10 / 47
JEP0-IL9537
2. Relay Specification
In this section, the relay specification such as the rating and relay element is explained.
2.1. General specification (CBV2-A02S1)
Table 2-1 General specification (CBV2-A02S1)
Name
Over/Undervoltage Relay
Relay Model
CBV2-A02S1
Style
563PQB
Elements
Protection
Undervoltage element (27)
Overvoltage (59)
Rating
Frequency
50Hz / 60Hz (selectable)
Voltage
AC110V
Aux. power
supply
Voltage
AC100V
– 110 V
DC100V
– 125 V *1
Operative range
AC: 85
–126.5 V
DC: 85-143 V *1
Setting
Undervoltage
element
Operation value LOCK
– 60~120 V (1 V step) *2
Operation time
INST - 0.1~ 5.0 s (0.1 s step)
TEST MODE
OFF
– AB – BC – CA
Overvoltage
element
Operation value LOCK
– 120~165 V (1 V step) *2
Operation time
INST - 0.1~ 5.0 s (0.1 s step)
Forced
operation
Trip and control (annunciator) contacts can be forced to operate.
Operation
indication
Operation indicator LED comes on when the relay element operates.
LED indication: Undervoltage element, Overvoltage element, AB-Phase, BC-Phase, CA-Phase
Display
RUN LED (green)
Indicate the result of automatic self-diagnosis. This LED is turned
on for normal and turned off for abnormal.
ALARM LED (red)
Indicate the result of automatic self-diagnosis. This LED is turned
off for normal and turned on for abnormal.
Self-diagnosis
(ALARM)
An electronic circuit and a built-in power supply are always supervised, and it outputs to the
RUN/ALARM LED and an ALARM contact.
Burden
Phase Circuit
0.5 VA or less (with rated current)
Auxiliary supply
For 110 VDC: approx. 1.6W
For 110 VAC: approx. 1.9VA
Output Contact Configuration For trip
Normally open contact
For control
Normally open contact (for 27 and 59)
For alarm
Normally close contact
Capacity
For trip
Make:
110 VDC, 15 A, 0.5 s (L/R=0 s)
220 VDC, 10 A, 0.5 s (L/R=0 s)
Brake:
110 VDC, 0.3 A (L/R
≦
40 ms)
220 VDC, 0.15 A (L/R
≦
40 ms)
Continuation: 1.5 A
For control and
alarm
Make:
10 VA (cos
= 0.4)
10 W (L/R = 0.007 s)
Case/Cover
Color: N1.5
Mass
approx. 1.2 kg
*1: When DC125 V is used, please note that the maximum voltage of operation range is still 143V.
(A maximum is not 125 V x 30 %.)
*2: If it sets to LOCK, the protection element will be in a lock state of operation.
Содержание MELPRO CBV2 -A02S1
Страница 1: ...1 47 JEP0 IL9537 Numerical Relay MELPROTM S Series MODEL CBV2 A02S1 COC4 A02S1 OPERATION MANUAL ...
Страница 46: ...46 47 JEP0 IL9537 ...
Страница 47: ...47 47 JEP0 IL9537 ...
Страница 48: ...48 48 JEP0 IL9536 HEAD OFFICE 7 3 MARUNOUCHI 2 CHOME CHIYODA KU TOKYO 100 8310 JAPAN Revised in Jan 2019 ...