 30 mA 30 mA Expansion adapter FX5 485ADP 20 mA 30 mA Input module FX5 C16EX D 100 mA Output module FX5 C16EYT D 100 mA 100 mA Output module FX5 C16EYT D 100 mA 100 mA Output module FX5 C16EYT D 100 mA 100 mA Connector conversion module FX5 C...

Страница 71: ...onfiguration using an extension power supply module 1150 mA 720 mA CPU module Current consumption 430 mA Calculation result NG Capacity of 5 V DC power supply Total of current consumed by extension module 360 mA 500 mA CPU module Current consumption 140 mA Calculation result OK Capacity of 24 V DC power supply Total of current consumed by extension module FX5 C16EYT D FX5 C16EYT D FX5 C16EX D FX5U...

Страница 72: ...Type No of modules used Limitations Judgment Expansion adapter Communication 2 Up to 2 OK Type No of modules used Limitations Judgment Extension module 11 Extension power supply modules connector conversion module are excluded Up to 16 Extension power supply modules connector conversion module are excluded OK Extension power supply module 1 Up to 2 OK Connector conversion module 1 Only 1 OK Bus co...

Страница 73: ... conversion module OK Model Limitations Judgment FX3U 128ASL M Only one module may be connected to the system Use together with the FX5 ASL M is not possible OK FX3U 64CCL Only one module may be connected to the system When using the FX5 CCL MS as the intelligent device station it cannot be used together with the FX5 CCL MS OK Type Model No of input output points No of occupied input output points...

Страница 74: ... capacity 5 V DC power supply 24 V DC power supply CPU module FX5UC 32MT D 720 mA 500 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion adapter FX5 232ADP 30 mA 30 mA Expansion adapter FX5 485ADP 20 mA 30 mA Input module FX5 C16EX D 100 mA Output module FX5 C16EYT D 100 mA 100 mA Output module FX5 C16EYT D 100 mA 100 mA 384 points Remote I O points 64 points OK M...

Страница 75: ...xtension power supply module FX5 C1PS 5V 1200 mA 625 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Output module FX5 C16EYT D 100 mA 100 mA Connector conversion module FX5 CNV IFC Simple motion module FX5 40SSC S Bus conversion module FX5 CNV BUS 150 mA Pulse output module FX3U 1PG 150 mA Analog input module FX3U 4AD 110 mA Temperature controller module FX3U 4LC 160 mA...

Страница 76: ...f the assigned numbers must begin with 0 Module number of extension modules The CPU module automatically assigns numbers 1 to 16 to intelligent function modules or bus conversion module as module numbers in order of distance from the CPU module Intelligent function modules or bus conversion module connected to the CPU module Module numbers are assigned to intelligent function modules in order of d...

Страница 77: ... in the following figure Spaces in enclosure Extension devices can be connected on the left and right sides of the CPU module of the PLC Keep a space of at least 50 mm between the module main body and other devices and structure Also separate the PLC from high voltage lines high voltage devices and power devices when possible Failure to do so may cause fire equipment failures or malfunctions If yo...

Страница 78: ...ule FX5 40SSC S FX5 40SSC S Extended extension cable FX5 30EC FX5 65EC Another equipment FX5UC CPU module FX5 C16EX FX5 C16EYT FX5 CNV IFC FX5 C16EYT FX5 232ADP 50mm FX5 CNV BC FX5 16EX Another equipment Extension module A 50 mm A A FX5UC CPU module For product dimensions or manual for various products refer to Appendix 4 I O Module Expansion adapter Input module Output module Input module Output ...

Страница 79: ...and direct installation The CPU module side can be installed on the DIN rail and the extension modules extended by the extended extension cable can be directly installed The PLC can be installed on a 35 mm wide DIN46277 rail The PLC can be easily moved and removed The PLC installation height is the same as the DIN rail The PLC can be installed directly in the enclosure with M4 screws For details o...

Страница 80: ...ilation slits before beginning the installation and wiring work For the affixing procedure refer to the instructions on the dust proof sheet Always remove the dust proof sheet when the installation and wiring work is completed Installation of CPU module Connect expansion adapters or extension modules extension connector type on the CPU module before mounting the PLC in the enclosure For the connec...

Страница 81: ...r CPU Module and Extension Devices 1 Turn off all the power supplies connected to the CPU module extension modules or terminal modules 2 Fit the upper edge of the DIN rail mounting groove A in the right figure onto the DIN rail 3 Push the product against the DIN rail 1 Remove the connection cables including power cables and I O cables 2 Insert the tip of a flathead screwdriver into the hole of the...

Страница 82: ...e table I O module Bus conversion module Intelligent function module For the mounting hole dimensions of intelligent function modules refer to user s manuals of each product Dimensions Model name Mounting hole pitch W Unit mm FX5 8EX ES FX5 8EYR ES FX5 8EYT ES FX5 8EYT ESS FX5 16EX ES FX5 16EYR ES FX5 16EYT ES FX5 16EYT ESS FX5 16ER ES FX5 16ET ES FX5 16ET ESS FX5 16ET ES H FX5 16ET ESS H Refer to...

Страница 83: ... Push in the DIN rail mounting hook A in the right figure of the extension module extension cable type If the DIN rail mounting hook is not pushed in the screw hole is covered and the extension module cannot be mounted This procedure may not be required depending on the model 3 Fit the extension module extension cable type B in the right figure to the holes and secure it with M4 screws C in the ri...

Страница 84: ...nnector cover A in the right figure 2 Slide the hook for coupling the expansion adapter of the CPU module B in the right figure 3 Connect the expansion adapter to the CPU module as shown in the right figure 4 Slide the hook for coupling the expansion adapter of the CPU module B in the right figure to fix the expansion adapter C in the right figure Connecting method B Expansion adapter Connecting m...

Страница 85: ...pply module can use either extension cable type or the extension connector type 1 Slide the hook for coupling the extension module A in the right figure of the existing module left side 2 Remove the subsequent extension connector cover B in the right figure 3 Connect an extension module as shown in the right figure 4 Slide the hook for coupling the extension module A in the right figure of the exi...

Страница 86: ...autions on mounting and removing extension cables Make sure that the pullout tab of extension cables do not touch the conductive parts of the module When removing the extension cable pull the pullout tab of the extension cable straight up 1 Remove the top cover B in the right figure of the existing module left side A in the right figure Only extension power supply module 2 Connect the extension ca...

