JEP0-IL9553

 

Structure 

 

 

 

 

 

 

 

 

 

 

Fig. 1-2 Structure of MOC-A3 series (front view) 

 

Operating Description

 

1.  Protection function 

The power supply can be derived from CT secondary. 

Operating time characteristics of time-lag element 

is expressed in the following formula. 

Extremely inverse (EI): 

T =

80

𝐼

2

−1

×

𝐷

10

(s)

 

Very inverse (VI): 

T =

13.5

𝐼−1

×

𝐷

10

(s)

 

Normal inverse (NI): 

T =

0.14

𝐼

0.02

−1

×

𝐷

10

(s)

 

Definite time (DT): 

T = 2 ×

𝐷

10

(s)

 

For switching step number of instantaneous element 

(2steps or 3steps) and 3rd step sensitivity (20%, 

40%, 60%, or 80% of operation value), use setting 

switches  (SW2

4).  Note  that  the  sensitivity 

setting  of  20%  is  not  allowed  if  the  operation 

value of instantaneous element is set to 10A. If 

you  do  that,  the  relay  operates  as  2-step 

characteristic. 

The  relay  calculates  and  compares  input  current 

of  each  phase  with  the  setting  value.  When  the 

relay  operates,  the  operation  indicator  turns 

according  to  the  fault  phenomena.  If  you  reset 

operation indicator, move reset lever up and down.

   

(

Operation indication) 

Fault phenomena 

Display of operation indicator 

Type 

Phase 

R-phase 

T-phase 

Inst. 

Overload 

R-S 

 

 

 

S-T 

 

 

 

T-R 

 

 

 

R-S-T 

 

 

 

Short 

circuit 

R-S 

 

 

 

S-T 

 

 

 

T-R 

 

 

 

R-S-T 

 

 

 

 

As  for  the  output  contact  of  the  relay,  once  it 

operated,  it  will  reset  in  approx.  60ms  after 

holding  when  input  current  is  less  than  the 

setting value.

 

 

Setting switches for using 
condition

 

Don't use any tool with a sharp point 
when the switches are set. 
(It  may  cause  damage  to  the  switch 
lever.) 

SW1 

Freque

ncy 

 

SW2 

Inst. 

Step No. 

ON 

50Hz 

 

ON 

3steps 

OFF 

60Hz 

 

OFF 

2steps 

 

SW3  SW4 

Inst. 

Sensitivity 

OFF  OFF 

20% 

OFF 

ON 

40% 

ON 

OFF 

60% 

ON 

ON 

80% 

 

SW5  SW6 

Time curve 

OFF  OFF 

EI 

OFF 

ON 

VI 

ON 

OFF 

NI 

ON 

ON 

DT 

Factory settings are set to a default 
of OFF. 

 

Setting switches for 
operation value and dial 

Set  the  setting  values.  The 
black part is equal to maximum 
value,  but  the  numerical 
display is turned off. 
Don't leave the switches with 
halfway state. 

RUN indicated LED (Green) 

It  shows  the  result  of  self-
monitoring.  It  lights  up  in 
normal condition. 

Operation indicator reset lever 

Move this lever up and down, then the operation 
indicator resets. 
(Note) Don't pull the lever strongly.  

Numerical display LED 

Following  item  is  displayed 
by  indicator  select  switch 
setting. 

Current measurement 

Time lapse 

Setting value 

Fault record 

Clear fault record 

Indicator select switch 

The  numerical  display  shows 
according  to  this  selection 
switch.  Don't  leave  this 
switch with halfway state. 

Operation indicator 

The  indicator  turns  from  black  into  orange  color 
when the protection element is put into operation. 

CPU reset button 

While this button is pressed, the 
relay function is locked and the 
RUN indicated LED is turned off. 

Содержание MELPRO MOC-A3T-R

Страница 1: ...1 JEP0 IL9553 Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager ...

Страница 2: ...t Failure to do so may lead to the risk of electric shock equipment failure malfunction or failure to operate Ensure that the equipment is connected correctly in accordance with the details e g polarity or phase sequence shown on the connection terminals Otherwise there is the risk of failure burning malfunction or maloperation All power supplies and transformers to the equipment must be of suitab...

