4.7. Forced Operation for Trip Digital Output [FORCED OP. (TRIP)]
The “FORCED OP. (TRIP)” function offers operating a digital output of the trip contact.
If password function is enabled, please refer to clause 4.6.1. Following operation steps shows the condition
after inputting correct password.
If password function is not used, the condition directly goes to following steps.
Turn Switch-1 to “FORCED
OP. (TRIP)” (position 8).
The “EL1” is indicated.
This means that the digital
output for the trip contact
can be operated.
Push
“PORCED OPERATION”
button.