Страница 87: ...sion flathead screwdriver Slightly insert the tip of the screwdriver into part A shown in the right figure and the hook B in the right figure will come off 4 places 2 Connect the extended extension cable on the upstream side C in the right figure 3 Connect the extension cable on the downstream side D in the right figure 4 Pull the tab E in the right figure outside fit the upper cover F in the righ...

Страница 88: ...only when crossover wiring to a subsequent module is performed FX5 C EX DS TS and FX5 C32ET DS do not have power connectors and the power is supplied from using input connectors or input terminal blocks Thus removing the resin cover is not required Precautions To perform crossover wiring supply the power from the preceding module to the subsequent module The power cannot be supplied from the subse...

Страница 89: ... the arrow Precautions If the power cable is removed by force the cable may break Connection of I O cables I O connectors Cable connection to I O connectors I O connectors conform to MIL C 83503 For I O cables refer to Page 88 Preparation of I O connectors and prepare them CPU module I O modules extension connector type a Example FX5UC 32MT D Push here with fingers Input X Output Y Example FX5UC 3...

Страница 90: ...f the terminal module and I O connectors For the connection with the terminal module refer to Page 89 WIRING Flat cables with tube On both ends 20 pin connectors are attached FX 16E 300CAB 3 m FX 16E 500CAB 5 m FX 16E 150CAB R 1 5 m Round multicore cables On both ends 20 pin connectors are attached FX 16E 300CAB R 3 m FX 16E 500CAB R 5 m Model and configuration of I O connectors Suitable wiring UL...

Страница 91: ...ed wire to the terminal Page 95 Grounding 4 Wire input X terminal Connect sensors and switches to the terminals Page 98 Input Wiring 5 Wire output Y terminal Connect the load to terminals Page 108 Output Wiring 6 Wire the built in RS 485 communication terminal blocks and Ethernet communication connectors MELSEC iQ F FX5 User s Manual Serial Communication MELSEC iQ F FX5 User s Manual MODBUS Commun...

Страница 92: ...wire ferrules with insulation sleeves are used Depending on the thickness of a wiring sheath used it may be difficult to insert the sheath into an insulating sleeve Refer to the external dimensions as a reference to select wires Reference No of wire per terminal Wire size Tightening torque Single wire Strand wire Ferrule with insulation sleeve Terminal block for built in RS 485 communication Commu...

Страница 93: ...h the terminal block Use of items that are not listed in the following table may result in wire ferrule getting stuck to the terminals Before use carefully confirm that the wire ferrule can be removed Reference product For tightening terminals use a small commercially available screwdriver with a straight tip The recommended shape is shown in the figure on the right Precautions When a precision sc...

Страница 94: ...ve of the lever push up the flathead screwdriver rotate the lever to the release position and the terminal block can be removed from the module easily After inserting the terminal block check that the lever is at the lock position Precautions When installing the terminal block check that the lever is in the release position If installation is performed while the lever is in the lock position it ma...

Страница 95: ...is securely clamped When wiring with the thick electric wire make sure to prevent the conductive parts from protruding to the front of the terminal block Disconnection of the cable While pushing the open close button with a flathead screwdriver having a tip width of 2 0 to 2 5 mm disconnect the cable or bar solderless terminal Screw terminal block Wire the screw terminal block in accordance with t...

Страница 96: ...ce with LVD directive M3 5 terminal screw When a single wire is connected to a single terminal When two wires are connected to a single terminal Terminal manufacturer Type No Applicable cable Certification Pressure bonding tool JST Mfg Co Ltd FV1 25 B3A AWG22 to 16 UL Listed YA 1 JST Mfg Co Ltd FV2 MS3 AWG16 to 14 Terminal manufacturer Type No Applicable cable Certification Pressure bonding tool J...

Страница 97: ...C extension devices excluding communication adapters Bring the grounding point close to the PLC as much as possible so that the ground cable can be shortened PLC PLC PLC Other equipment Other equipment Other equipment Independent grounding Best condition Shared grounding Good condition Common grounding Not allowed PLC CPU module Extension module Other equipment Expansion adapter Independent ground...

Страница 98: ...ply is used to them turn on the power supply at the same time with the CPU module or earlier than the CPU module When tuning off the power confirm the safety of the system and turn off the CPU module at the same time Some extension modules may not have power supply terminals FX5UC 32MT D FX5 C32EX D FX5 C32ET D FX5 16EX ES Class D grounding 1 Fuse MC MC PL Power ON Emergency stop 24 V DC MC MC FX5...

Страница 99: ...r than the CPU module When tuning off the power confirm the safety of the system and turn off the CPU module at the same time Some extension modules may not have power supply terminals FX5UC 32MT DSS FX5 C32ET DSS Class D grounding 1 Fuse MC PL Power ON MC 24 V DC MC MC FX5 C32EYT DSS Power supply for loads connected to PLC output terminals For details of the emergency stop operation refer to DESI...

Страница 100: ...nput The connection in which the current flows from the input X terminal Page 104 Sink input wiring Source input The connection in which the current flows into the input X terminal Page 105 Source input wiring Inputs X of FX5UC MT DS can be set to either sink input or source input However sink and source input modes cannot be mixed Sink input means a DC input signal with a current flowing from the...

Страница 101: ... circuit At this time the input display LED turns on For the module having DISP switch LED complying with DISP switch turns on In the source input the input X is turned on by connecting 24 V DC with the COM terminal or S S terminal and connecting a no voltage contact or PNP open collector transistor output between the input terminal and 24 V DC to close the circuit At this time the input display L...

Страница 102: ...The C R filter is designed to prevent malfunctions caused by chattering of the input contact and noise from input line Input has a response delay switching from ON to OFF and OFF to ON shown in the following table Item Specifications Input response time H W filter delay FX5UC 32MT X0 to X5 ON 2 5 s or less OFF 2 5 s or less FX5UC 64MT FX5UC 96MT X0 to X7 High speed pulse input output module X0 to ...

