14 / 47
JEP0-IL9537
3.2. Switch-1: Select Item Switch
There is “Select Item Switch” which is assigned by following tables.
The “Protectable items by password” column means that the password input is required for operating if
password function is activated.
Table 3-1 Select items of Switch-1 (CBV2)
Rotary
position
of Switch-1
CBV2-A02S1
Description
Related
chapters
Protectable
items by
password
1
MEASURE
Real-Time Measurement
Clause 4.1
−
2
RECORD(RMS)
Fault Record
– Measurement Value Clause 4.2
−
3
RECORD (ELE.)
Fault Record
– Relay Element
Clause 4.3
−
4
PICK UP
Relay Element Detection before Trip Clause 4.4
−
5
DISP. (SET.)
Display Relay Element Setting
Clause 4.5
−
6
−
No assigned
7
SETTING
Change Relay Element Setting
Clause 4.6
○
8
FORCED OP.(TRIP)
Forced Operation for Trip Digital
Output
Clause 4.7
○
9
FORCED OP.(
U<
)
Forced Operation for Relay Element
(Undervoltage)
Clause 4.8
○
10
FORCED OP.(
U>
)
Forced Operation for Relay Element
(Overvoltage)
Clause 4.8
○
11
−
No assigned
12
−
No assigned
13
RECORD RESET
Clear Fault Record Data
Clause 4.9
○
14
DISP.(ERR.CODE)
Display Error Code by
Self-Diagnosis
Clause 4.10
−
15
ERR.CODE RESET
Clear Error Code
Clause 4.11
○
16
−
No assigned
Table 3-2 Select items of Switch-1 (COC4)
Rotary
position
of Switch-1
COC4-A02S1
Description
Related
chapters
Protectable
items by
password
1
MEASURE
Real-Time Measurement
Clause 4.1
−
2
RECORD(RMS)
Fault Record
– Measurement Value Clause 4.2
−
3
RECORD (ELE.)
Fault Record
– Relay Element
Clause 4.3
−
4
LAPSE
Relay Element Detection before Trip Clause 4.4
−
5
DISP. (SET.)
Display Relay Element Setting
Clause 4.5
−
6
−
No assigned
7
SETTING
Change Relay Element Setting
Clause 4.6
○
8
FORCED OP.(TRIP)
Forced Operation for Trip Digital
Output
Clause 4.7
○
9
FORCED OP.(
I>
)
Forced Operation for Relay Element
(Time Overcurrent, 51)
Clause 4.8
○
10
FORCED OP.(
I>>
)
Forced Operation for Relay Element
(Instantaneous Overcurrent, 50)
Clause 4.8
○
11
FORCED OP.(
I >
)
Forced Operation for Relay Element
(Ground Overcurrent, 50N, 51N)
Clause 4.8
○
12
−
No assigned
13
RECORD RESET
Clear Fault Record Data
Clause 4.9
○
14
DISP.(ERR.CODE)
Display Error Code by
Self-Diagnosis
Clause 4.10
−
15
ERR.CODE RESET
Clear Error Code
Clause 4.11
○
16
−
No assigned
Содержание MELPRO CBV2 -A02S1
Страница 1: ...1 47 JEP0 IL9537 Numerical Relay MELPROTM S Series MODEL CBV2 A02S1 COC4 A02S1 OPERATION MANUAL ...
Страница 46: ...46 47 JEP0 IL9537 ...
Страница 47: ...47 47 JEP0 IL9537 ...
Страница 48: ...48 48 JEP0 IL9536 HEAD OFFICE 7 3 MARUNOUCHI 2 CHOME CHIYODA KU TOKYO 100 8310 JAPAN Revised in Jan 2019 ...