Страница 3: ...el Otherwise there are risks of electric shock injury failure malfunction and maloperation Handling and maintenance of the equipment must only be carried out after gaining a thorough understanding of the instruction manual Otherwise there is the risk of electric shock injury failure malfunction or maloperation When replacing the equipment use a product of same model rating and specifications Other...

Страница 4: ... special damages and secondary damages whether foreseeable or not compensation for accidents and compensation for damages to products other than MITSUBISHI ELECTRIC CORPORATION products and other tasks 4 Applications of products 1 The user is requested to confirm the standards the regulations and the restrictions which should be applied in case of utilizing this product and another one in combinat...

Страница 5: ...ecommended to replace 2 Product supply including repair parts is not available after production is discontinued 6 Changes in product specification The specification given in the catalogue manuals or technical documents are subject to change without prior notice 7 Scope of service The technical service fee such as engineer dispatching fee is excluded in the price of our products Please contact to o...

Страница 6: ...eous sensitivity 20 SW3 OFF SW4 OFF 40 SW3 OFF SW4 ON 60 SW3 ON SW4 OFF 80 SW3 ON SW4 ON Caution If the operation value of instantaneous element is set to 10A the sensitivity setting of 20 is not allowed If you do that the relay operates as 2 step characteristic Operating time characteristics Time lag Extremely inverse EI SW5 OFF SW6 OFF Very inverse VI SW5 OFF SW6 ON Normal inverse NI SW5 ON SW6 ...

Страница 7: ...on CT Normal 3 5VA Operating 4 5VA Case Munsell color Unit fixed type Fig 1 11 0 6B7 6 0 2 Unit drawer type Fig 1 12 0 6B7 6 0 2 Unit fixed type Fig 1 11 0 6B7 6 0 2 Mass Approx 1 0kg Approx 1 1kg Approx 1 0kg shows factory setting ...

Страница 8: ...17 1 80 12 1 80 17 1 80 12 1 80 12 Instantaneous element 50ms or less Input 200 of setting value Refer to Fig 1 1 3 for characteristic example Overshoot time characteristics Time lag element Dial 10 Input 1000 of setting value Applied time 90 of theoretical operating time The relay shall not operate Temperature characteristics Time lag element Ambient temperature 20 or 60 Operation value Within 20...

Страница 9: ...for 2 seconds Between all CT circuits and external box Between all control circuits and external box Setting Minimum operation value and minimum operating time Input 80 of time lag element operation value Criteria No malfunction Radio disturbance Intermittently irradiate radio waves to the front panel of the relay with a transceiver of 150MHz or 400MHz band 5W output from a distance of 0 5m Settin...

Страница 10: ...s Current multiples to the setting I EI characteristic 2 5 20 0 25 0 5 1 1 5 2 2 5 5 10 20 Dial D 0 01 0 1 1 10 100 1000 1 10 Operating time T s Current multiples to the setting I VI characteristic 2 5 20 0 25 2 5 5 10 20 Dial D 0 5 1 1 5 2 3 3 5 4 Extremely inverse EI T 80 𝐼2 1 𝐷 10 s Very inverse VI T 13 5 𝐼 1 𝐷 10 s ...

Страница 11: ...s Current multiples to the setting I NI characteristic 2 5 20 2 5 5 10 20 Dial D 1 1 5 2 3 0 5 0 25 0 01 0 1 1 10 100 1000 1 10 Operating time T s Current multiples to the setting I DT characteristic 2 5 20 2 5 5 10 20 Dial D 1 1 5 2 3 0 5 0 25 3 5 4 6 Normal inverse NI T 0 14 𝐼0 02 1 𝐷 10 s Definite time DT T 2 𝐷 10 s ...

Страница 12: ...stics 20 40 60 80 100 120 140 160 180 200 500 450 400 350 300 250 200 150 100 50 0 Current multiples to the setting Operating time ms 20 40 60 80 100 120 140 160 180 200 500 450 400 350 300 250 200 150 100 50 0 20 40 60 80 Sensitivity setting in 3 step characteristic Current multiples to the setting Operating time ms ...