Страница 103: ...FX5UC 32MT X6 to X17 15 FX5UC 64MT FX5UC 96MT X10 to X17 High speed pulse input output module X6 X7 FX5UC 64MT FX5UC 96MT X20 and subsequent 13 Input module Input output module Powered input output module Item Specifications Bleeder resistance Rb k FX5UC 32MT X0 to X5 5Rp 14 Rp or less FX5UC 64MT FX5UC 96MT X0 to X7 High speed pulse input output module X0 to X5 FX5UC 32MT X6 to X17 4Rp 15 Rp or le...

Страница 104: ...module side Connect a 1 5 k 1 W or more bleeder resistance to the input terminal so that the sum of the load current of the open collector transistor output on the mating device and the input current of the CPU module is 20 mA or more The above mentioned restrictions are due to specifications of connecting device encoder etc Please adjust the cable length and load for connecting device Item Specif...

Страница 105: ...n accordance with Power Supply Wiring 3 For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required FX5UC 32MT D FX5 C32EX D FX5 16EX ES FX5 CNV IFC COM COM 24 V DC S S 1 2 3 Fuse X0 X1 X0 X1 X0 X1 Power connector 3 wire sensor Input impedance Input connector Power connector Input connector 2 wire sensor Input terminal Class D grounding ...

Страница 106: ...roperly in accordance with Power Supply Wiring 3 For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required FX5UC 32MT DSS FX5 C32EX DS COM0 X0 X1 COM0 X0 X1 24 V DC FX5 16EX ES S S 1 2 3 Fuse X0 X1 FX5 CNV IFC Power connector 3 wire sensor 2 wire sensor Input connector Input impedance Input connector Input terminal Class D grounding ...

Страница 107: ...ower Supply Wiring 3 For an input device having a parallel resistance or a two wire proximity switch a bleeder resistance may be required FX5UC 32MT DSS FX5 C32EX DS COM0 X0 X1 COM0 24 V DC 1 2 3 Input terminal Fuse X0 X1 FX5 CNV IFC FX5 16EX ES S S X0 X1 Power connector Input connector Input connector Input impedance 3 wire sensor 2 wire sensor Class D grounding ...

Страница 108: ...number with the one of the connected connector 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse COM Input number of PLC 3 wire sensor NPN Vacant terminal 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger ...

Страница 109: ... 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse COM0 1 3 wire sensor PNP Input number of PLC Vacant terminal 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 to 3 0 to 3 4 to 7 4 to 7 24 V DC 10 15 Fuse Fuse PLC input No Photocoupler power supply 100 V to 120 V AC ...

Страница 110: ...odule extension connector type and input output module extension connector type the transistor output type is a 8 point common output type Sink output common Source output common Output to make load current flow into the output Y terminal is called sink output Output to make load current flow out of the output Y terminal is called source output Sink output Source output The COM number terminals th...

Страница 111: ...r shut off to when the transistor is turned on or off differs depending on the output terminal used For specifications of each module refer to the following For output specifications of the CPU modules refer to Page 34 Output Specifications For output specifications of the I O modules refer to Page 162 Output specifications For output specifications of the terminal modules refer to Page 180 Output...

Страница 112: ...es larger than the load current Contact protection circuit for inductive loads When an inductive load is connected connect a diode for commutation in parallel with the load as necessary The diode for commutation must comply with the following specifications Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external ...

Страница 113: ...ads Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current Make sure that the rush current does not exceed the current corresponding to the maximu...

Страница 114: ...til the output contact is turned on and from when the coil is shut off until the output contact is turned off is approx 10 ms Output current At a circuit voltage of 240 V AC or less 250 V AC or less when the module does not comply with CE UL or cUL standards a resistance load of 2 A per point or an inductive load of 80 VA or less 100 V AC or 200 V AC can be driven For the life of the contact for s...

Страница 115: ...e load Select a surge absorber with voltage rating that is suitable for the output used For other specifications refer to the following Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external interlock should be provided for interlocking along with an interlock in the PLC program as shown below In phase PLC outpu...

Страница 116: ...rent Current of 0 3 A can flow per one output point However current of four output points should be 0 8 A average of 0 2 A per one point to suppress temperature rise When a load with a high rush current is frequently turned on or off the mean square current should be 0 2 A or less Open circuit leakage current C R absorbers are connected in parallel at the triac output terminal for turning off the ...

Страница 117: ...low In phase PLC output contacts 1 should be used in an in phase manner C R absorbers are connected in parallel at the triac output circuit for turning off the triac When a minute current load of 0 4 VA or less 100 V AC or 1 6 VA or less 200 V AC is connected a surge absorber must be connected in parallel with the load Select a surge absorber with the rated voltage that is suitable for the output ...

Страница 118: ...r output Sink output type 1 represents a vacant terminal 5 30 V DC Fuse Load Y0 COM0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 MC1 MC2 MC2 MC1 COM0 Inductive load Fuse Fuse Fuse Load Y0 COM0 Y1 Y2 Y3 COM0 FX5UC 32MT D FX5 C32EYT D Fuse Load Y0 Y1 Y2 Y3 FX5 16EYT ES COM0 FX5 CNV IFC 1 ...

Страница 119: ...rce output type 1 represents a vacant terminal Load Y0 V0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 MC1 MC2 MC2 MC1 V0 Inductive load Load Y0 V0 Y1 Y2 Y3 V0 FX5UC 32MT DSS FX5 C32EYT DSS Load Y0 Y1 Y2 Y3 FX5 16EYT ESS V0 FX5 CNV IFC Fuse Fuse Fuse 1 5 30 V DC ...

Страница 120: ... 6 Output Wiring Relay output 1 represents a vacant terminal 24 V DC Fuse Load Y0 COM0 Y1 COM0 FX5UC 32MT D Fuse COM0 Y0 Y1 Y2 Y3 FX5 8EYR ES COM1 Y4 Y5 Y6 Y7 Fuse AC power supply 100 to 240 V FX5 CNV IFC Load 1 Load ...

Страница 121: ...DSS 1 Replace this number with the one of the connected connector 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 COM0 24 V DC MC1 MC2 COM COM COM COM COM COM COM COM 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse Fuse Fuse 1 Output number of PLC 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 V0 24 V DC MC1 MC2 COM COM COM COM COM...

Страница 122: ...relay output contacts FX 16EYT TB Connectable models FX5UC MT D FX5 C EYT D FX5 C32ET D For external wiring precautions refer to Page 110 Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse 0 to 7 Smaller numbers 0 to 7 Larger numbers PLC output No Relay power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24...

