JEP0-IL9553
MOC-A3 Series Over Current Relay [Standard: JIS C 4602 (2017)]
Features
1. Various operating time characteristics.
Time-lag element: 4 types (EI, VI, NI, DT)
Instantaneous element: 2 types (2 steps, 3 steps)
2. Alert function which detects the difference between
setting frequency and injected frequency.
3. The fault value record function is installed.
4. Good operability and visibility design is adopted.
The numerical display turns on for 3 seconds when the
setting value is changed, which enables to check
setting values easily.
5. The power supply can be derived from CT secondary.
6. Panel cutout is the same as previous MELPRO-A series
and E series.
Ratings and Specifications
Type name
MOC-A3V-R
MOC-A3V-RD
MOC-A3T-R
Style No.
102PGA
518PGA
103PGA
Tripping method
Voltage tripping
Current tripping
Ratings
Phase current
5A
Frequency
50/60Hz (switchable)
Setting
Time-lag element
Operation value
LOCK
(*)
-3-3.5-4-4.5-5-6A
Dial
0.25
(*)
-0.5-1-1.5-2-2.5-3-3.5-4-5-6-7-8-9-10-20
Instantaneous element
Operation value
LOCK
(*)
-10-15-20-25-30-35-40-50-60A
Using
condi
tion
Frequency
50Hz(SW1-ON) - 60Hz
(*)
(SW1-OFF)
Instantaneous
step number
3steps(SW2-ON)
–
2steps
(*)
(SW2-OFF)
Instantaneous
sensitivity
20%
(*)
(SW3-OFF,SW4-OFF)
40% (SW3-OFF,SW4-ON)
60% (SW3-ON,SW4-OFF)
80% (SW3-ON,SW4-ON)
(Caution) If the operation value of instantaneous element is set to 10A, the
sensitivity setting of 20% is not allowed. If you do that, the relay operates
as 2-step characteristic.
Operating time
characteristics
(Time-lag)
Extremely inverse (EI)
(*)
(SW5-OFF,SW6-OFF)
Very inverse (VI) (SW5-OFF,SW6-ON)
Normal inverse (NI) (SW5-ON,SW6-OFF)
Definite time (DT) (SW5-ON,SW6-ON)
Display
Self-monitoring
The "RUN" indicator (green-color) is lighted when current exceeds 1.5A in normal
condition.
Operation indicator
R-phase, T-phase, Instantaneous: The indicator turns from black into orange
color when the protection element is put into operation.
(Manual resetting type)
Numerical display
※
1 "Lo." means LOCK setting (the protection element is locked).
※
2 This shows current sensitivity (ratio to operation value) when setting 3-
step characteristic in instantaneous element. None is displayed when
setting 2-step characteristic.
Indication item
Range
Current measurement
2.0
~
9.9A,10
~
30A
Time lapse
0
~
10
Time-lag element
current setting
Lo.
(
※
1)
,3
~
6A
Dial setting
0.25
~
20
Instantaneous element
current setting
Lo.
(
※
1)
,10
~
60A
Number of step setting
2,3 steps
Sensitivity setting
(
※
2)
20,40,60,80%
Operating time
characteristics setting
EI,VI,NI,DT
Frequency setting
50,60Hz
Fault record
3.0
~
9.9A,10
~
80A
Clear fault record
O.K.