13
2. Trouble criterion of main parts
MCFZ-A12WV -
MCFZ-A18WV -
MCFZ-A24WV -
E1
E1
E1
Check of indoor fan motor
A
Indoor fan does not operate.
Turn OFF power supply.
Check connector (Fan motor) visually.
Replace the indoor fan motor.
Disconnect lead wires from connector (Indoor fan motor).
Measure resistance between lead wires No.1 and No.4 and then No.3 and No.4 of the indoor fan
motor.
Are lead wires connected?
Reconnect the lead wires.
Is soldered point of the connector
correctly soldered?
Replace the indoor electronic control
P.C. board.
Resolder it.
Is resistance 0 (short circuit) or
∞
(open circuit)?
Yes ( 0 or
∞
)
No
(others)
Yes
No
Yes
No
Measure the resistance between the terminals with a tester.
(Part temperature 10°C ~ 30°C)
Room
temperature
thermistor (RT11)
Part name
Indoor coil
thermistor (RT12)
Indoor fan
motor
(MF)
INNER FUSE
145
i
2
:
CUT OFF
Check method and criterion
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Figure
Normal
8k
Ω
~ 20k
Ω
Abnormal
Open or short-circuit
Vane
motor
(MV)
Measure the resistance between the terminals with a tester.
(Part temperature 10°C ~ 30°C)
Open or
short-circuit
328
~
356
Ω
BLK
RED ORN
YLW BLU BRN
WHT
GRN
YLW
FUSE
Abnormal
Normal
Color of lead
wire
BRN-other
one
YLW
GRN
ORN
BRN
RED
ROTOR
Abnormal
Open or
short-circuit
MCFZ-A24WV
80~88
Ω
44~49
Ω
35~39
Ω
43~47
Ω
13~15
Ω
Normal
MCFZ-A18WV
WHT-BLK
MCFZ-A12WV
79~87
Ω
175~190
Ω
BLK-YLW
63~69
Ω
66~72
Ω
YLW-BLU
34~38
Ω
45~50
Ω
BLU-BRN
25~29
Ω
30~33
Ω
BRN-RED
13~15
Ω
22~24
Ω
Color of lead
wire
OB344A--1.qxp 04.6.14 1:04 PM Page 13