Страница 123: ... C EYT DSS FX5 C32ET DSS For external wiring precautions refer to Page 110 Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse PLC output No Photocoupler power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse PLC output...

Страница 124: ... Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 U U U U U 24 V DC Surge absorbers are connected to each output Fuse Fuse Fuse Load Fuse PLC output No Photocoupler power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 U U U U U 24 V DC Surge absorber...

Страница 125: ...ction Blocks Positioning function For wiring examples for the positioning function refer to MELSEC iQ F FX5 User s Manual Positioning Control CPU module built in High speed pulse input output module Communication function For wiring of the built in RS 485 communication terminal blocks and communication adapters refer to the following MELSEC iQ F FX5 User s Manual Serial Communication MELSEC iQ F F...

Страница 126: ... Operation mode CH1 CPU module or CH9 high speed pulse input output module 1 phase 1 input S W Invalid Invalid Normal mode FX5UC 32MT D COM X0 A phase B phase Z phase 0 V 24 V Rotary encoder Class D grounding Fuse FX5 16ET ES H FX5UC 32MT D 24 V DC FX5UC 32MT D COM 0 V 24 V Rotary encoder Class D grounding Fuse 24 V DC FX5 CNV IFC FX5 16ET ES H X0 S S 1 5 k 1 1 1 5 k A phase B phase Z phase FX5UC ...

Страница 127: ...24 V DC X3 COM X2 FX5UC 32MT D FX5 16ET ES H FX5UC 32MT D 0 V 24 V Rotary encoder Fuse 24 V DC COM X3 X2 FX5 CNV IFC FX5 16ET ES H S S Class D grounding 1 Class D grounding 1 1 5 k 1 5 k A phase B phase Z phase A phase B phase Z phase 1 The grounding resistance should be 100 or less FX5UC 32MT DSS 0 V 24 V Rotary encoder Fuse 24 V DC X3 COM0 X2 FX5UC 32MT DSS Sink input wiring FX5 16ET ESS H FX5UC...

Страница 128: ...00 or less 1 The grounding resistance should be 100 or less 3 wire sensor of PNP open collector transistor output 1 The grounding resistance should be 100 or less Fuse 24 V DC X0 COM 3 wire type FX5UC 32MT D FX5UC 32MT D FX5 16ET ES H Fuse 24 V DC COM 3 wire type FX5UC 32MT D X0 FX5 CNV IFC FX5 16ET ES H S S Class D grounding 1 Class D grounding 1 1 5 k 1 5 k FX5UC 32MT DSS Fuse 24 V DC X0 COM0 3 ...

Страница 129: ... 32MT D Source wiring The example is the wiring for the input output of the FX5UC 32MT DSS 1 The grounding resistance should be 100 or less DSW SM400 X10 Y10 D100 K1 COM X10 X11 X12 X13 X15 X14 X16 X17 COM0 Y10 Y11 Y12 Y13 Sink input FX5UC 32MT D 1 2 4 8 103 102 101 100 103 102 101 100 Transistor output sink COM0 Fuse 24 V DC 1 Digital switch of BCD 0 1 A 50 V diode is necessary Class D grounding ...

Страница 130: ... Blocks Example of program Example of wiring Sink wiring The example is the wiring for the input output of the FX5UC 32MT D Source wiring The example is the wiring for the input output of the FX5UC 32MT DSS 1 The grounding resistance should be 100 or less BIN SM400 K2X10 D102 COM X10 X11 X12 X13 X15 X14 X16 X17 1 2 4 8 1 2 4 8 101 100 Fuse 24 V DC Class D grounding 1 FX5UC 32MT D COM0 X10 X11 X12 ...

Страница 131: ...Y11 Y12 Y13 Y14 Y15 Y16 Y17 M30 M31 M32 M33 M34 M35 M36 M37 M40 M41 M42 M43 M44 M45 M46 M47 M50 M51 M52 M53 M54 M55 M56 M57 Transistor output sink X11 X13 X15 X17 X12 X14 X16 X11 X13 X15 X17 X12 X14 X16 Fuse 24 V DC Class D grounding 1 COM0 Sink input FX5UC 32MT D 0 1 A 50 V diode is necessary When the input points X0 to X17 are used connect a pull up resistor 3 3 k 0 5 W COM0 X10 V0 X11 X12 X13 X...

Страница 132: ...ce wiring The example is the wiring for the input output of the FX5UC 32MT DSS 1 Use a 7 segment display with a latch and a built in BCD decoder SEGL SM400 D100 Y10 K1 103 102 101 100 1 2 4 8 103 102 101 100 1 2 4 Y10 COM0 Y11 Y12 Y13 Y14 Y15 Y16 Y17 8 Transistor output sink 1 COM0 FX5UC 32MT D Signal 7 segment display Y COM1 PLC 7 segment display used for sink wiring for transistor output Fuse In...

Страница 133: ...e is the wiring for the input output of the FX5UC 32MT DSS BCD SM400 D100 K2Y10 Y10 COM0 Y11 Y12 Y13 Y14 Y15 Y16 Y17 1 2 4 8 1 2 4 8 8 4 2 1 8 4 2 1 Signal 7 segment display Y COM1 PLC 7 segment display used for sink wiring for transistor output COM0 FX5UC 32MT D Transistor output sink Fuse Internal circuit Y10 V0 Y11 Y12 Y13 Y14 Y15 Y16 Y17 1 2 4 8 1 2 4 8 8 4 2 1 8 4 2 1 V0 FX5UC 32MT DSS Transi...

Страница 134: ...l Procedure until operation The procedure until operation is explained below 1 Turn on the power of the system Check the following items before turning on the power of the system When the CPU module with the factory default setting is powered on the ERR LED flashes because the module has no programs The power connector is connected correctly The power supply voltage is within the specified range T...

Страница 135: ...ersonal computer are shown below Ethernet connection Ethernet port direct connection GX Works3 settings For the FX5 CPU module the Ethernet adapter on the personal computer side used for the Ethernet port direct connection can be specified Click the CPU Module Direct Coupled Setting button on the Specify Connection Destination Connection window to display the CPU Module Direct Coupled Setting wind...