Страница 13: ...x 60ms after holding when input current is less than the setting value Setting switches for using condition Don t use any tool with a sharp point when the switches are set It may cause damage to the switch lever SW1 Freque ncy SW2 Inst Step No ON 50Hz ON 3steps OFF 60Hz OFF 2steps SW3 SW4 Inst Sensitivity OFF OFF 20 OFF ON 40 ON OFF 60 ON ON 80 SW5 SW6 Time curve OFF OFF EI OFF ON VI ON OFF NI ON ...

Страница 14: ... of larger one among two phases is recorded The relay can save the newest single phenomenon The record is saved in the non volatile memory therefore the record can be read again after shutting the power off Note that the fault record may not be saved if the input current is turned off soon after the relay operation Clearing of fault records Set indicator select switch to CLEAR FAULT REC and hold f...

Страница 15: ...it E C1R C2R C2T C1T a2 a1 D T1 T2 52a Pallet switch Auxiliary power supply Current changeover switch Tripping route When a fault occurs the trip contact between and closes then trip coil of CB is energized and make CB trip c No voltage tripping type MOC A3V R S T CB CT Load side TC1 Current changeover switch A No voltage tripping coil To alarm circuit E C1R C2R C2T C1T a2 a1 D T1 T2 Pallet switch...

Страница 16: ...onnection This figure shows the connection of current tripping type For voltage tripping type the terminal number should be changed as below T1R T1 T1T T2 C2T2R C2R C2T2T C2T Fig 1 5 Connection example Test A relay test is carried out sufficiently before shipment but at the following cases it is recommended the test should be carried out again a When the products are delivered and unpacked b At th...

Страница 17: ... setting Minimum setting 10 of setting value Instantaneous Each setting 15 of setting value Operating time Time lag 300 of setting Minimum setting Characteristic control point of operating time 17 of nominal value 700 of setting 12 of nominal value Instantaneous 200 of setting Minimum setting 50ms or less 5 Example of operation test circuit The circuit examples of the overcurrent relay test equipm...

Страница 18: ...1 a2 9 9 9 9 9 9 14 MOC A3V R MOC A3V RD C1R T1R C2 T2R C2 T2T T1T C1T a2 a1 9 5 9 5 9 5 9 5 9 5 9 5 9 5 9 5 9 5 9 5 MOC A3T R Do not connect to the terminals or the relay may not operate properly The terminal is junction terminal for grounding wire if there was grounding wire in the existing relay Fig 1 7 Terminal layout ...

Страница 19: ...t may cause electric shock or damage to the circuit Before the subunit is to be drawn out ensure that the following items are checked in order not to carry out the work in hot line condition Lock of the tripping circuit Turning off the main circuit Disconnect CT VT circuit Turning off the auxiliary power supply The CT circuit is equipped with an automatic short circuit piece so that the CT seconda...

Страница 20: ...the subunit with your finger hooked on the drawer handle on both sides Support the frame of subunit and pull out 2 Procedure of housing Drawer fixing screw Support the frame of subunit and place the subunit in the case along the rails Insert the subunit into the case horizontally Open the cover and tighten the drawer fixing screw Cover Cover ...

Страница 21: ...p the upper side of the cover from the inner surface Then remove from the protrusion of the body Installing the cover As shown in Fig 1 10 mount the holes on the upper side of the cover to the protrusion of the body Then press down lightly on the lower side of the cover and mount to the protrusion of the body in the same way as above When replacing the cover during operation be careful not to touc...

Страница 22: ...plied to the protection relay have limited lifetime which will bring the degradation to the relay The degree of degradation will be variable depending on the purpose aging usage environment and unevenness on the performance of each part Our company designs its products so that the recommended renewal period is 15 years or more However there may be some possibilities to occur any failures before re...

Страница 23: ...HEAD OFFICE 7 3 MARUNOUCHI 2 CHOME CHIYODA KU TOKYO 100 8310 JAPAN First edition Oct 2020 ...

Отзывы: