![Mitsubishi Electric MELPRO MOC-A3T-R Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/mitsubishi-electric/melpro-moc-a3t-r/melpro-moc-a3t-r_instruction-manual_240696009.webp)
9
JEP0-IL9553
Shock
Maximum acceleration: 300m/s
2
Direction: 3 directions in forward/backward, right/left, and up/down
Criteria: No abnormality when applying two shocks in each direction
Insulation
resistance
Test circuit: Between all circuits and external box, between separate circuits, and between the poles of contacts
Criteria: More than 10M
Ω
by DC500V megger.
(Note) The test is held under the condition that relative humidity is less than 80%.
Withstand
voltage
Between all circuits and external box: AC2000V, for 1 minute
Between separate circuits: AC2000V, for 1 minute
Between the poles of contacts (T1-T2, a1-a2): AC1000V for 1 minute
Lightning
impulse
withstand
voltage
Apply standard waveform
(1.2/50 μs)
to positive/negative pole for 3 times respectively.
Between all circuits and external box, between mutual CT circuits, between CT circuit and control circuit: 4.5kV
Between terminals of CT circuit, between mutual control circuits (only for MOC-A3V): 3.0kV
Criteria: No abnormality
Noise-proof
Apply damped oscillatory wave prescribed in JIS C 4602 for 2 seconds.
・
Between all CT circuits and external box
・
Between all control circuits and external box
Setting: Minimum operation value and minimum operating time
Input: 80% of time-lag element operation value
Criteria: No malfunction
Radio
disturbance
Intermittently irradiate radio waves to the front panel of the relay with a transceiver of 150MHz or 400MHz
band (5W output) from a distance of 0.5m.
Setting: Minimum operation value and minimum operating time
Input: 80% of time-lag element operation value
Criteria: No malfunction
Contact capacity
Tripping
method
Voltage tripping type
Current tripping type
For trip
Making
(Closing)
DC110V 15A (L/R=0ms)
DC220V 10A (L/R=0ms)
AC110V 10A (cosφ=0.1)
Breaking
(Opening)
DC110V 0.3A (L/R=7ms)
AC110V 5A (cosφ=0.1)
AC220V 1A
(cosφ=0.1)
Breaking (Opening): AC110V 60A
The 2Ω (power factor = 0.5) loads in
parallel to the contacts
For alarm
Rating: 5A AC250V/DC24V (Resistance load)
Maximum voltage: AC400V, DC300V
Making
(Closing)
DC110V 15A (L/R=0ms)
DC220V 10A (L/R=0ms)
AC110V 10A (cosφ=0.1)
Breaking
(Opening)
DC110V 0.3A (L/R=7ms)
AC110V 5A
(cosφ=0.1)
AC220V 1A
(cosφ=0.1)
Making and breaking: AC100V 2A (cos
φ
=0.4)
DC24V 2A (L/R=7ms)
Rating: 3A AC250V/DC24V (Resistance load)
Maximum voltage: AC277V, DC30V
Note) For details, refer to JIS C 4602 (2017).