Страница 136: ... the RUN instruction Page 135 Running Stopping and Resetting If any error is detected the ERR LED flashes or lights up Monitoring and debugging The ON OFF status of PLC s devices current values or set values can be monitored or changed by using engineering tools For details refer to GX Works3 Operating Manual No Item Selection item Internal setting Input value 1 PC side I F Serial USB RS 232C COM ...

Страница 137: ...status of the CPU module can be changed externally with the RUN STOP RESET switch set to the RUN position The operation status of the CPU module can be set to the PAUSE status Remote operation can be performed by either of the following methods Using contacts MELSEC iQ F FX5 User s Manual Application Using engineering tools GX Works3 Operating Manual Using external devices using SLMP MELSEC iQ F F...

Страница 138: ...s normal Page 141 Checking with LEDs User s manuals for each module Item Inspection item Description 1 Ambient environment Operating ambient temperature The temperature in the panel should be 20 to 55 1 Operating ambient humidity The humidity in the panel should be 5 to 95 RH Working atmosphere Free from corrosive or flammable gas and excessive conductive dust 2 Power supply voltage Voltage within...

Страница 139: ... CPU module during shipment from the factory To use the battery attach it following the procedure below Parameter setting is required to back up the device memory and clock data using the battery Page 138 Setting an optional battery using the engineering tool Attachment procedure 1 Turn the power supply off 2 Remove the battery cover A in the figure below 3 Push the battery into the battery holder...

Страница 140: ... When the battery voltage is low the BAT LED on the panel flashes red while the power is on and SM51 SM8005 and SM52 SM8006 turn ON The memory can be retained for about one month after the LED turned on However the drop in battery voltage may not be detected immediately Prepare a new battery and replace the battery with new one promptly Standard life of FX3U 32BL 5 years at ambient temperature of ...

Страница 141: ...connect the battery connector B in the figure below from the old battery and remove the battery from the battery holder C in the figure below 4 Install the new battery Page 137 Battery attachment 5 Attach the battery cover After replacing the battery check whether the devices set by the latch and clock data are backed up correctly confirm safety and then run the PLC If the devices set by the latch...

Страница 142: ...en the battery voltage is less than the specified value The special relay turns OFF when the battery voltage returns is normal SM51 SM8006 The special relay turns ON when the battery voltage is less than the specified value The special relay status ON even when the battery voltage is normal SD8005 Battery voltage can be monitored SM52 SM8005 Battery low voltage Y1 is output when a battery low volt...

Страница 143: ... the cause of the error and take corrective actions 9 2 Checking with LEDs Check the module status with LEDs as a means to perform the primary diagnosis Checking the PWR LED If the PWR LED is turned off check the following items If the PWR LED still does not turn on even after the items shown above are checked there may be a hardware issue Consult your local Mitsubishi Electric representative Chec...

Страница 144: ...D flashes Set the CPU module to the STOP status and turn on the power supply again When the ERR LED turns off a watchdog timer error has probably occurred Take any of the following measures Review the program and avoid the maximum value SD524 SD525 of the scan time exceeding the setting value of the scan time monitoring time which was set with parameters Check that the input used for input interru...

Страница 145: ...ing generated and its detailed information Information required for troubleshooting such as the current error details and cause of the error and action to be taken are displayed The incorrect parameter setting and program error location can also be identified by selecting the error and clicking the Error Jump button On the Module Information List tab the LED status and the switch status of the tar...

Страница 146: ... be displayed the error cause can be identified based on the errors The displayed information can also be saved in CSV file format Diagnostics Module diagnostics CPU Diagnostics Event History button Use the event history function to identify the cause of failure that occurred in facilities or devices For details on this function and collected information refer to the following MELSEC iQ F FX5 User...

Страница 147: ... Page 146 Canceling Errors Operation settings of the CPU module on occurrence of an intelligent function module error The operation of the CPU module on occurrence of an intelligent function module error can be set with an engineering tool Configure the settings with I O Assignment Setting in the system parameters Error status Program execution status Description Required action Major error Stop T...

Страница 148: ...s and buffer memory using the engineering tool is explained below Online Read from PLC 1 Click the Device Memory check box 2 Click Detail 3 Input character strings in Device Data Name and select the devices to back up 4 Select the Buffer Memory Intelligent Module No and input module number 5 Click OK and then click Execute to read the data from the PLC 9 6 Canceling Errors Only continuable errors ...

Страница 149: ...5UC MT D Remove the external wiring and short circuit the COM terminal and the input terminal Check that the input turns on with LEDs and peripheral devices When the input turns on Check that the input device does not have a built in diode or parallel resistance If so refer to Page 100 Precautions for connecting input devices When the input does not turn on Remove the external wiring and measure t...

Страница 150: ...ails on the boot operation refer to MELSEC iQ F FX5 User s Manual Application Boot operation Boot operation cannot be performed from the SD memory card If the boot operation cannot be performed even after the items shown above are checked there may be a hardware issue Consult your local Mitsubishi Electric representative Item to check Action Check if a password is not registered Authenticate a pas...

Страница 151: ...U module Check on the module front surface The year and month of production of the product can be checked from the manufacturer s serial number LOT on the front at the bottom of the CPU module FX5UC 32MT D 24VDC OUT 5 30VDC MAC 0 1A 5W MAX 1 5 1 0 0 0 1 Right side Example nameplate manufacturer s serial number 1510001 Actual product nameplate differs from the example shown above 5 1 1 0 0 0 Contro...

Страница 152: ...Models FX5 manufactured from October 1st 2014 FX5 8EX ES FX5 8EYR ES FX5 8EYT ES FX5 8EYT ESS FX5 16EX ES FX5 16EYR ES FX5 16EYT ES FX5 16EYT ESS FX5 232ADP FX5 485ADP FX5 CNV BUS from January 1st 2015 FX5UC 32MT D FX5UC 32MT DSS FX5 C32EX D FX5 C32EYT D FX5 C32ET D FX5 C32EX DS FX5 C32EYT DSS FX5 C32ET DSS FX5 4AD ADP FX5 4DA ADP FX5 CNV BUSC FX5 CNV IFC from October 1st 2015 FX5UC 64MT D FX5UC 6...

Страница 153: ...manufactured after April 1st 2018 are compliant with EN61131 2 2007 and EN61010 2 201 2013 1 1 For some models PLCs manufactured in March 2018 are compliant with LVD directive successively from October 1st 2014 FX5 8EYR ES FX5 16EYR ES from May 1st 2016 FX5 32ER DS from October 1st 2016 FX5 16ER ES Compliance with LVD directive Remarks EN61131 2 2007 Programmable controllers Equipment requirements...

Страница 154: ...ordance with the following precautions Use EN60947 1 or EN60947 3 standards Place the cutoff device so that it can be operated easily Specify that the cutoff device is for this equipment 1 For the time of compliance with the LVD directive EN61010 2 201 2013 refer to Page 151 Requirement for Compliance with LVD directive Caution for when analog products are used It is recommended to perform the fol...

Страница 155: ...cket of a shielded twisted pair cable as shown below and ground as much of the exposed shield as possible to both sides of the cables Connect a ferrite core to both ends of the cable Ferrite core used in tests by Mitsubishi ZCAT2035 0930A manufactured by TDK Co The control cabinet must be conductive Ground the control cabinet with the thickest possible grounding cable To ensure that there is elect...

Страница 156: ...ng closing of the control panel or other reasons condensation may occur which may cause a fire fault or malfunction Furthermore use an air conditioner in dehumidifier mode to prevent condensation Related devices which cannot be used at an operating ambient temperature below 0 The following devices cannot be used at an operating ambient temperature below 0 Specifications when used at an operating a...

Страница 157: ...ink and source input type FX5 C16EX DS 24 V DC 16 Connector FX5 C32EX DS 24 V DC 32 Connector FX5 C32EX DS TS 24 V DC 32 Spring clamp terminal block Model Input Output Input output connection type Type No of points Common wiring system Type No of points Common wiring system Input extension sink and source input type FX5 8EX ES 24 V DC 8 Screw terminal block FX5 16EX ES 24 V DC 16 Screw terminal bl...

Страница 158: ...8 Screw terminal block FX5 16EYR ES Relay 16 Screw terminal block Output extension sink output only FX5 8EYT ES Transistor 8 Screw terminal block FX5 16EYT ES Transistor 16 Screw terminal block Output extension source output only FX5 8EYT ESS Transistor 8 Screw terminal block FX5 16EYT ESS Transistor 16 Screw terminal block Model Input Output Input output connection type Type No of points Common w...

Страница 159: ... extension sink and source input relay output type DC power supply DC input type FX5 32ER DS 24 V DC 16 Relay 16 Screw terminal block Input output extension sink and source input sink output only DC power supply DC input type FX5 32ET DS 24 V DC 16 Transistor 16 Screw terminal block Input output extension sink and source input source output only DC power supply DC input type FX5 32ET DSS 24 V DC 1...

Страница 160: ...ly 5 V DC supplied from PLC Current consumption 5 V DC FX5 C16EX 100 mA FX5 C32EX 120 mA FX5 8EX ES 75 mA FX5 16EX ES 100 mA Current consumption 24 V DC FX5 C16EX 65 mA 1 FX5 C32EX 130 mA 1 FX5 8EX ES 50 mA 1 FX5 16EX ES 85 mA 1 Item Specifications Voltage rating 24 V DC supplied from PLC 5 V DC supplied from PLC Current consumption 5 V DC FX5 C16EYT 100 mA FX5 C32EYT 120 mA FX5 8EY 75 mA FX5 16EY...

Страница 161: ...4 V DC Power consumption 1 25 W 24 V DC built in power supply 310 mA 5 V DC built in power supply 965 mA Item Specifications Voltage rating 24 V DC supplied from external power supply 5 V DC supplied from PLC Current consumption 5 V DC 100 mA Current consumption 24 V DC 125 mA The current of the input circuit is included 1 Item Specifications Exterior color Munsell 0 6B7 6 0 2 Mass weight FX5 C16E...

Страница 162: ...4 V DC FX5 16ET E H 5 3 mA 24 V DC Input impedance Other than FX5 16ET E H 5 6 k FX5 16ET E H 4 3 k Input sensitivity current ON Other than FX5 16ET E H 3 0 mA or more FX5 16ET E H 3 5 mA or more OFF 1 5 mA or less Input response frequency FX5 16ET E H X0 to 5 200 kHz X6 X7 10 kHz Input response time Other than FX5 16ET E H ON 50 s or less OFF 150 s or less FX5 16ET E H X0 to X5 ON 2 5 s or less O...

Страница 163: ...FX5 16ER ES FX5 16ET E FX5 32E D Item Specifications Photocoupler X COM 24 V DC Photocoupler Photocoupler Source input wiring X COM Sink input wiring X COM 24 V DC 24 V DC Photocoupler Photocoupler Source input wiring X S S Sink input wiring X S S 24 V DC 24 V DC Photocoupler Photocoupler Source input wiring X S S Sink input wiring X S S 24 V DC 24 V DC ...

Страница 164: ... is switched with the DISP switch IN OUT Max load FX5 C EYT D TS FX5 C32ET D S TS 0 1 A point The total load current of resistance loads per common terminal should be the following value 8 output points common terminal 0 8 A or less FX5 EYT ES FX5 16ET ES FX5 32ET DS FX5 16ET ES H 0 5 A point The total load current of resistance loads per common terminal should be the following value 4 output poin...

Страница 165: ...n Photo coupler insulation Indication of output operation LED is lit when output is on With FX5 C32EYT DSS the lower number higher number order is switched with the DISP switch F L With FX5 C32ET DSS the input output is switched with the DISP switch IN OUT Max load FX5 C EYT DSS TS FX5 C32ET DSS TS 0 1 A point The total load current of resistance loads per common terminal should be the following v...

Страница 166: ...FX5 EYT ESS FX5 16ET ESS FX5 32ET DSS 0 2 ms or less 200 mA at 24 V DC FX5 16ET ESS H Y0 Y1 Y4 Y5 2 5 s or less 10 mA at 5 24 V DC Y2 Y3 Y6 Y7 0 2 ms or less 200 mA at 24 V DC Maximum frequency FX5 16ET ESS H Y0 Y1 Y4 Y5 200 kpps Voltage drop when ON 1 5 V or less Y0 Y1 Y4 and Y5 of FX5 16ET ESS H is 1 0 V or less Output circuit configuration FX5 C EYT DSS TS FX5 C32ET DSS TS FX5 EYT ESS FX5 16ET ...

Страница 167: ...ith CE UL or cUL standards Output circuit insulation Mechanical insulation Indication of output operation LED is lit when output is on Max load 2 A point The total load current of resistance loads per common terminal should be the following value 4 output points common terminal 8 A or less 8 output points common terminal 8 A or less Open circuit leakage current Min load 5 V DC 2 mA reference value...

Страница 168: ...ut modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 I O display LED Lit when input or output is on 4 I O connectors Connector for connecting input signal cables or output signal cables For details on the terminal layout refer to Page 172 Terminal layout 5 DISP switch Switches the display of smaller and larger numbers of the input display LED or output displa...

Страница 169: ...ion module Model W mm FX5 8EX ES 40 FX5 8EYR ES FX5 8EYT ES FX5 8EYT ESS FX5 16EX ES FX5 16EYR ES FX5 16EYT ES FX5 16EYT ESS No Name Description 1 Input display LED output display LED Lit when input or output is on 2 POWER LED Indicates whether the input modules output modules are powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab Tab for pulling out an extension cable 4 Ex...

Страница 170: ... input signal cables For details on the terminal layout refer to Page 172 Terminal layout 5 Output connector Connector for connecting output signal cables For details on the terminal layout refer to Page 172 Terminal layout 6 DISP switch Switches input output of the I O display LED Input IN Output OUT 7 Extension connector Connector for connecting the extension connector of an extension module Mod...

Страница 171: ...X5 16ER ES FX5 16ET ES FX5 16ET ESS 40 No Name Description 1 Input display LED output display LED Lit when input or output is on 2 POWER LED Indicates whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable used to connect the extension module 5 Terminal Terminal...

Страница 172: ...splay LED Lit when output is on 6 Extension connector cover for next module Cover for protecting the extension connector cover for next module 7 Extension connector for preceding module Connector for connecting the supplied extension cable that connects to the preceding module the CPU module side 8 Terminal block mounting screws Gradually loosen the left and right screws alternatingly to remove th...

Страница 173: ...utput modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable connected to extend modules 5 Terminal Terminals for input and output For details on the terminal layout refer to Page 172 Terminal layout 6 Extension connector Connector for connecting the extension cable of an extension module Witho...

Страница 174: ... X6 X7 COM Smaller numbers Larger numbers Input X0 X1 X2 X3 X4 X5 X6 X7 S S X10 X11 X12 X13 X14 X15 X16 X17 S S Input X0 X1 X2 X3 X4 X5 X6 X7 S S X10 X11 X12 X13 X14 X15 X16 X17 S S Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Notch Input X0 X1 X2 X3 X4 X5 X6 X7 COM0 X0 X1 X2 X3 X4 X5 X6 X7 COM0 Notch Input X0 X1 X2 X3 X4 X5 X6 X7 COM0 X0 X1 X2 X3 X4 X5 X6 X7 COM0 Input X0 X1 X...

Страница 175: ...5 X6 X7 COM X0 X1 X2 X3 X4 X5 X6 X7 COM Notch Input X0 X1 X2 X3 X4 X5 X6 X7 S S X10 X11 X12 X13 X14 X15 X16 X17 S S Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 COM0 Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V1 Notch Smaller numbers Larger numbers Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 Y10 Y11 Y12 Y13 Y1...

Страница 176: ... 5 6 7 V 1 X 0 C O M 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 S S X 0 S S 1 2 3 4 5 7 6 X 0 1 2 3 4 5 6 7 Smaller numbers Larger numbers Y 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 Smaller numbers Larger numbers C O M 0 C O M 1 Y 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 Smaller numbers Larger numbers V 0 V 1 X 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 V S S Y4 2 3 V1 1 Y0 V0 5 6 7 Y0 1 2 3 Y4 5 6 7 V2 V3 FX5 32ET DSS X0 S S 1 2 ...

Страница 177: ...are the same as those for the CPU module Page 30 Generic Specifications External color weight accessories Model W mm FX5 CNV IFC 14 6 No Name Description 1 Extension connector for preceding module The extension connector that connects to the preceding module the CPU module side 2 Extension connector for next module Connector for connecting the extension connector of an extension module extension c...

Страница 178: ...iant with IEC61131 2 The SDHC memory card can be used only with devices with an SDHC logo or whose user s manual lists an SDHC logo Note that SDHC cards cannot be used with devices that support only SD specifications Turning off or resetting the CPU module or removing the SD memory card while the card is being accessed may corrupt the data in the SD memory card Always turn off or reset the CPU mod...

Страница 179: ...n When SM605 mount and remove memory card disabling flag is ON the CARD LED is not turned OFF even if the SD memory card stop switch is pressed If the CARD LED is not turned OFF turn ON SM606 instruction of forcibly stop using SD memory card so that the SD memory card cannot be used 1 Insert the SD memory card 1 straight into the SD memory card slot Make sure that the notch of the card is directed...

Страница 180: ...D FX5 C32ET D 24 V DC 48 mA FX 16EYR TB 16 Relay output type FX5UC MT D FX5 C EYT D FX5 C32ET D 24 V DC 80 mA FX 16EYT TB 16 Transistor output type sink 24 V DC 112 mA FX 16EYS TB 16 Triac output type Sink and source common input source output transistor output FX 16E TB UL 16 input points or 16 output points Directly connected to I O terminals of a PLC FX5UC MT DSS FX5 C EX DS FX5 C EYT DSS FX5 C...

Страница 181: ...t sensitivity ON 3 8 mA 80 V AC or more OFF 1 7 mA 30 V AC or less Input response time 1 25 to 30 ms Input signal format Input sensor form Voltage contact Input circuit insulation Photo coupler insulation Indication of input operation No input LED However the 24 V power LED display exists Power consumption 1 2 W 48 mA 24 V DC Input output configuration circuit Unsupported applications High speed c...

Страница 182: ...lation Mechanical insulation Indication of output operation LED is lit when the power is supplied to relay coils Power consumption 1 92 W 80 mA 24 V DC Input output configuration circuit FX 16EYR TB FX 16EYR ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O fu...

Страница 183: ...r insulation Indication of output operation LED is lit when the power is supplied to photo couplers Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit FX 16EYT TB FX 16EYT ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O function D HIOE...

Страница 184: ...of output element 1 5 V Output circuit insulation Photo coupler insulation Indication of output operation LED is lit when the power is supplied to photo couplers Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop o...

Страница 185: ...ion Indication of output operation LED is lit when the power is supplied to photo thyristors Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit FX 16EYS TB FX 16EYS ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O function D HIOEN instr...

Страница 186: ...or connecting input signal cables or output signal cables for CN2 FX 32E TB and FX 32E TB UL only 3 POWER LED Indicates the conduction status FX 16EX A1 TB only Lit Powered Off Not powered or hardware error 4 Operation display LED Turns on when the output is on FX 16EYR TB FX 16EYR ES TB UL FX 16EYT TB FX 16EYT ES TB UL FX 16EYT ESS TB UL FX 16EYS TB and FX 16EYS ES TB UL only 5 Terminal block for...

Страница 187: ...5 6 7 COM COM Smaller numbers Larger numbers CN1 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Smaller numbers Larger numbers CN2 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Smaller numbers Larger numbers CN1 CN2 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM2 0 1 2 3 COM3 COM3 4 5 6 7 COM4 COM4 Smaller numbers Larger numbers 24 24 POWER 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM...

Страница 188: ...9 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 3 2 1 0 COM 7 6 5 4 3 2 1 0 CN1 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 5 4 3 2 1 0 0 COM 7 6 5 4 3 2 0 1 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 FX 16E TB FX 32E TB 1 1 1 0 to 7 Smaller numbers 0 to 7 Larger numbers 0 to 7 Smaller numbers 0 to 7 Larger numbers 5 4 1 C...

Страница 189: ... 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM0 7 6 5 4 3 2 1 0 0 COM0 7 6 5 4 3 2 0 1 1 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM0 7 6 5 4 3 2 1 0 COM0 7 6 5 4 3 2 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 FX 16E TB UL FX 32E TB UL 1 1 1 0 to 7 Smaller numbers 0 to 7 Larger numbers 0 to 7 Smaller numbers 0 to 7 Larger numbers CN2...

Страница 190: ... COM4 COM4 4 to 7 20 COM 6 7 5 4 3 2 1 0 COM 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 CN1 Photocoupler Photocoupler Photocoupler Photocoupler 0 to 3 0 to 3 4 to 7 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 0 to 7 Smaller numbers 0 to 7 Larger numbers 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM0 6 7 5 4 3 2 1 0 COM0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 1...

Страница 191: ...2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 4 5 6 7 1 1 3 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM0 6 7 5 4 3 2 1 0 COM0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3 3 k 3 3 k 3 3 k 3 3 k 2 2 2 2 0 to 7 Smalle...

Страница 192: ...V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3 3 k 3 3 k 3 3 k 3 3 k 0 to 7 Smaller numbers 0 to 7 Larger numbers 1 1 Photo coupler Photo coupler 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3...

Страница 193: ... 5 6 7 3 3 k 3 3 k U U U U U Surge absorbers are connected to each output 3 3 k 3 3 k 0 to 7 Smaller numbers 0 to 7 Larger numbers 1 1 Photo thyristor Photo thyristor Photo thyristor Photo thyristor Photo thyristor Photo thyristor 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 ...

Страница 194: ...ot include batteries when shipped from the factory Battery only spare parts and optional parts 1 Weight in packaging Precautions for transportation When transporting the product above follow IATA Dangerous Goods Regulations IMDG Code International Maritime Dangerous Goods Code and domestic transportation regulations in each country For details contact the transportation company to be used Model Ba...

Страница 195: ...ry Directive 2006 66 EC Article 20 Information for end users and Annex II Exportation precautions The new EU Battery Directive 2006 66 EC requires the following when marketing or exporting batteries and or devices with built in batteries to EU member states To print the symbol on batteries devices or their packaging To explain the symbol in the manuals of the products Labeling To market or export ...

Страница 196: ...supported from CPU module serial No 16Y and later Add Change Function Supported CPU module firmware version Supported engineering tool software version Reference High speed input output module is supported 1 030 and above 1 025B and above Page 47 FX5 CCLIEF is supported 1 030 and above 1 025B and above Page 48 Event history is supported 1 040 and above 1 1 030G and above Page 144 FX5 80SSC S is su...

Страница 197: ...splay LED 27 Input connector 27 Input display LED 28 Input terminal 28 Installation Location 75 Installing directly 80 M Memory capacity 35 N Nameplate 28 Number of input output points 53 O Operation status display LED 27 Output connector 28 Output display LED 28 Output terminal 28 P P RUN LED 27 Power connector for CPU module 29 PWR LED 27 R RD LED 27 Remote I O points 59 RS 485 terminal resistor...

Страница 198: ...VANT MANUALS TERMS Section 2 6 3 1 3 3 4 1 4 2 6 5 6 6 9 1 9 3 Appendix 2 4 6 10 April 2017 F Added models FX5 8AD FX5 4LC FX5 20PG P FX5 CCL MS FX5 ASL M Added or modified parts SAFETY PRECAUTIONS RELEVANT MANUALS TERMS Section 3 1 3 3 4 1 4 3 4 5 Appendix 10 August 2017 G Added models FX5UC 32MT DS TS FX5UC 32MT DSS TS FX5 C32EX DS TS FX5 C32EYT D TS FX5 C32EYT DSS TS FX5 C32ET DS TS FX5 C32ET D...

Страница 199: ...tions in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies and applications in which a special quality assurance system is required such as for railway companies or public service purposes shall be excluded from the programmable controller applications In addition applications in which human life or property that could ...

Страница 200: ...ration Anywire and ANYWIREASLINK is a trademark of Anywire Corporation MODBUS is a registered trademark of Schneider Electric SA Phillips is a registered trademark of Phillips Screw Company SD logo and SDHC logo are trademarks or registered trademarks of SD 3C LLC The company name and the product name to be described in this manual are the registered trademarks or trademarks of each company ...

Страница 201: ......

Страница 202: ...0 JAPAN Specifications are subject to change without notice When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permission Manual number JY997D61401J Model FX5UC U HW E Model code 09R558 ...

Отзывы: